Faults & Symmetrical Components question solutions for EEE job exams. 2 written questions and 34 math problems on Faults & Symmetrical Components, the kind asked in Bangladesh EEE recruitment exams (BPDB, PGCB, DPDC, DESCO, NWPGCL, EGCB, BCS and others), each solved in exam style: the given data, what is required, the formula used at every step, the substitution and the final answer.
This post is part 22 of the EEE Job Preparation Question Bank series. It covers faults and symmetrical components with 36 solved questions: 2 written (theory) questions on sequence networks for a double line-to-ground fault and the short-circuit current of a generator and 18 math problems on sequence components, sequence impedances, line-to-ground and three-phase fault currents, fault MVA, current-limiting reactors and Z-bus fault calculation from recruitment exams (BPDB, PGCB, PGCL, NWPGCL, NPCBL, APSCL, EGCB) and BUET M.Sc. admission tests, plus 16 practice problems on the same topics.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution is laid out the way an examiner wants to see it: the given data with symbols and values, the quantity required, and then each step as formula → substitution → result, with the reason for that step written beside it. It also shows how to think about that type of problem, a diagram, and what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
- Formulas to memorize first
- Part A: Written questions (2)
- Part B: Solved problems (34)
Show the list
- Zero- and negative-sequence currents from phase currents
- Neutral current and sequence components of unbalanced currents
- Sequence components of unbalanced line currents and the neutral current
- Zero-sequence current from the neutral-to-ground current
- Sequence components of a faulted current set
- Sequence components with an open phase
- Fault type and neutral current from phase currents
- Neutral voltage of an unbalanced set
- Phase voltages from their sequence components
- Missing negative-sequence component and the other phase voltages
- Power from sequence voltages and currents
- Complex power from sequence voltages and currents
- Sequence impedances of a star-connected system with neutral impedance
- Sequence networks of a two-generator system
- Single line-to-ground fault current
- Single line-to-ground fault current
- Line-to-ground fault at the far end of a feeder (impedances in ohms)
- Ratio of line-to-ground to three-phase fault current
- Line-to-line fault current at the generator terminals
- Double line-to-ground fault current in per unit
- Sequence reactances of an alternator from three fault tests
- Fault with a reactor-earthed generator in parallel with another
- Short-circuit current with two alternators
- Bus fault fed by two alternators of different ratings (percent method)
- Fault kVA at the end of a line and at the transformer terminals
- Breaker duty on the low and high voltage sides of a generating station
- Short-circuit MVA at two interconnected stations
- Fault MVA with and without bus-section reactors
- External reactance to limit the short-circuit current
- Reactance of a current-limiting reactor in ohms
- Fault current at a busbar using per-unit reactance
- Current fed by an alternator into a fault 50 km along a 33 kV line
- Thevenin impedance from a bus fault current
- Short-circuit currents and voltages from the Z-bus
- Other parts of this series
Formulas to Memorize First
- Operator a = 1∠120°; a² = 1∠240° = 1∠−120°; 1 + a + a² = 0; a³ = 1.
- Sequence components: I₀ = (Ia + Ib + Ic)/3; I₁ = (Ia + aIb + a²Ic)/3; I₂ = (Ia + a²Ib + aIc)/3.
- Back to phases: Ia = I₀ + I₁ + I₂; Ib = I₀ + a²I₁ + aI₂; Ic = I₀ + aI₁ + a²I₂.
- Neutral current In = Ia + Ib + Ic = 3I₀. Zero-sequence impedance includes 3Zn.
- Power: S = 3(V₀I₀* + V₁I₁* + V₂I₂*) in actual per-phase values; in per unit (3-phase base) S = V₀I₀* + V₁I₁* + V₂I₂*.
- Three-phase fault: If = E/Z₁; fault MVA = base MVA/Z₁(pu).
- Single line-to-ground: networks in series: If = 3E/(Z₁ + Z₂ + Z₀ + 3Zn + 3Zf).
- Line-to-line: positive and negative in parallel: If = √3E/(Z₁ + Z₂); no zero sequence.
- Double line-to-ground: all three in parallel: Ia1 = E/[Z₁ + Z₂ ∥ (Z₀ + 3Zn)].
- Isolated neutral: no zero-sequence path (Z₀ = ∞ for that machine).
- Base current Ib = Sb/(√3 Vb); If(A) = If(pu) × Ib. Short-circuit current = IFL/Xpu.
- Z-bus fault at bus k: If = Vf/Zkk; Vi = Vf(1 − Zik/Zkk).
Part A: Written Questions on Fault Analysis & Symmetrical Components
Q1. An unloaded, grounded generator has a double line-to-ground fault. Draw the positive-, negative- and zero-sequence networks and write the fault current. BUET M.Sc.
Show full answer
Fault conditions
Double line-to-ground fault on phases b and c (through zero fault impedance) of an unloaded generator: Ia = 0 and Vb = Vc = 0. In sequence terms this gives Va1 = Va2 = Va0 and Ia1 + Ia2 + Ia0 = 0, which means the three sequence networks are connected in parallel at the fault point.
How to draw the networks
- Positive sequence: the generator e.m.f. Ea in series with Z₁, from the reference (neutral) to the fault point F₁.
- Negative sequence: Z₂ only; there is no source because the generator produces only positive-sequence voltage.
- Zero sequence: Z₀ + 3Zn (the neutral impedance appears three times because all three zero-sequence currents flow through it); no source.
- Join the three F terminals together and the three reference terminals together.
The connection
Fault current
Ia1 = Ea/[Z₁ + Z₂(Z₀ + 3Zn)/(Z₂ + Z₀ + 3Zn)]
Ia2 = −Ia1(Z₀ + 3Zn)/(Z₂ + Z₀ + 3Zn); Ia0 = −Ia1 Z₂/(Z₂ + Z₀ + 3Zn)
Current into the ground: If = Ib + Ic = 3Ia0.
Keep in mind
SLG: series. LL: positive ∥ negative. DLG: all three in parallel. Zero-sequence network gets 3Zn; only the positive network has a source.
Q2. Draw the waveshape of the armature current of a generator subjected to a sudden three-phase short circuit at its terminals. Define the various reactances of the generator from this waveshape. EGCB
Show full answer
How to draw the waveform
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 1 of 3. Draw the a.c. short-circuit current: very large at first, then decaying to a steady value (the d.c. offset is left out for clarity).
Drawing step 2 of 3. Draw the envelope. Extend the slowly decaying part back to t = 0 (orange dashed): the gap between it and the actual envelope is the fast sub-transient part.
Drawing step 3 of 3. Mark the three current levels at t = 0: I″ from the actual envelope, I′ from the extended transient envelope, I from the steady state.The three periods
- Sub-transient (first few cycles, time constant Td″ ≈ 0.03 s): the damper windings oppose the change of flux, so the reactance is smallest and the current largest.
- Transient (a few tenths of a second to a second or more, Td′ ≈ 1 s): the damper currents have decayed, but the field winding still opposes the flux change.
- Steady state: the full armature reaction acts; the current is limited by the synchronous reactance.
Defining the reactances
With E the r.m.s. no-load e.m.f.:
- Xd″ = E/I″ (sub-transient reactance), used to find the breaker interrupting duty and the initial fault current.
- Xd′ = E/I′ (transient reactance), used in stability studies.
- Xd = E/I (synchronous reactance), steady-state value.
Xd″ < Xd′ < Xd. Typical values for a turbo-alternator: 0.1, 0.2 and 1.5 pu.
Keep in mind
I″ > I′ > I; Xd″ < Xd′ < Xd. Breakers are rated on I″ (with the d.c. offset), relays on I′, steady-state on Xd.
Part B: Solved Problems on Fault Analysis & Symmetrical Components
Problem 1. Zero- and negative-sequence currents from phase currents PGCL
A Y-connected generator with a solidly grounded neutral has phase currents 10∠−5°, 10∠−115° and 10∠115° A. Find the zero-sequence and negative-sequence currents.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Ia | 10∠−5° A | |
| Ib | 10∠−115° A | |
| Ic | 10∠115° A |
- I₀
- I₂
- I₀ = (Ia + Ib + Ic)/3.
- I₂ = (Ia + a²Ib + aIc)/3.
- A small I₀ and I₂ mean a nearly balanced set.
Problem 2. Neutral current and sequence components of unbalanced currents BPDB
In a power system with a neutral return path the line currents are Ia = 10∠0°, Ib = 10∠−30° and Ic = 10∠−150° A. Calculate the neutral current In and the positive-sequence current in phase b.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Ia | 10∠0° A | |
| Ib | 10∠−30° A | |
| Ic | 10∠−150° A |
- In
- Ib1
- In = Ia + Ib + Ic = 3I₀.
- In the positive sequence, b lags a by 120°.
- Check: I₀ = In/3 = 4.71∠−45°.
Problem 3. Sequence components of unbalanced line currents and the neutral current Practice problem
In a 3-phase, 4-wire system the line currents under abnormal loading are IR = 100∠30° A, IY = 50∠300° A and IB = 30∠180° A. Find the zero, positive and negative sequence currents in the R line and the return current in the neutral wire.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| IR | 100∠30° A | |
| IY | 50∠300° A | |
| IB | 30∠180° A |
- I₀, I₁, I₂
- In
- a = −0.5 + j0.866; a² = −0.5 − j0.866.
- In = 3I₀.
- Check by adding the components back.
Problem 4. Zero-sequence current from the neutral-to-ground current Practice problem
The current from the neutral of a star-connected system to ground is 12 A. Find the zero-sequence component of current in each phase.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| In | 12 A | neutral to ground |
- I₀
- In = 3I₀.
- Isolated neutral → no zero-sequence current.
Problem 5. Sequence components of a faulted current set BPDB
If Ia = 0 and Ib = −Ic = −2j, find the symmetrical components of the fault current and state what type of fault has occurred.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Ia | 0 | |
| Ib | −j2 | |
| Ic | +j2 |
- Ia0, Ia1, Ia2
- fault type
- LL fault: Ia = 0, Ib = −Ic, I₀ = 0, I₁ = −I₂.
- SLG fault: I₀ = I₁ = I₂.
- DLG fault: I₀ + I₁ + I₂ = 0.
Problem 6. Sequence components with an open phase BUET M.Sc.
One conductor (line c) of a 3-phase line to a delta load is open and Ia = 10 A is the reference. Find the symmetrical components of the line currents.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Ia | 10∠0° A | reference |
| line c | open |
- Ia0, Ia1, Ia2
- Delta load: I₀ = 0 always.
- An open conductor creates negative sequence.
- Ia1 and Ia2 have equal size here.
Problem 7. Fault type and neutral current from phase currents BUET M.Sc.
If Ia = 0 and Ib = −Ic = −j2 A, (i) which type of fault has occurred and (ii) what is the current through the neutral wire of the generator?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Ia | 0 | |
| Ib | −j2 A | |
| Ic | +j2 A |
- fault type
- In
- In = 3I₀.
- LL faults have I₀ = 0.
- The same data as Problem 3.
Problem 8. Neutral voltage of an unbalanced set BUET Admission
Three phase voltages are given as 11∠35°, 30∠150° and 8∠240°. Find out the neutral voltage.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Va | 11∠35° | |
| Vb | 30∠150° | |
| Vc | 8∠240° |
- V₀
- V₀ = (Va + Vb + Vc)/3.
- A balanced set has V₀ = 0.
- Add in rectangular form.
Problem 9. Phase voltages from their sequence components Practice problem
The sequence voltages of the red phase are ER0 = 100 V, ER1 = (200 − j100) V and ER2 = −100 V. Find the phase voltages ER, EY and EB.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| ER0 | 100 V | |
| ER1 | 200 − j100 V | |
| ER2 | −100 V |
- ER, EY, EB
- EY = E₀ + a²E₁ + aE₂.
- EB = E₀ + aE₁ + a²E₂.
Problem 10. Missing negative-sequence component and the other phase voltages Practice problem
The zero- and positive-sequence components of the red phase are ER0 = (0.5 − j0.866) V and ER1 = 2∠0° V. If the phase voltage ER = 3∠0° V, find the negative-sequence component of the red phase and the phase voltages EY and EB.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| ER0 | 0.5 − j0.866 V | |
| ER1 | 2∠0° V | |
| ER | 3∠0° V |
- ER2
- EY
- EB
- E₂ = ER − E₀ − E₁.
- |a| = 1: multiplying by a only rotates.
Problem 11. Power from sequence voltages and currents PGCB
Positive and negative sequence components of phase ‘a’ voltage of a Y-connected resistive load are 0.9867∠43.6° and 0.2346∠250.3° pu; the currents have the same values. System base 100 MVA, neutral isolated. Find the power in MW.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V₁ | 0.9867∠43.6° pu | |
| V₂ | 0.2346∠250.3° pu | |
| I₁, I₂ | same as V₁, V₂ | |
| Sbase | 100 MVA |
- P
- Spu = Σ Vk Ik*.
- V I* = |V|² when I = V.
- Positive and negative sequence powers add.
Problem 12. Complex power from sequence voltages and currents BUET Admission
The symmetrical components are Va0 = 0, Va1 = 0.9857∠43.6°, Va2 = 0.2366∠250.3° and Ia0 = 0, Ia1 = 0.985∠43.6°, Ia2 = 0.2345∠250.3° (pu). Calculate the power absorbed by phase a of a Y-connected load.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Va1 | 0.9857∠43.6° | |
| Va2 | 0.2366∠250.3° | |
| Ia1 | 0.985∠43.6° | |
| Ia2 | 0.2345∠250.3° | pu |
- Sa
- Phase from sequence: Va = V₀ + V₁ + V₂.
- S = VI*.
- Q ≈ 0 → resistive.
Problem 13. Sequence impedances of a star-connected system with neutral impedance EGCB
In a Y-connected system the phase impedance is 0.2 pu and the impedance between neutral and ground is 0.1 pu. Find the zero-, positive- and negative-sequence impedances.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Z | 0.2 pu | phase impedance |
| Zn | 0.1 pu | neutral to ground |
- Z₀, Z₁, Z₂
- Z₀ = Z + 3Zn.
- Isolated neutral: Z₀ = ∞.
- Solid grounding: Z₀ = Z.
Problem 14. Sequence networks of a two-generator system NPCBL, BUET M.Sc.
Two generators G1 (250 MVA, 15 kV, X = 25 %) and G2 (100 MVA, 15 kV, X = 10 %) are joined through two 10 km lines (0.225 Ω/km) with bus 3 at the midpoint. Draw the positive-sequence network on 100 MVA and find the fault level at bus 3.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G1 | 250 MVA, 15 kV, 25 % | |
| G2 | 100 MVA, 15 kV, 10 % | |
| lines | 2 × 10 km, 0.225 Ω/km | |
| base | 100 MVA |
- fault level
- If
- Fault MVA = MVAbase/Xth(pu).
- If = MVA/(√3 kV).
- Parallel paths feed the fault together.
Problem 15. Single line-to-ground fault current Titas Gas, BUET
A 3-phase, 11 kV, 25 MVA generator has X₀ = 0.05, X₁ = 0.2, X₂ = 0.2 pu and is grounded through a 0.3 Ω reactor. Find the fault current for a single line-to-ground fault.
Figure: series connection of sequence networksShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 25 MVA | |
| V | 11 kV | |
| X₀, X₁, X₂ | 0.05, 0.2, 0.2 pu | |
| Xn | 0.3 Ω | neutral reactor |
- If
- SLG: If = 3E/(X₁ + X₂ + X₀ + 3Xn).
- 3Xn because 3I₀ flows in the neutral.
- Base current = MVA/(√3 kV).
Problem 16. Single line-to-ground fault current SGFL, APSCL
A 3-phase, 11 kV, 25 MVA generator has X₀ = 0.05 pu, X₁ = 0.2 pu and X₂ = 0.2 pu. Its neutral is grounded through a 0.3 Ω reactor. Find the fault current for a single line-to-ground fault.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 25 MVA | |
| V | 11 kV | |
| X₀, X₁, X₂ | 0.05, 0.2, 0.2 pu | |
| Xn | 0.3 Ω |
- If
- SLG: networks in series.
- If = 3E/(X₀ + 3Xn + X₁ + X₂).
- A neutral reactor reduces earth-fault current.
Problem 17. Line-to-ground fault at the far end of a feeder (impedances in ohms) Practice problem
A 3-phase, 10 MVA, 11 kV generator with a solidly earthed neutral supplies a feeder. The impedances in ohms are: generator Z₁ = j1.2, Z₂ = j0.9, Z₀ = j0.4; feeder Z₁ = j1.0, Z₂ = j1.0, Z₀ = j3.0. A fault from one phase to earth occurs at the far end of the feeder. Find (i) the fault current and (ii) the line-to-neutral voltage at the generator terminals of the faulted phase.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 11 kV | |
| Zg | j1.2, j0.9, j0.4 Ω | generator Z₁, Z₂, Z₀ |
| Zf | j1.0, j1.0, j3.0 Ω | feeder Z₁, Z₂, Z₀ |
- If
- V (at generator)
- L-G: If = 3E/(Z₁ + Z₂ + Z₀).
- Vterminal = E − I₁Z₁g − I₂Z₂g − I₀Z₀g.
Problem 18. Ratio of line-to-ground to three-phase fault current Practice problem
A 3-phase, 11 kV, 10 MVA alternator has sequence reactances X₀ = 0.05 pu, X₁ = 0.15 pu and X₂ = 0.15 pu. If it is on no load, find the ratio of the fault current for a line-to-ground fault to that for a three-phase short circuit.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 11 kV | |
| X₀, X₁, X₂ | 0.05, 0.15, 0.15 pu |
- ILG/I3φ
- ILG/I3φ = 3X₁/(X₁ + X₂ + X₀).
- Neutral grounding impedance limits earth-fault current.
Problem 19. Line-to-line fault current at the generator terminals Practice problem
A 3-phase, 3-wire system has a normal voltage of 10.4 kV between lines. It is supplied by a generator with positive, negative and zero sequence reactances of 0.6, 0.5 and 0.2 Ω per phase. Find the fault current when a line-to-line fault occurs at the generator terminals.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VL | 10.4 kV | |
| X₁, X₂, X₀ | 0.6, 0.5, 0.2 Ω |
- If (line-to-line)
- L-L: If = VL/(X₁ + X₂) = √3E/(X₁ + X₂).
- Zero-sequence reactance does not matter for L-L faults.
Problem 20. Double line-to-ground fault current in per unit Practice problem
The per-unit positive, negative and zero sequence reactances of a network at the fault point are 0.08, 0.07 and 0.05. Determine the fault current if the fault is a double line-to-ground fault.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| X₁, X₂, X₀ | 0.08, 0.07, 0.05 pu |
- If (double line-to-ground)
- L-L-G: I₁ = E/[Z₁ + Z₂∥Z₀].
- If (to ground) = 3I₀.
Problem 21. Sequence reactances of an alternator from three fault tests Practice problem
A 50 MVA, 11 kV three-phase alternator with a solidly grounded neutral was subjected to different faults. The fault currents were: three-phase 2000 A; line-to-line 2600 A; line-to-ground 4200 A. Find the positive, negative and zero sequence reactances (ignore resistance).
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 50 MVA | |
| V | 11 kV | |
| I3φ | 2000 A | |
| ILL | 2600 A | |
| ILG | 4200 A |
- X₁, X₂, X₀
- 3φ: I = E/X₁; L-L: I = √3E/(X₁ + X₂); L-G: I = 3E/(X₁ + X₂ + X₀).
Problem 22. Fault with a reactor-earthed generator in parallel with another NPCBL
A 20 MVA, 11 kV, 3-phase, 50 Hz generator has its neutral earthed through a 5 % reactor and is in parallel with an identical generator having an isolated neutral. Each generator has X₁ = 20 %, X₂ = 10 % and X₀ = 15 %. Find the fault current for a line-to-ground fault on the common bus-bar.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 20 MVA each | |
| V | 11 kV | |
| X₁, X₂, X₀ | 20 %, 10 %, 15 % | each |
| Xn | 5 % | reactor on one machine |
- If (L-G fault)
- Isolated neutral = open in the zero-sequence network.
- Parallel identical: X/2.
- 3Xn for the earthing reactor.
Problem 23. Short-circuit current with two alternators BCMCL
Two alternators of 15 000 kVA (10 % reactance) and 10 000 kVA (20 % reactance) are connected to a 3.3 kV bus. Find the short-circuit current for a fault on the bus. Choose 3000 kVA as base.
Figure: reactance diagram of the two alternatorsShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G1 | 15 MVA, 10 % | |
| G2 | 10 MVA, 20 % | |
| V | 3.3 kV | bus |
| base | 3000 kVA |
- Isc
- Percent reactance on a common base.
- Short-circuit current = Ibase/Xpu.
- Fault MVA = MVAbase/Xpu.
Problem 24. Bus fault fed by two alternators of different ratings (percent method) Practice problem
Two alternators, A (15 000 kVA, 30 % reactance) and B (20 000 kVA, 50 % reactance), feed a 12 kV bus-bar; each reactance is on its own rating. Find the current that flows into a complete three-phase short circuit at the bus.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| A | 15 MVA, 30 % | |
| B | 20 MVA, 50 % | |
| V | 12 kV |
- Isc
- %Xnew = %Xold × kVAbase/kVArated.
- Isc = Ibase × 100/%X.
Problem 25. Fault kVA at the end of a line and at the transformer terminals Practice problem
A 3-phase line operating at 10 kV has a resistance of 1 Ω and a reactance of 4 Ω. It is connected to the station bus-bars through a 5 MVA step-up transformer of 5 % reactance; the bus-bars are supplied by a 10 MVA alternator of 10 % reactance. Find the short-circuit kVA for a symmetrical fault (i) at the load end of the line and (ii) at the high-voltage terminals of the transformer.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| line | 1 + j4 Ω at 10 kV | |
| T | 5 MVA, 5 % | |
| G | 10 MVA, 10 % | |
| base | 10 MVA |
- fault kVA (line end and HV terminals)
- %Z = kVA × Ω/(10 × kV²).
- Fault kVA = base kVA × 100/%Z.
Problem 26. Breaker duty on the low and high voltage sides of a generating station Practice problem
A generating station has two 10 000 kVA generators of 12 % reactance each and one 5000 kVA generator of 18 % reactance, all on the station bus-bars. Load is taken through three 5000 kVA step-up transformers, each of 5 % reactance. Find the maximum fault MVA which the circuit breakers on (i) the low-voltage side and (ii) the high-voltage side may have to interrupt.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 2 × 10 MVA, 12 %; 5 MVA, 18 % | |
| T | 3 × 5 MVA, 5 % | |
| base | 10 MVA |
- fault MVA (LV and HV side)
- Parallel sources: combine reactances in parallel.
- A transformer in the fault path lowers the fault MVA.
Problem 27. Short-circuit MVA at two interconnected stations Practice problem
The estimated short-circuit MVA at the bus-bars of station A is 1500 MVA and of station B is 1200 MVA; each generates at 33 kV. The stations are interconnected through a line with a reactance of 1 Ω and negligible resistance. Find the possible short-circuit MVA at both stations.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| SCA | 1500 MVA | |
| SCB | 1200 MVA | |
| V | 33 kV | |
| Xline | 1 Ω |
- SC MVA (at A and B)
- %Xsource = base MVA × 100/SC MVA.
- Interconnection raises fault levels.
Problem 28. Fault MVA with and without bus-section reactors Practice problem
A generating station has three section bus-bars connected to a tie-bar through 6 % reactors rated at 5000 kVA. Each generator is 5000 kVA with 12 % reactance and is connected to one section. Find the total steady input to a dead short circuit between the lines on one section (i) with the reactors and (ii) without them.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 3 × 5 MVA, 12 % | one per section |
| reactors | 6 % on 5 MVA |
- fault MVA (with and without reactors)
- Bus-section/tie-bar reactors limit fault MVA.
- Combine series paths first, then parallel.
Problem 29. External reactance to limit the short-circuit current NWPGCL
A 3-phase, 20 MVA, 10 kV alternator has an internal reactance of 5 % and negligible resistance. Find the external reactance per phase to be connected in series so that the steady short-circuit current does not exceed 8 times the full-load current.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 20 MVA | |
| V | 10 kV | |
| Xint | 5 % | |
| Isc ≤ 8IFL |
- Xext
- Isc = IFL/Xpu.
- Reactors limit fault current.
- Zbase = kV²/MVA.
Problem 30. Reactance of a current-limiting reactor in ohms Practice problem
A 3-phase alternator can supply a maximum load of 5000 kVA at 6600 V. Its internal reactance is 6 %. Find the reactance per phase of the limiting reactor if the steady apparent power on short circuit is not to exceed 5 times the full-load value.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 5000 kVA | |
| V | 6600 V | |
| Xint | 6 % | |
| Ssc ≤ 5S |
- Xreactor
- Total %X = 100/(allowed multiple of full load).
- Ω = %X × 10 kV²/kVA.
Problem 31. Fault current at a busbar using per-unit reactance ERL
A 10 000 kVA, 6.6 kV, 3-phase generator with a reactance of 1.12 pu feeds a 6.6 kV busbar, and a feeder rated 5 MVA with a reactance of 0.5 pu is connected to the busbar. Find the fault current for a 3-phase short circuit at the busbar.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 10 MVA, 6.6 kV, 1.12 pu | |
| feeder | 5 MVA, 0.5 pu |
- If (bus fault)
- Only sources contribute fault current.
- If = Ib/Xpu.
- Put all X on one base.
Problem 32. Current fed by an alternator into a fault 50 km along a 33 kV line Practice problem
A 10 MVA, 6.6 kV, 3-phase star-connected alternator with 20 % reactance is connected through a 5 MVA, 6.6/33 kV transformer of 10 % reactance to a transmission line with a resistance of 0.2 Ω and a reactance of 1 Ω per conductor per km. A three-phase short circuit occurs 50 km along the line. Find the current fed to the fault by the alternator.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 10 MVA, 6.6 kV, 20 % | |
| T | 5 MVA, 6.6/33 kV, 10 % | |
| line | 0.2 + j1 Ω/km | |
| l | 50 km |
- I (from alternator)
- Fault current = fault MVA/(√3 × kV at that point).
- Line resistance matters on long lines.
Problem 33. Thevenin impedance from a bus fault current PGCB
In a 33 kV bus the voltage is 1 p.u. on a base line voltage of 33 kV. If an L-L-L-G fault occurs at this bus, the fault current flowing to the fault is 30 kA. The three-phase base MVA is 100 MVA. What is the Thevenin equivalent impedance seen looking into the network from the bus?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 1 pu | on 33 kV |
| If | 30 kA | |
| Sbase | 100 MVA |
- Zth
- Zth = Vf/If.
- Fault MVA = 1/Zth(pu) × base MVA = 1715 MVA here.
- Ibase = MVA/(√3 kV).
Problem 34. Short-circuit currents and voltages from the Z-bus BPDB
Consider the Zbus matrix of a small two-bus system, Zbus = j[0.11565 0.04580; 0.04580 0.13893] pu. A three-phase short-circuit fault occurs at bus 1; the pre-fault voltage is 1.05 pu and the pre-fault load current is neglected. Calculate (i) the sub-transient fault current and (ii) the voltages at bus 1 and bus 2 during the fault.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Z₁₁ | j0.11565 pu | |
| Z₂₁ | j0.04580 pu | |
| Vf | 1.05 pu | pre-fault |
- If″
- V₁, V₂
- If = Vf/Zkk.
- Vi = Vf(1 − Zik/Zkk).
- Z-bus diagonal = Thevenin impedance at that bus.
- DC Circuit Analysis
- Network Theorems
- RL, RC & RLC Transients
- Single-Phase AC Circuits
- Series & Parallel Resonance
- Power Factor Correction
- Three-Phase Circuits
- Transformer
- DC Generator & DC Motor
- Three-Phase Induction Motor
- Synchronous Machines
- Diode Circuits
- BJT Biasing & Amplifiers
- MOSFET & Power Electronics
- Op-Amp Circuits
- AM, FM & Analog Modulation
- Signals and Sampling
- PCM, Delta Modulation & TDM
- Digital Communication & Telecom
- Load Curves & Power Generation
- Per-Unit & Transmission Lines
- Faults & Symmetrical Components (this post)
- Protection & Switchgear
- Control Systems
- Digital Logic & Microprocessors
- Measurement, Mechanics & Aptitude
Topics shown in grey are coming soon. See every post in this series.
Found a mistake or have a better method? Leave a comment below. More topics from the question bank are in the other posts of this series.
Thank you for visiting my blog.