Two factories may draw exactly the same real power, yet one needs a bigger transformer, thicker cables and pays a penalty to the utility. The difference is power factor (PF). Power factor and its correction are core topics for PGCB, BPDB, BREB/PBS, DPDC, DESCO, WZPDCL and BCS (EEE) exams and for every power-sector viva. This post explains the concept visually, then covers causes, disadvantages, correction methods and capacitor sizing with fully solved problems.
- PF = cos φ = P / S = R / Z, where φ is the angle between voltage and current.
- P (kW) does useful work, Q (kVAR) only builds magnetic/electric fields, S (kVA) is what the system must carry: S² = P² + Q².
- Low PF ⇒ more current for the same power ⇒ bigger equipment, higher I²R loss, poorer voltage regulation and penalty charges.
- Main cause: inductive loads, especially lightly loaded induction motors and transformers.
- Correction: shunt capacitors, synchronous condensers, phase advancers. Capacitor size QC = P (tan φ₁ − tan φ₂).
- Active, reactive and apparent power
- What is power factor?
- Seeing power factor (animation)
- Causes of low power factor
- Disadvantages of low power factor
- Methods of power factor correction
- Capacitor sizing formula
- Solved problems
- Most economical power factor
- One-line exam facts
- Practice MCQs
- বাংলায় দ্রুত রিভিশন
1. Active, Reactive and Apparent Power
| Quantity | Symbol & unit | Formula (single-phase) | Meaning |
|---|---|---|---|
| Active (real/true) power | P — W, kW, MW | P = V I cos φ | Power actually converted into work, heat, light |
| Reactive power | Q — VAR, kVAR | Q = V I sin φ | Power that flows back and forth to build magnetic fields (inductors) or electric fields (capacitors); average value zero |
| Apparent power | S — VA, kVA | S = V I = √(P² + Q²) | Total power the source, cables and transformers must carry |
For a balanced three-phase system multiply by √3 with line values: P = √3 VL IL cos φ, Q = √3 VL IL sin φ, S = √3 VL IL. These three form the power triangle.
2. What Is Power Factor?
Power factor is the ratio of active power to apparent power. For sinusoidal voltage and current it equals the cosine of the phase angle between them:
PF = cos φ = P / S = kW / kVA = R / Z- Lagging PF: current lags voltage — inductive loads (motors, transformers, chokes).
- Leading PF: current leads voltage — capacitive loads (capacitor banks, over-excited synchronous motors, lightly loaded long cables).
- Unity PF (= 1): current in phase with voltage — purely resistive loads (heaters, incandescent lamps), or an RLC circuit at resonance.
PF lies between 0 and 1; it is never expressed as negative — we always say “lagging” or “leading”. For non-sinusoidal (harmonic) currents, true PF = displacement PF (cos φ) × distortion factor.
3. Seeing Power Factor (Animation)
In the animation, the phase angle φ between voltage (blue) and current (orange) grows from 0° to 75°. The product p(t) = v·i is the instantaneous power. Green areas are energy delivered to the load; red areas are energy returned to the source. As φ increases, more energy sloshes back and forth, the average power (dashed line) falls, and the power triangle shows Q growing while P shrinks — even though the current magnitude stays the same.
4. Causes of Low Power Factor
- Induction motors — the largest cause in industry. They need magnetising current; PF is about 0.2–0.3 at no load and 0.8–0.9 at full load, so lightly loaded (oversized) motors are very poor.
- Transformers, especially at light load (magnetising current is a larger share of total current).
- Discharge lighting with magnetic ballasts (fluorescent tubes, mercury-vapour and sodium-vapour lamps).
- Arc furnaces, induction furnaces and welding sets.
- Variable industrial loads — at light load the reactive power stays almost constant while active power falls.
- Increased supply voltage above rated — raises magnetising current of motors and transformers.
- Harmonic-producing loads (rectifiers, drives, SMPS) reduce true PF through distortion.
5. Disadvantages of Low Power Factor
For a given power, current is inversely proportional to PF: I = P / (√3 VL cos φ). Example — a 100 kW, 400 V three-phase load draws 144 A at PF 1.0 but 241 A at PF 0.6.
- Larger kVA rating of equipment: generators, transformers and switchgear are rated in kVA = kW / cos φ, so they must be bigger and costlier.
- Larger conductor size: more current needs thicker cables and busbars.
- Higher copper losses: I²R loss ∝ 1 / cos²φ. At PF 0.6 the loss is 2.78 times that at unity PF, so efficiency drops.
- Poor voltage regulation: larger current causes more voltage drop in lines, transformers and alternators, so extra voltage-regulating equipment is needed.
- Reduced handling capacity: lines and transformers reach their current limit while carrying less useful kW.
- Penalty in electricity bill: utilities charge industrial consumers extra (or bill on kVA demand) when PF falls below the limit set in the tariff.
6. Methods of Power Factor Correction
A lagging load draws reactive power from the supply. The cure is to supply that reactive power locally with a device that draws leading current, so that the supply only needs to provide P plus a small Q.
6.1 Static capacitors (shunt capacitor banks)
Capacitors connected in parallel with the load take a leading current that cancels part of the lagging reactive current. They can be fixed (connected permanently to a motor), or switched in steps by an Automatic Power Factor Correction (APFC) panel that monitors PF and switches capacitor stages through contactors or thyristors. In three-phase systems they are usually connected in delta, because the required capacitance is one-third of that in star.
Placement: individual (at each large motor), group (at a distribution board), or central (at the main incoming bus). The closer to the load, the more of the system is relieved of reactive current.
6.2 Synchronous condenser
A synchronous motor running at no mechanical load and over-excited draws leading current and behaves like a variable capacitor. By adjusting field current, its reactive output can be varied smoothly. Used at grid sub-stations for large-scale reactive power and voltage control.
6.3 Phase advancer
An AC exciter mounted on the shaft of a large induction motor and connected in its rotor circuit. It supplies the magnetising ampere-turns at slip frequency, so the motor no longer draws magnetising current from the supply and can even run at leading PF.
Comparison
| Feature | Static capacitor | Synchronous condenser |
|---|---|---|
| Moving parts | None — little maintenance | Rotating machine — needs maintenance |
| Losses | Very low | Higher |
| Control of kVAR | In steps | Smooth, continuous |
| Can absorb kVAR (lagging)? | No | Yes (under-excited) |
| Economical range | Small to medium ratings | Large ratings (tens of MVAR and above) |
| Weak points | Damaged by over-voltage & harmonics; limited life | Noise, high initial cost |
7. Capacitor Sizing Formula
Real power P stays the same; only Q is reduced. If the PF is to be improved from cos φ₁ to cos φ₂:
QC = P (tan φ₁ − tan φ₂) kVARCapacitance needed (f = supply frequency, ω = 2πf):
- Single-phase: C = QC / (ω V²)
- Three-phase, star-connected bank: C per phase = QC / (ω VL²)
- Three-phase, delta-connected bank: C per phase = QC / (3 ω VL²)
8. Solved Problems
Problem 1 — Three-phase plant: raise PF from 0.70 to 0.95
| Given | To find |
|---|---|
| VL = 415 V, f = 50 Hz, P = 100 kW cos φ₁ = 0.70 (lag), cos φ₂ = 0.95 (lag) | QC (kVAR); C per phase for Δ and Y; current and loss saving |
Step 1 — Find the power-factor angles and their tangents
φ₁ = cos⁻¹(0.70) = 45.57° ⇒ tan φ₁ = 1.0202 φ₂ = cos⁻¹(0.95) = 18.19° ⇒ tan φ₂ = 0.3287Step 2 — Build the power triangle before correction
S₁ = P / cos φ₁ = 100 / 0.70 = 142.86 kVA Q₁ = P tan φ₁ = 100 × 1.0202 = 102.02 kVARStep 3 — Power triangle after correction (P does not change)
S₂ = P / cos φ₂ = 100 / 0.95 = 105.26 kVA Q₂ = P tan φ₂ = 100 × 0.3287 = 32.87 kVARStep 4 — Capacitor kVAR required
QC = Q₁ − Q₂ = P (tan φ₁ − tan φ₂) = 100 × (1.0202 − 0.3287) = 69.15 kVARPer phase (one capacitor of the three-unit bank):
QC,ph = 69.15 / 3 = 23.05 kVAR = 23 050 VARStep 5 — Angular frequency
ω = 2πf = 2 × 3.1416 × 50 = 314.16 rad/sStep 6 — Capacitance per phase, delta (Δ) connection
In delta, each capacitor is connected between two lines, so it sees the full line voltage VL = 415 V.
XC = VL² / QC,ph = 415² / 23 050 = 172 225 / 23 050 = 7.472 Ω CΔ = 1 / (ω XC) = 1 / (314.16 × 7.472) = 4.260 × 10⁻⁴ F ≈ 426 µF per phaseCheck with the direct formula: CΔ = QC / (3 ω VL²) = 69 150 / (3 × 314.16 × 415²) = 426 µF ✔
Step 7 — Capacitance per phase, star (Y) connection
In star, each capacitor is connected from a line to neutral, so it sees only the phase voltage.
Vph = VL / √3 = 415 / 1.732 = 239.6 V XC = Vph² / QC,ph = 239.6² / 23 050 = 57 408 / 23 050 = 2.491 Ω CY = 1 / (ω XC) = 1 / (314.16 × 2.491) = 1.278 × 10⁻³ F ≈ 1278 µF per phaseCY / CΔ = 1278 / 426 = 3 — star needs three times the capacitance, which is why delta-connected banks are preferred on LV systems.
Step 8 — Line current and loss saving
I₁ = S₁ / (√3 VL) = 142 857 / (1.732 × 415) = 142 857 / 718.8 = 198.7 A I₂ = S₂ / (√3 VL) = 105 263 / 718.8 = 146.4 A Current reduction = (198.7 − 146.4) / 198.7 = 26.3 % Loss ratio = (I₂ / I₁)² = (0.70 / 0.95)² = 0.543 ⇒ I²R loss falls by ≈ 45.7 %Capacitor-bank line current: IC = QC / (√3 VL) = 69 150 / 718.8 = 96.2 A.
kVA: 142.9 → 105.3 (−26 %) | Line current: 198.7 A → 146.4 A | Copper loss: −46 %
Problem 2 — Single-phase motor: raise PF from 0.6 to unity
| Given | To find |
|---|---|
| V = 230 V, f = 50 Hz, IM = 10 A cos φ₁ = 0.6 (lag), target cos φ₂ = 1 | QC, IC, C and the new line current I |
Step 1 — Power-factor angle
φ₁ = cos⁻¹(0.6) = 53.13° ⇒ sin φ₁ = √(1 − 0.6²) = 0.8Step 2 — Power drawn by the motor
S = V I = 230 × 10 = 2300 VA P = V I cos φ₁ = 230 × 10 × 0.6 = 1380 W Q = V I sin φ₁ = 230 × 10 × 0.8 = 1840 VAR (lagging)Step 3 — Reactive power the capacitor must supply
For unity PF, φ₂ = 0 so tan φ₂ = 0 and Q₂ = 0 — all of the motor's reactive power must be cancelled:
QC = Q₁ − Q₂ = 1840 − 0 = 1840 VARStep 4 — Capacitor current and reactance
IC = QC / V = 1840 / 230 = 8 A XC = V / IC = 230 / 8 = 28.75 ΩStep 5 — Capacitance
ω = 2π × 50 = 314.16 rad/s C = 1 / (ω XC) = 1 / (314.16 × 28.75) = 1 / 9032 = 1.107 × 10⁻⁴ F = 110.7 µFCheck with the direct formula: C = QC / (ω V²) = 1840 / (314.16 × 230²) = 1840 / 16 619 025 = 110.7 µF ✔
Step 6 — New supply current
After correction the supply only provides the active component (the capacitor provides the reactive one):
I = P / (V cos φ₂) = 1380 / (230 × 1) = 6 APhasor check: I = √[(IM cos φ)² + (IM sin φ − IC)²] = √[6² + (8 − 8)²] = 6 A ✔ — a 40 % drop from 10 A.
9. Most Economical Power Factor
Raising PF all the way to unity needs a very large capacitor bank for a small extra benefit. If x = annual cost per kVA of maximum demand (tariff charge) and y = annual cost per kVAR of the correcting equipment (interest + depreciation), the most economical PF is:
cos φ2 = √(1 − (y / x)²)This is why industries usually correct to about 0.95–0.98 lagging, not to exactly 1. Over-correction to a leading PF can cause over-voltage at light load.
10. One-Line Exam Facts
- PF of a pure resistor = 1; pure inductor = 0 lagging; pure capacitor = 0 leading.
- Series RLC circuit at resonance: PF = 1.
- Over-excited synchronous motor → leading PF; under-excited → lagging PF (V-curves / inverted V-curves).
- Wattmeter reads P; varmeter reads Q; PF meter reads cos φ.
- In the two-wattmeter method: if W₁ = W₂, PF = 1; if one reading is zero, PF = 0.5; if one reading is negative, PF < 0.5.
- Capacitor banks also raise voltage and release system capacity (kVA).
- Reactive power is measured in VAR (volt-ampere reactive).
11. Practice MCQs (click to see answer)
1. Power factor is defined as: (a) kVA/kW (b) kW/kVA (c) kVAR/kW (d) kW/kVAR
2. The main cause of low power factor in industry is: (a) Heaters (b) Incandescent lamps (c) Induction motors (d) Capacitors
3. Power factor of a purely resistive circuit is: (a) 0 (b) 0.5 (c) 1 (d) 0.707
4. Static capacitors for PF correction are connected: (a) In series with load (b) In parallel with load (c) In series with neutral (d) Across the generator field
5. An over-excited synchronous motor at no load used for PF improvement is called: (a) Phase advancer (b) Synchronous condenser (c) Reactor (d) Booster
6. Copper loss in a line is inversely proportional to: (a) cos φ (b) cos²φ (c) sin φ (d) tan φ
7. kVAR rating of capacitor to improve PF from cos φ₁ to cos φ₂ is: (a) P(tan φ₂ − tan φ₁) (b) P(tan φ₁ − tan φ₂) (c) P(cos φ₁ − cos φ₂) (d) S(sin φ₁ − sin φ₂)
8. For the same kVAR, a delta-connected capacitor bank needs capacitance per phase equal to ______ of star connection. (a) 3 times (b) 1/3 (c) √3 times (d) Same
9. A load takes 80 kW at 100 kVA. Its power factor is: (a) 0.6 (b) 0.8 (c) 1.25 (d) 0.75
10. Low power factor results in: (a) Lower line losses (b) Better voltage regulation (c) Larger kVA rating of equipment (d) Lower current
11. In the two-wattmeter method, one wattmeter reads zero. The PF is: (a) 1 (b) 0.866 (c) 0.5 (d) 0
12. Unit of reactive power is: (a) Watt (b) VA (c) VAR (d) Joule
12. বাংলায় দ্রুত রিভিশন
- পাওয়ার ফ্যাক্টর = সক্রিয় শক্তি ÷ আপাত শক্তি = kW/kVA = cos φ, যেখানে φ হলো ভোল্টেজ ও কারেন্টের মধ্যবর্তী কোণ।
- P (kW) কাজ করে, Q (kVAR) চৌম্বক ক্ষেত্র তৈরি করে, S (kVA) মোট শক্তি; S² = P² + Q²।
- কম PF-এর কারণ: আবেশ মোটর (হালকা লোডে), ট্রান্সফরমার, ফ্লুরোসেন্ট বাতির চোক, আর্ক ফার্নেস, ওয়েল্ডিং।
- অসুবিধা: একই শক্তির জন্য বেশি কারেন্ট — বড় যন্ত্র ও মোটা তার লাগে, I²R লস বাড়ে (1/cos²φ অনুপাতে), ভোল্টেজ রেগুলেশন খারাপ হয়, বিলে জরিমানা।
- সংশোধন: লোডের সমান্তরালে স্ট্যাটিক ক্যাপাসিটর, সিনক্রোনাস কনডেন্সার (অতি-উত্তেজিত সিনক্রোনাস মোটর), ফেজ অ্যাডভান্সার।
- ক্যাপাসিটরের মান: Qc = P (tan φ₁ − tan φ₂)। ডেল্টা সংযোগে স্টারের তুলনায় এক-তৃতীয়াংশ ক্যাপাসিট্যান্স লাগে।
Related Posts
- 220 Most Repeated Power Sector MCQs (PGCB, BPDB, BREB, DPDC)
- Rooftop Solar in Bangladesh: Net Metering Rules & Exam Questions
- EEE Job Viva Voce Preparation
- EEE MCQ Syllabus for Job Exams
References: V. K. Mehta & Rohit Mehta, Principles of Power System; B. L. Theraja, Electrical Technology Vol. I; IEEE Std 1459 (power definitions). Images and animations: original work by Totalecer.
Thank you for visiting my blog.