The transformer is the single most important machine in a power system: electricity generated at 11–20 kV is stepped up to 132, 230 or 400 kV for transmission and then stepped down to 33 kV, 11 kV and finally 400/230 V for your home. That is why transformer questions appear in almost every PGCB, BPDB, BREB/PBS, DPDC, DESCO, NWPGCL, EGCB and BCS (EEE) exam and viva. This guide takes you from the basic idea to the EMF equation, losses, efficiency, regulation and exam-style numericals — with animations and 15 MCQs.
- A transformer is a static device that transfers AC power from one circuit to another by mutual induction, changing voltage and current but not frequency.
- EMF equation: E = 4.44 f N Φm volts.
- Ratio: V₁/V₂ = N₁/N₂ = I₂/I₁ (ideal transformer).
- Core (iron) loss = hysteresis + eddy current, almost constant. Copper loss = I²R, varies with load².
- Maximum efficiency occurs when copper loss = core loss.
- Rated in kVA, not kW; cannot work on DC.
- What is a transformer?
- Construction
- Working principle (animated)
- EMF equation – derivation
- Turns ratio, step-up and step-down
- Ideal vs practical transformer
- Equivalent circuit – derivation
- Phasor diagrams
- Losses in a transformer
- Efficiency and maximum efficiency
- Voltage regulation
- OC and SC tests
- Per-unit system
- Solved problems
- One-line exam facts
- Practice MCQs
- বাংলায় দ্রুত রিভিশন
1. What Is a Transformer?
A transformer is a static electrical machine that transfers electrical energy from one AC circuit (primary) to another (secondary) through a common magnetic core, by the principle of mutual induction. During the transfer, the voltage and current levels change, but the frequency remains the same and the power remains almost the same (losses are only 1–3%).
- Step-up transformer: V₂ > V₁ (N₂ > N₁) — used at generating stations.
- Step-down transformer: V₂ < V₁ (N₂ < N₁) — used at grid sub-stations and distribution (e.g. 11 kV/0.415 kV).
- Since it has no rotating parts, there is no friction or windage loss, which makes its efficiency very high (95–99.5%).
2. Construction
Main parts
- Core: made of thin laminations (about 0.23–0.35 mm) of cold-rolled grain-oriented (CRGO) silicon steel (≈3% Si), insulated from each other by varnish. Silicon raises resistivity and lowers hysteresis loss; lamination reduces eddy current loss. It provides a low-reluctance path for flux.
- Windings: copper (or aluminium) coils — primary connected to the supply and secondary to the load. The LV winding is placed next to the core and the HV winding outside it, so that less insulation is needed.
- Transformer oil: mineral oil that both insulates and cools.
- Conservator (allows oil expansion), breather with silica gel (absorbs moisture from incoming air), Buchholz relay (gas-actuated protection for internal faults in oil-filled transformers with a conservator), bushings, tap changer (adjusts the turns ratio), radiators and explosion vent / pressure relief device.
Core type vs shell type
| Feature | Core type | Shell type |
|---|---|---|
| Arrangement | Windings surround the core | Core surrounds the windings |
| Magnetic circuit | Single magnetic path | Two parallel paths (double magnetic circuit) |
| Limbs | 2 limbs (1-phase) | 3 limbs; windings on the central limb |
| Cooling & repair | Easier — windings exposed | Harder |
| Leakage flux | More | Less |
| Typical use | High-voltage power transformers | Low-voltage, high-current transformers |
3. Working Principle (Animated)
The transformer works on Faraday’s law of electromagnetic induction:
- An alternating voltage V₁ is applied to the primary. It drives a small magnetising current that produces an alternating flux Φ in the core.
- This flux links both windings. Because it keeps changing, it induces an EMF in each turn: e = −N dΦ/dt.
- The EMF induced in the primary (E₁) almost balances the applied voltage (back EMF). The EMF induced in the secondary (E₂) appears at its terminals and drives current through the load.
- Since the same flux links every turn, the EMF per turn is the same in both windings, so E₁/E₂ = N₁/N₂.
4. EMF Equation of a Transformer – Derivation
Let the flux in the core be sinusoidal: Φ = Φm sin ωt, where ω = 2πf.
- Induced EMF in a winding of N turns: e = −N dΦ/dt = −N ω Φm cos ωt = N ω Φm sin(ωt − 90°)
- Maximum value: Emax = N ω Φm = 2π f N Φm
- RMS value: Erms = Emax/√2 = (2π/√2) f N Φm
So E₁ = 4.44 f N₁ Φm and E₂ = 4.44 f N₂ Φm. Here Bm is the maximum flux density (T) and Ai is the net iron area of the core (m²). The result also shows that the induced EMF lags the flux by 90°.
5. Turns Ratio, Step-Up and Step-Down
E₁/E₂ = V₁/V₂ = N₁/N₂ = I₂/I₁ = aMany Indian/Bangladeshi textbooks define the transformation ratio K = N₂/N₁ = V₂/V₁. K > 1 → step-up; K < 1 → step-down. Because input VA ≈ output VA (V₁I₁ = V₂I₂), the side with higher voltage carries lower current — that is why the HV winding uses thinner wire with more turns.
Impedance transfer: an impedance Z₂ on the secondary appears on the primary as Z₂′ = Z₂ (N₁/N₂)² = Z₂/K². This is used for impedance matching (e.g. an audio output transformer matching an amplifier to a loudspeaker).
6. Ideal vs Practical Transformer
| Ideal transformer | Practical transformer |
|---|---|
| Winding resistance = 0 | Windings have resistance R₁, R₂ → copper loss |
| No leakage flux (all flux links both windings) | Some leakage flux → leakage reactance X₁, X₂ |
| Core has infinite permeability, zero core loss | Core needs magnetising current and has hysteresis + eddy losses |
| Efficiency 100%, regulation 0 | Efficiency 95–99.5%, regulation a few percent |
At no load, a practical transformer draws a small no-load current I₀ (about 2–5% of rated current) with two components: the magnetising component Iμ (lags V₁ by 90°, produces flux) and the core-loss (working) component Iw (in phase with V₁, supplies iron loss). The no-load power factor is therefore very low (about 0.1–0.2).
7. Equivalent Circuit of a Transformer – Derivation
To calculate currents, losses, efficiency and regulation we replace the real transformer by an electric circuit that behaves the same way at its terminals. The idea is simple: start from an ideal transformer and add one circuit element for each imperfection of a practical one.
Step 1 — Put every imperfection outside an ideal transformer
- Winding resistances R₁, R₂ in series with each winding → copper loss I²R.
- Leakage reactances X₁, X₂ in series → leakage flux that links only its own winding.
- Exciting (shunt) branch R₀ ∥ X₀ across the primary → carries the no-load current I₀. R₀ draws the core-loss component Iw, X₀ draws the magnetising component Iμ:
Step 2 — Write the circuit equations
V₁ = E₁ + I₁(R₁ + jX₁) | E₂ = V₂ + I₂(R₂ + jX₂) E₂ / E₁ = N₂ / N₁ = K | I₁ = I₀ + I₁′, I₁′ = K I₂I₁′ is the load component of primary current: it flows only to cancel the mmf of I₂ (N₁I₁′ = N₂I₂).
Step 3 — Refer the secondary to the primary
We want one circuit without the ideal transformer, so every secondary quantity is replaced by an equivalent primary-side value that gives the same power / loss. For the resistance:
I₁′² R₂′ = I₂² R₂ ⇒ R₂′ = R₂ (I₂ / I₁′)² = R₂ / K²The same reasoning (equal reactive power) gives X₂′, and the voltage scales with the turns ratio:
X₂′ = X₂ / K² ZL′ = ZL / K² V₂′ = V₂ / K I₂′ = K I₂Step 4 — Approximate: move the exciting branch to the input
I₀ is only 2–5 % of rated current, so its drop in R₁ and X₁ is negligible. Shifting R₀ ∥ X₀ to the supply terminals puts R₁ in series with R₂′ and X₁ in series with X₂′:
R₀₁ = R₁ + R₂′ = R₁ + R₂ / K² X₀₁ = X₁ + X₂ / K² Z₀₁ = √(R₀₁² + X₀₁²)Step 5 — Same circuit referred to the secondary
Multiplying every primary-side impedance by K² refers it to the secondary:
R₀₂ = R₂ + K² R₁ X₀₂ = X₂ + K² X₁ Z₀₂ = K² Z₀₁8. Phasor Diagrams of a Transformer
8.1 On no load
Take the mutual flux Φ as reference. Both induced EMFs lag Φ by 90° (E = −N dΦ/dt). The supply voltage must balance −E₁, so V₁ leads Φ by 90°. The no-load current I₀ lags V₁ by φ₀ (close to 90°):
Iw = I₀ cos φ₀ (in phase with V₁) | Iμ = I₀ sin φ₀ (in phase with Φ)8.2 On load — complete diagram (lagging pf)
The diagram is built straight from the equivalent-circuit equations of section 7. The secondary drops are added to V₂ to obtain E₂; the primary current is the phasor sum of I₀ and the load component I₁′; the primary drops are added to −E₁ to obtain V₁.
8.3 Simplified diagram referred to the secondary
Neglecting I₀ and using R₀₂, X₀₂, the diagram reduces to one drop triangle on top of V₂. The resistive drop I₂R₀₂ is parallel to I₂ and the reactive drop I₂X₀₂ leads I₂ by 90°. Projecting the triangle on V₂:
₀V₂ ≈ V₂ + I₂R₀₂ cos φ + I₂X₀₂ sin φFor a leading load the I₂X₀₂ sin φ term changes sign, so the terminal voltage can rise on load — this is exactly the regulation formula used in section 11.
9. Losses in a Transformer
| Loss | Cause | Formula / depends on | How to reduce |
|---|---|---|---|
| Hysteresis loss (core) | Repeated magnetic reversal of the core | Ph = η Bm1.6 f V (Steinmetz) | Silicon steel / CRGO with narrow hysteresis loop |
| Eddy current loss (core) | Circulating currents induced in the core | Pe = Ke Bm² f² t² V | Thin insulated laminations (t small), high-resistivity steel |
| Copper loss | I²R heating of windings | Pcu = I₁²R₁ + I₂²R₂ ∝ (load)² | Thicker conductors, good design |
| Stray loss | Leakage flux inducing currents in tank/clamps | Small | Magnetic shielding |
| Dielectric loss | Insulation (oil, paper) | Very small; rises as insulation ages | Good-quality insulation |
Core (iron) loss = hysteresis + eddy current loss. It depends on voltage and frequency, which are nearly constant, so it is called the constant loss. Copper loss depends on load current, so it is the variable loss. Amorphous-metal cores (see Types of Solids) cut no-load core loss dramatically, and soft magnetic materials are chosen for their narrow hysteresis loop.
10. Efficiency and Condition for Maximum Efficiency
η = Output / (Output + Core loss + Cu loss) = x S cosφ / (x S cosφ + Pi + x² Pcu,FL)where S = rated kVA, x = fraction of full load, Pi = core loss, Pcu,FL = full-load copper loss. Differentiating η with respect to load current and setting it to zero gives:
η is maximum when Copper loss = Core loss ⇒ x = √(Pi / Pcu,FL)The animated graph below plots the numerical example from section 14 (100 kVA, Pi = 1 kW, Pcu,FL = 1.5 kW, pf 0.8). Watch the efficiency peak exactly where the copper-loss curve crosses the core-loss line:
All-day (energy) efficiency = output energy in kWh / input energy in kWh over 24 hours. Distribution transformers are energised all day but lightly loaded much of the time, so they are designed with low core loss and reach maximum efficiency at about 50–75% load. Power transformers in generating stations run near full load and are designed for maximum efficiency near full load.
11. Voltage Regulation
Voltage regulation is the change in secondary terminal voltage from no load to full load, expressed as a percentage of the full-load voltage (primary voltage held constant):
% Regulation = (V2,NL − V2,FL) / V2,FL × 100 % R ≈ (I₂R₀₂ cosφ ± I₂X₀₂ sinφ) / V₂ × 100 (+ lagging, − leading)Lower regulation is better. With a leading power factor the regulation can become zero or even negative (terminal voltage rises on load). Zero regulation occurs when tan φ = R₀₂/X₀₂ (leading pf).
12. Open-Circuit and Short-Circuit Tests
| Open-circuit (no-load) test | Short-circuit test | |
|---|---|---|
| Connection | Rated voltage on LV side, HV side open | Reduced voltage (5–10% of rated) on HV side, LV side shorted |
| Wattmeter reads | Core (iron) loss | Full-load copper loss |
| Gives | R0, X0 (shunt branch) | Req, Xeq, Zeq (series branch) |
| Why that side? | Rated LV voltage is easy to supply; current is small | Rated HV current is small and easy to measure |
13. Per-Unit (pu) System
In power-system work, voltages, currents and impedances are expressed as a fraction of a chosen base value instead of in volts, amperes and ohms:
Per-unit value = Actual value / Base value (dimensionless; × 100 gives per cent)Step 1 — Choose two bases, derive the rest
Pick a common apparent-power base Sbase (normally the rated kVA) for the whole transformer, and the rated voltage of each side as its Vbase. Current and impedance bases follow from them:
Ibase = Sbase / Vbase Zbase = Vbase / Ibase = Vbase² / SbaseFor three-phase: Ibase = Sbase(3φ) / (√3 VL,base) and Zbase = VL,base² / Sbase(3φ) — the √3 disappears from pu calculations.
Step 2 — Why the per-unit impedance is the same on both sides
Zpu,1 = Z₀₁ / Zbase1 = Z₀₁ Sbase / V₁² Zpu,2 = Z₀₂ / Zbase2 = (K² Z₀₁) Sbase / (K V₁)² = Z₀₁ Sbase / V₁² = Zpu,1 ✔The K² in the referred impedance is cancelled by the K² in the base impedance, so a transformer has one per-unit impedance and the ideal transformer vanishes from the pu circuit.
Step 3 — Per-unit impedance = short-circuit voltage
In the SC test, rated current flows when Vsc = Irated Z₀₁. Dividing by rated voltage:
Vsc / Vrated = Irated Z₀₁ / Vrated = Z₀₁ / Zbase = ZpuSo a nameplate "impedance 5 %" means 5 % of rated voltage circulates full-load current with the secondary shorted. Likewise Rpu = full-load copper loss in pu, and regulation ≈ Rpu cos φ ± Xpu sin φ.
Step 4 — Changing the base
Zpu,new = Zpu,old × (Sbase,new / Sbase,old) × (Vbase,old / Vbase,new)²Example: a 500 kVA transformer with Z = 0.05 pu on its own rating becomes 0.05 × (100 000 / 500) = 10 pu on a 100 MVA system base (same voltage).
| Advantages of the pu system | Typical transformer values |
|---|---|
| • Same pu impedance from HV or LV side — no referring needed • Values fall in a narrow range, so errors are easy to spot • Machines of very different ratings are compared directly • √3 and turns ratios drop out of 3-φ network calculations • Ideal for computer load-flow and fault studies |
• Leakage impedance: 0.04–0.10 pu (distribution ≈ 0.04–0.06) • Rpu ≪ Xpu for large units • No-load current: 0.02–0.05 pu • Full-load copper loss ≈ Rpu (e.g. 0.01 pu = 1 %) |
14. Solved Problems
Problem 1 — EMF equation: number of turns
| Given | To find |
|---|---|
| f = 50 Hz, A = 400 cm², Bm = 1.2 T V₁ = 3300 V, V₂ = 230 V | N₁, N₂ |
Step 1 — Convert the core area to m²
A = 400 cm² = 400 × 10⁻⁴ m² = 0.04 m²Step 2 — Maximum flux
Φm = Bm × A = 1.2 × 0.04 = 0.048 WbStep 3 — EMF per turn (same for both windings)
E / N = 4.44 f Φm = 4.44 × 50 × 0.048 = 10.656 V/turnStep 4 — Primary turns
N₁ = E₁ / (E/N) = 3300 / 10.656 = 309.7 ≈ 310 turnsStep 5 — Secondary turns
N₂ = E₂ / (E/N) = 230 / 10.656 = 21.6 ≈ 22 turnsStep 6 — Check
Turns are rounded up to whole numbers. With 310 and 22 turns the no-load secondary voltage is 3300 × 22/310 = 234 V — slightly above 230 V, which also allows for the voltage drop on load.
Problem 2 — Full-load and maximum efficiency
| Given | To find |
|---|---|
| S = 100 kVA, Pi = 1 kW, Pcu,FL = 1.5 kW, pf = 0.8 | ηFL; load for ηmax; ηmax |
(a) Full-load efficiency
Step 1 — Output power
Pout = S × cos φ = 100 × 0.8 = 80 kWStep 2 — Total losses at full load
Ploss = Pi + Pcu,FL = 1 + 1.5 = 2.5 kWStep 3 — Input power
Pin = Pout + Ploss = 80 + 2.5 = 82.5 kWStep 4 — Efficiency
η = Pout / Pin × 100 = 80 / 82.5 × 100 = 96.97 %(b) Maximum efficiency
Step 5 — Condition: copper loss = core loss
At a fraction x of full load, copper loss = x² Pcu,FL. Setting it equal to Pi:
x² × 1.5 = 1 ⇒ x = √(1 / 1.5) = 0.8165Step 6 — Load at maximum efficiency
Sηmax = x × 100 = 81.65 kVAStep 7 — Output and losses at that load
Pout = 81.65 × 0.8 = 65.32 kW Ploss = 1 + (0.8165² × 1.5) = 1 + 1 = 2 kWStep 8 — Maximum efficiency
ηmax = 65.32 / (65.32 + 2) × 100 = 65.32 / 67.32 × 100 = 97.03 %Problem 3 — Current ratio
| Given | To find |
|---|---|
| V₁ = 11 000 V, V₂ = 415 V, I₂ = 139 A | I₁ |
Step 1 — Power balance of an ideal transformer
V₁ I₁ = V₂ I₂ ⇒ I₁ / I₂ = V₂ / V₁ = KStep 2 — Transformation ratio
K = V₂ / V₁ = 415 / 11 000 = 0.03773Step 3 — Primary current
I₁ = K × I₂ = 0.03773 × 139 = 5.24 AStep 4 — Check with volt-amperes
V₂ I₂ = 415 × 139 = 57.7 kVA V₁ I₁ = 11 000 × 5.24 = 57.7 kVA ✔139 A is in fact the full-load line current of a 100 kVA three-phase 11 kV/415 V unit (100 000 / (√3 × 415) = 139 A); the ratio of line currents is the same, so I₁ ≈ 5.25 A in that case too.
Problem 4 — Per-unit impedance
| Given | To find |
|---|---|
| S = 50 kVA, V₁ = 2400 V, V₂ = 240 V Z₀₁ = 1.152 + j4.608 Ω | Bases, Zpu (both sides), Vsc, Pcu,FL, regulation |
Step 1 — Base values
Sbase = 50 kVA Vbase1 = 2400 V Vbase2 = 240 V Ibase1 = 50 000 / 2400 = 20.83 A Ibase2 = 50 000 / 240 = 208.3 A Zbase1 = 2400² / 50 000 = 115.2 Ω Zbase2 = 240² / 50 000 = 1.152 ΩStep 2 — Per-unit impedance from the HV side
Zpu = (1.152 + j4.608) / 115.2 = 0.01 + j0.04 puStep 3 — Refer to LV side and repeat
K = 240 / 2400 = 0.1 ⇒ Z₀₂ = K² Z₀₁ = 0.01 × (1.152 + j4.608) = 0.01152 + j0.04608 Ω Zpu = (0.01152 + j0.04608) / 1.152 = 0.01 + j0.04 pu — identical ✔Step 4 — Short-circuit test voltage
|Zpu| = √(0.01² + 0.04²) = 0.04123 pu (4.12 %) Vsc = 0.04123 × 2400 = 98.95 V (applied on HV side to circulate 20.83 A)Step 5 — Full-load copper loss
Pcu,FL = Rpu × Sbase = 0.01 × 50 = 0.5 kW (check: 20.83² × 1.152 = 500 W ✔)Step 6 — Approximate regulation at 0.8 pf lagging
Reg ≈ Rpu cos φ + Xpu sin φ = 0.01 × 0.8 + 0.04 × 0.6 = 0.032 pu = 3.2 %Problem 5 — Equivalent circuit and regulation
| Given | To find |
|---|---|
| S = 10 kVA, V₁ = 2000 V, V₂ = 200 V R₁ = 5.5 Ω, X₁ = 12 Ω, R₂ = 0.045 Ω, X₂ = 0.1 Ω, pf 0.8 lag | R₀₁, X₀₁, R₀₂, X₀₂, regulation, V₂ on full load |
Step 1 — Transformation ratio
K = V₂ / V₁ = 200 / 2000 = 0.1 ⇒ K² = 0.01Step 2 — Referred to the primary
R₀₁ = R₁ + R₂ / K² = 5.5 + 0.045 / 0.01 = 5.5 + 4.5 = 10 Ω X₀₁ = X₁ + X₂ / K² = 12 + 0.1 / 0.01 = 12 + 10 = 22 ΩStep 3 — Referred to the secondary
R₀₂ = R₂ + K² R₁ = 0.045 + 0.01 × 5.5 = 0.1 Ω (= K² R₀₁ ✔) X₀₂ = X₂ + K² X₁ = 0.1 + 0.01 × 12 = 0.22 Ω (= K² X₀₁ ✔)Step 4 — Full-load secondary current
I₂ = S / V₂ = 10 000 / 200 = 50 AStep 5 — Voltage drop (from the phasor diagram, Fig. 8(c))
cos φ = 0.8, sin φ = 0.6 Drop ≈ I₂(R₀₂ cos φ + X₀₂ sin φ) = 50 × (0.1 × 0.8 + 0.22 × 0.6) = 50 × 0.212 = 10.6 VStep 6 — Regulation and terminal voltage
% Regulation ≈ 10.6 / 200 × 100 = 5.3 % V₂ (full load) ≈ 200 − 10.6 = 189.4 VExact check: (V₂ + 10.6)² + (I₂X₀₂ cos φ − I₂R₀₂ sin φ)² = 200², with the second term = 50(0.176 − 0.06) = 5.8 V ⇒ V₂ = 189.3 V — the approximation is excellent.
15. One-Line Exam Facts
- Transformer does not change frequency or (ideally) power.
- Rated in kVA because copper loss depends on current and core loss on voltage — neither depends on load power factor.
- Core loss is found by the OC test; copper loss by the SC test.
- Laminations reduce eddy current loss; silicon steel reduces hysteresis loss.
- Hysteresis loss ∝ f; eddy current loss ∝ f².
- Buchholz relay protects oil-immersed transformers against internal (incipient) faults; it is placed in the pipe between tank and conservator.
- Silica gel breather removes moisture from air entering the conservator.
- Conditions for parallel operation: same voltage ratio, same polarity, equal % impedance (and similar X/R ratio); for 3-phase also the same phase sequence and phase displacement (vector group).
- An auto-transformer has a single winding; it saves copper but gives no electrical isolation.
- CT secondary must never be left open-circuited (dangerous high voltage and core saturation).
16. Practice MCQs (click to see answer)
1. A transformer works on the principle of: (a) Self induction (b) Mutual induction (c) Electrostatic induction (d) Lenz’s law only
2. The EMF equation of a transformer is: (a) E = 4.44 f N Φm (b) E = 2.22 f N Φm (c) E = 4.44 f Φm / N (d) E = f N Φm
3. Which quantity does a transformer NOT change? (a) Voltage (b) Current (c) Frequency (d) Impedance level
4. Transformer core is laminated to reduce: (a) Hysteresis loss (b) Eddy current loss (c) Copper loss (d) Stray loss
5. Maximum efficiency of a transformer occurs when: (a) Copper loss = core loss (b) Copper loss = 2 × core loss (c) Core loss is zero (d) Load is maximum
6. The open-circuit test of a transformer measures: (a) Copper loss (b) Core loss (c) Total loss (d) Stray loss only
7. Transformer rating is expressed in: (a) kW (b) kVAR (c) kVA (d) HP
8. If a transformer is connected to a DC supply of rated voltage, it will: (a) Work normally (b) Step up voltage (c) Burn out due to heavy current (d) Give double output
9. Eddy current loss is proportional to: (a) f (b) f² (c) √f (d) 1/f
10. Buchholz relay is used for protection of: (a) Alternators (b) Transmission lines (c) Oil-immersed transformers (d) Induction motors
11. A transformer has 500 primary and 50 secondary turns. With 230 V primary, the secondary voltage is: (a) 2300 V (b) 23 V (c) 46 V (d) 11.5 V
12. The no-load current of a transformer is about: (a) 2–5% of rated current (b) 25% (c) 50% (d) 100%
13. The core of a power transformer is commonly made of: (a) Cast iron (b) CRGO silicon steel (c) Copper (d) Aluminium
14. Voltage regulation can be negative when the load power factor is: (a) Lagging (b) Unity (c) Leading (d) Zero lagging
15. Silica gel in a transformer breather is used to: (a) Cool the oil (b) Absorb moisture (c) Detect faults (d) Increase insulation thickness
17. বাংলায় দ্রুত রিভিশন
- ট্রান্সফরমার একটি স্থির যন্ত্র যা পারস্পরিক আবেশ (mutual induction) নীতিতে AC শক্তি এক সার্কিট থেকে অন্য সার্কিটে স্থানান্তর করে; ভোল্টেজ ও কারেন্ট বদলায়, কিন্তু ফ্রিকোয়েন্সি বদলায় না।
- EMF সমীকরণ: E = 4.44 f N Φm; অনুপাত: V₁/V₂ = N₁/N₂ = I₂/I₁।
- কোর লস (হিস্টেরেসিস + এডি কারেন্ট) প্রায় স্থির; কপার লস (I²R) লোডের বর্গের সমানুপাতিক। ল্যামিনেশন এডি কারেন্ট লস কমায়, সিলিকন স্টিল হিস্টেরেসিস লস কমায়।
- সর্বোচ্চ দক্ষতা হয় যখন কপার লস = কোর লস।
- OC টেস্টে কোর লস এবং SC টেস্টে কপার লস পাওয়া যায়।
- রেটিং kVA-তে হয়; DC সাপ্লাইতে ট্রান্সফরমার কাজ করে না, বরং পুড়ে যেতে পারে।
- বুখোলজ রিলে তেলভর্তি ট্রান্সফরমারের অভ্যন্তরীণ ত্রুটি থেকে সুরক্ষা দেয়; সিলিকা জেল আর্দ্রতা শোষণ করে।
Related Posts
- 220 Most Repeated Power Sector MCQs (PGCB, BPDB, BREB, DPDC)
- Hard vs Soft Magnetic Materials
- Classification of Magnetic Materials
- EEE Job Viva Voce Preparation