This post is part 8 of the EEE Job Preparation Question Bank series. It covers the Transformer: 13 written (theory) questions and 27 math problems asked in recruitment exams such as BPDB, DPDC, PGCB, NWPGCL, DWASA and BUET M.Sc. admission.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution shows each line of working with the reason for it beside it, starts with how to think about that type of problem, and ends with what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
Contents: Formulas to memorize | Part A: Written questions (13) | Part B: Solved problems (27)
Formulas to Memorize First
- EMF equation: E = 4.44 f N Φm. Voltage per turn is the same on both windings.
- Ratios: V1/V2 = N1/N2 = a, I1/I2 = 1/a, impedance moves across with a² (to the primary: Z′ = a²Z).
- Rated current: I = VA / V on each side.
- No load: I0 = P0/(V cos φ0); Ic = I0 cos φ0 (core loss), Im = I0 sin φ0 (magnetising).
- OC test gives the core loss, Rc and Xm. SC test gives the full-load copper loss, Req and Xeq.
- Losses: core loss Pi is constant; copper loss at load fraction x is x²Pcu.
- Efficiency: η = x S cos φ / (x S cos φ + Pi + x²Pcu). It is maximum when x²Pcu = Pi, so x = √(Pi/Pcu).
- Regulation (lagging load): ≈ I(R cos φ + X sin φ)/V, or in per unit x(Rpu cos φ + Xpu sin φ). For a leading load the sign of the X term becomes minus.
- Parallel sharing: SA = S · ZB/(ZA + ZB), with both impedances on the same kVA base.
- Auto-transformer: rating = two-winding rating × (Vhigh / Vseries winding).
Part A: Written Questions on Transformer
Q1. Why is a transformer rated in kVA and not kW? PGCL
Show full answer
Short answer (write this in the exam)
A transformer has two losses: copper loss, which depends on the current, and iron loss, which depends on the voltage. Neither depends on the power factor of the load. The heating, and so the safe loading limit, is therefore fixed by V × I, which is volt-amperes. That is why the rating is given in kVA and not kW.
What a rating really means
A rating is the load the machine can carry continuously without its temperature rising above the safe limit of the insulation. Temperature rise comes from losses, so to understand the rating you ask one thing: what do the losses depend on?
Why power factor does not enter
- Copper loss = I²R. Only the size of the current matters, not its phase angle.
- Iron loss (hysteresis + eddy current) depends on the flux in the core, and the flux is fixed by the applied voltage and frequency.
- So total loss depends on V and I, never on cos φ. Two loads of the same kVA but different power factor heat the transformer exactly the same.
The second reason is practical: when the transformer is built, the manufacturer does not know what load the customer will connect. kW = kVA × cos φ can only be stated if cos φ is known, and it is not.
How to see it with numbers
Take a 100 kVA transformer. At unity power factor it delivers 100 kW. At 0.6 power factor it delivers only 60 kW, yet the current, the losses and the heating are the same in both cases. If it had been rated "100 kW", someone could load it to 100 kW at 0.6 pf, which is 167 kVA, and burn it.
Where the same idea applies
Alternators, transmission lines, cables and UPS units are also rated in kVA or MVA for the same reason. A motor is rated in kW (or hp) because its output is mechanical power at the shaft, where power factor has no meaning.
Keep in mind
Copper loss follows current, iron loss follows voltage, and the product of voltage and current is VA. Say these three things and the answer is complete.
Q2. Why does a transformer not work on DC? DPDC
Show full answer
Short answer (write this in the exam)
A transformer works by mutual induction, which needs a changing flux (e = N dΦ/dt). DC gives a constant flux, so dΦ/dt = 0 and no e.m.f. is induced in the secondary. Also, with no back e.m.f. in the primary, the current is limited only by the small winding resistance, so it becomes very large and burns the winding.
What happens, step by step
- You apply a steady DC voltage to the primary.
- The current rises and settles at a constant value, so the flux in the core becomes constant.
- A constant flux does not cut the secondary turns at any rate, so the secondary e.m.f. is zero. No output.
- On AC the primary generates a back e.m.f. almost equal to the supply, and that back e.m.f. is what keeps the current small. On DC there is none.
Why it is dangerous, with numbers
Suppose a 230 V primary has a resistance of 0.5 Ω. On AC the no-load current may be about 1 A, because the back e.m.f. opposes the supply. On 230 V DC the current is 230/0.5 = 460 A. The core also saturates. The winding overheats in seconds.
Where this matters
- DC transmission (HVDC) cannot step voltage up or down with a transformer directly. It converts AC to DC with converters, and transformers are used only on the AC side.
- When the DC winding resistance of a transformer is measured, only a very low DC voltage is applied.
- A brief pulse does appear on the secondary at the instant DC is switched on or off, because the flux is changing at that instant. The ignition coil of a car uses this.
Keep in mind
No change of flux, no e.m.f. No back e.m.f., no limit on current except R. Those are the two points examiners look for.
Q3. Draw the exact equivalent circuit of a transformer. BCPCL
Show full answer
What the circuit is for
A real transformer is not ideal: its windings have resistance, some flux leaks, and the core takes a current and wastes power. The equivalent circuit replaces the real transformer with an ideal one plus a few ordinary R and X elements that account for these imperfections. Once it is drawn, any transformer problem becomes a normal AC circuit problem.
How to draw it (build it in three steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Why each element is there
| Element | Represents | Why series or shunt |
|---|---|---|
| R1, R2 | Winding resistance (copper loss) | Series: the loss depends on load current |
| X1, X2 | Leakage flux of each winding | Series: the drop depends on load current |
| Rc | Core loss (hysteresis + eddy) | Shunt: the loss depends on voltage |
| Xm | Magnetising the core | Shunt: the flux depends on voltage |
How to refer the secondary to the primary
With a = N1/N2: R′2 = a²R2, X′2 = a²X2, Z′L = a²ZL, V′2 = aV2, I′2 = I2/a. Voltage is multiplied by a, current is divided by a, so impedance (V/I) is multiplied by a².
The approximate circuit
Because I0 is only 2 to 5 % of the full-load current, the shunt branch can be moved to the supply terminals with very little error. Then R1 and R′2 add to give Req = R1 + R′2, and Xeq = X1 + X′2. Most numerical problems use this form.
Keep in mind
Series elements belong to the windings (current-dependent). Shunt elements belong to the core (voltage-dependent). If the question says "exact", the shunt branch sits between the two winding impedances; if "approximate", it sits at the input.
Q4. Draw the equivalent circuit of a transformer referred to the secondary. DWASA
Show full answer
What changes when you refer to the secondary
The circuit has the same shape as the one referred to the primary. The only difference is the direction of scaling: now every primary quantity is moved across to the secondary side. Let K = N2/N1 (the transformation ratio).
| Primary quantity | Referred to secondary |
|---|---|
| Voltage V1 | V′1 = KV1 |
| Current I1 | I′1 = I1/K |
| R1, X1 | K²R1, K²X1 |
| Exciting branch R0, X0 | R′0 = K²R0, X′0 = K²X0 |
How to draw it (two steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Why you would choose this side
Voltage regulation and load calculations are about what the load sees, so it is convenient to have everything on the load side. Then V′1 is simply the no-load secondary voltage, and V′1 − V2 is the drop inside the transformer.
Keep in mind
Moving toward the side with more turns makes impedance larger; toward fewer turns, smaller. For a step-down transformer K is less than 1, so the primary impedances shrink when referred to the secondary. A quick check: the per-unit value is the same on both sides.
Q5. Draw the vector (phasor) diagram of a single-phase step-down transformer on load. BPDB
Show full answer
How to think about it
A phasor diagram is just three equations drawn as arrows. Write the equations first, then draw one equation at a time:
- Secondary: E2 = V2 + I2R2 + jI2X2
- Currents: I1 = I0 + I′2, where I′2 = KI2 and opposes I2
- Primary: V1 = −E1 + I1R1 + jI1X1
Two drawing rules do all the work: an IR drop is parallel to its current, and an IX drop is 90° ahead of its current.
How to draw it (four steps, inductive load)
Each picture adds one step to the one before it. Draw it on paper in the same order.
What the finished diagram tells you
- V1 is slightly larger than E1, and V2 slightly smaller than E2: the difference is the internal drop, which is the cause of voltage regulation.
- φ1 is a little larger than φ2, so the primary power factor is slightly worse than the load power factor. The magnetising current and the leakage reactances cause this.
- For a resistive load, draw I2 along V2. For a capacitive load, draw I2 ahead of V2; then V2 can even exceed E2.
Keep in mind
Order of drawing: Φ, then E1 and E2 (90° behind), then the secondary triangle, then the currents, then the primary triangle. Some books take V2 as the reference instead of Φ; the diagram is the same, only rotated.
Q6. Describe the open-circuit and short-circuit tests.
Show full answer
What the two tests are for
They find the equivalent-circuit parameters and the losses of a transformer without actually loading it. Only the losses are supplied during the tests, so a very large transformer can be tested with a small supply.
Connections for the two tests. In each, a wattmeter W, an ammeter A and a voltmeter V are on the supply side.Open-circuit (no-load) test
- How: apply rated voltage to the LV winding and keep the HV winding open. Read V0, I0 and W0.
- Why the LV side: rated LV voltage is easy to obtain and safe to measure, and the meters are ordinary low-voltage instruments.
- What the wattmeter reads: the core (iron) loss. The current is only 2 to 5 % of rated, so the copper loss I0²R is negligible.
- What you calculate: cos φ0 = W0/(V0I0); Ic = I0 cos φ0, Im = I0 sin φ0; Rc = V0/Ic, Xm = V0/Im.
Short-circuit test
- How: short the LV winding with a thick conductor. Raise the voltage on the HV winding slowly from zero (using a variac) until rated current flows. Read Vsc, Isc and Wsc.
- Why the HV side: the rated current on the HV side is small, and the voltage needed is only about 5 to 10 % of the HV rating, which is convenient.
- What the wattmeter reads: the full-load copper loss. The voltage is so low that the flux, and so the core loss, is negligible.
- What you calculate: Zeq = Vsc/Isc, Req = Wsc/Isc², Xeq = √(Zeq² − Req²), all referred to the side where the meters are.
Where the results are used
With Pi from the OC test and Pcu from the SC test you can find the efficiency at any load and power factor. With Req and Xeq you can find the voltage regulation. Together they give the complete approximate equivalent circuit.
Keep in mind
OC test: rated voltage, gives core loss and the shunt branch. SC test: rated current, gives copper loss and the series branch. The values you get are referred to the side where the instruments are connected, so check which side that is before using them.
Q7. What are the losses of a transformer? What is all-day efficiency? BUET M.Sc.
Show full answer
Short answer (write this in the exam)
Transformer losses are (1) iron or core loss = hysteresis loss + eddy-current loss, which is constant at constant voltage and frequency, and (2) copper loss = I²R in the two windings, which varies as the square of the load. All-day efficiency = output energy in kWh over 24 hours ÷ input energy in kWh over 24 hours.
What each loss is and why it occurs
- Hysteresis loss: the core is magnetised and demagnetised 50 times a second, and the steel resists each reversal. Wh ∝ Bmax1.6 · f. Reduced by using silicon steel (CRGO).
- Eddy-current loss: the changing flux induces circulating currents in the core itself. We ∝ Bmax² · f² · t², where t is the lamination thickness. Reduced by building the core from thin insulated laminations.
- Copper loss: I1²R1 + I2²R2. At a fraction x of full load it is x² times the full-load value.
- Small extras: stray loss in the tank and clamps, and dielectric loss in the insulation.
A transformer has no rotating part, so there is no friction or windage loss. That is why its efficiency is so high (95 to 99 %).
How the losses decide the efficiency
η = x S cos φ / (x S cos φ + Pi + x²Pcu). Efficiency is maximum when the variable loss equals the constant loss: x²Pcu = Pi, so the load fraction for maximum efficiency is x = √(Pi/Pcu).
What all-day efficiency is, and why it is needed
A distribution transformer is energised 24 hours a day, so its core loss runs all day. But it is heavily loaded for only a few hours, so its copper loss is significant only then. Ordinary efficiency at one load does not show this. All-day efficiency compares energy instead of power:
ηall-day = kWh output in 24 h / (kWh output + Pi × 24 + Σ copper loss × hours at each load)
It is always lower than the ordinary full-load efficiency. This is why distribution transformers are designed with a low core loss, while power transformers, which run near full load, are designed for maximum efficiency near full load.
Keep in mind
Core loss: constant, depends on voltage and frequency, found from the OC test. Copper loss: varies as load², found from the SC test. Maximum efficiency when they are equal.
Q8. What are the no-load losses of a transformer? PGCB
Show full answer
Short answer (write this in the exam)
On no load the secondary is open, so the primary takes only the small no-load current I0 (about 2 to 5 % of rated current). The no-load loss is therefore almost entirely the core (iron) loss: hysteresis loss + eddy-current loss. A very small primary copper loss I0²R1 and a small dielectric loss are also present but are neglected.
What each part is
- Hysteresis loss Wh = Kh Bmax1.6 f V: energy spent reversing the magnetism of the core every cycle.
- Eddy-current loss We = Ke Bmax² f² t² V: heating by currents induced in the core steel. (V is the core volume, t the lamination thickness.)
Why it is constant
Both parts depend on Bmax and f. From E = 4.44 f N Φm, the flux is fixed by the applied voltage and frequency, not by the load. So as long as the supply voltage and frequency are constant, the no-load loss is the same from no load to full load. This is why it is also called the constant loss.
How it is measured and where it matters
It is measured by the open-circuit test: the wattmeter reading at rated voltage is the no-load loss. The no-load power factor is low, about 0.1 to 0.3 lagging, because most of I0 is magnetising current. The loss matters most in distribution transformers, which stay energised all day even when lightly loaded.
Keep in mind
No-load loss = core loss = hysteresis + eddy current = constant loss = wattmeter reading in the OC test. These are five names for the same thing.
Q9. What are the load and no-load losses of a transformer? What is the all-day efficiency of a transformer? BUET Admission
Show full answer
Short answer (write this in the exam)
No-load loss is the core loss (hysteresis + eddy current). It is present whenever the transformer is energised and is constant at constant voltage and frequency. Load loss is the copper loss I²R in both windings, plus a small stray loss; it is proportional to the square of the load current. All-day efficiency = output energy in 24 h ÷ input energy in 24 h.
How to tell the two losses apart
| No-load (core) loss | Load (copper) loss | |
|---|---|---|
| Where | In the core | In the windings |
| Depends on | Voltage and frequency | Load current squared |
| With load | Constant | x² times the full-load value |
| Measured by | Open-circuit test | Short-circuit test |
| Reduced by | CRGO steel, thin laminations | Thicker conductors, lower resistance |
How to calculate all-day efficiency
- Output energy = Σ (kW at each load × hours).
- Core-loss energy = Pi × 24, because the core loss never stops.
- Copper-loss energy = Σ (x² Pcu × hours), where x = kVA at that load ÷ rated kVA. Use kVA, not kW, for x.
- ηall-day = output energy / (output energy + core-loss energy + copper-loss energy).
Problem 22 in Part B works a full example.
Why it matters
A distribution transformer supplies houses and shops: heavy load in the evening, almost nothing late at night, but energised all the time. Judging it by full-load efficiency would hide the energy wasted in the core during the idle hours. All-day efficiency shows it.
Keep in mind
In the copper-loss term the load fraction is based on kVA. A load of 30 kVA at 0.6 pf on a 100 kVA transformer has x = 0.3, not 0.18.
Q10. Write the conditions for parallel operation of transformers. BUET M.Sc.
Show full answer
Short answer (write this in the exam)
- The same voltage ratio (same primary and secondary voltage ratings).
- The same polarity.
- The same phase sequence and zero relative phase displacement (same vector group) for three-phase units.
- Equal per-unit (percentage) impedance, so each shares load in proportion to its kVA rating.
- Preferably the same X/R ratio.
What parallel operation is, and why it is done
Two or more transformers have their primaries on the same supply bus and their secondaries on the same load bus. It is done to supply a load larger than one unit can carry, to keep supply on when one unit is out for maintenance, and to switch off a unit at light load to save its core loss.
Why each condition is needed (what goes wrong without it)
| Condition | If it is not met |
|---|---|
| Same voltage ratio | The secondary e.m.f.s differ, so a circulating current flows between the transformers even at no load, causing extra copper loss. |
| Same polarity | The two secondary e.m.f.s add around the local loop instead of cancelling. This is a dead short circuit. Must be satisfied. |
| Same phase sequence and vector group | A phase difference (for example 30° between Y-Y and Δ-Y) leaves a large voltage across the paralleling switch and drives a very large circulating current. Must be satisfied. |
| Equal per-unit impedance | The unit with the lower per-unit impedance takes more than its share and overloads before the other is fully used. |
| Same X/R ratio | The two currents are not in phase, so the units work at different power factors and the total kVA available is slightly less than the sum. |
How the load divides
The two transformers are two impedances in parallel, so the current divides inversely as the impedances: SA = S · ZB/(ZA + ZB) and SB = S · ZA/(ZA + ZB), with both impedances expressed on the same kVA base. Problem 23 in Part B is a worked example.
Keep in mind
Polarity and phase sequence are essential (wrong means short circuit). Equal ratio and equal per-unit impedance are desirable (wrong means circulating current or unequal sharing).
Q11. What are the disadvantages of 3-phase Y-Y connected transformers? How can these disadvantages be removed? BUET Admission
Show full answer
What a Y-Y connection is and where it is used
Both the primary and the secondary windings are star connected. Each winding carries only the phase voltage (line voltage ÷ √3), so it needs less insulation and fewer turns. That makes it economical for high-voltage, small-current transformers. There is no phase shift between primary and secondary line voltages.
Disadvantages, and why each happens
- Unbalanced loads shift the neutral. With an isolated neutral, a single-phase load on the secondary cannot be balanced by the primary, so the neutral point moves and the phase voltages become unequal.
- Third-harmonic voltages. The core is non-linear, so a sinusoidal flux needs a magnetising current that contains a third harmonic. The three third-harmonic currents are in phase with each other and need a return path. In an isolated star there is none, so the current is forced to be sinusoidal and the flux and phase voltages become distorted with a large third-harmonic component.
- Telephone interference. If the neutrals are grounded to give that path, the third-harmonic currents flow in the ground and neutral wires and can disturb nearby communication circuits.
How the disadvantages are removed
- Solidly ground the neutrals (especially the primary neutral to the source neutral). This gives the unbalanced and third-harmonic currents a path.
- Add a tertiary delta winding. Third-harmonic currents circulate inside the closed delta and supply the needed magnetising component, so the flux stays sinusoidal. The delta also stabilises the neutral for unbalanced loads and can feed station auxiliaries.
- Use Y-Δ or Δ-Y instead, where one winding is already a delta.
Keep in mind
Two problems, one cure: unbalanced load and third harmonics are both solved by a delta somewhere (a tertiary winding) or by grounded neutrals. Triplen harmonics (3rd, 9th, …) are in phase in all three phases, which is why they circulate in a delta and cannot flow in an isolated star.
Q12. Give four differences between CT and PT. MIST
Show full answer
What they are
Both are instrument transformers. They step a high current or a high voltage down to a small standard value so that ordinary meters and relays can be used, and they isolate those instruments from the high-voltage circuit. A CT (current transformer) handles current; a PT (potential or voltage transformer) handles voltage.
A CT has the line itself as its primary. A PT is connected from line to earth like a small step-down transformer.Differences
| Point | CT | PT |
|---|---|---|
| Connection | In series with the line | In parallel (across line and earth or line and line) |
| Primary | Few turns (often one), thick conductor; carries full line current | Many turns, thin conductor; has full line voltage across it |
| Action | Steps current down (so voltage up) | Steps voltage down |
| Standard secondary | 5 A or 1 A | 110 V |
| Secondary condition | Works almost short-circuited; must never be opened | Works almost open-circuited; must never be shorted |
| Primary current | Fixed by the line; independent of the burden | Depends on the burden |
| Feeds | Ammeter, current coils of wattmeters and relays | Voltmeter, pressure coils of wattmeters and relays |
Why a CT secondary must never be opened
In a CT the primary current is the line current; the CT cannot reduce it. Normally the secondary current produces an opposing m.m.f., so the net flux in the core is small. If the secondary is opened, that opposing m.m.f. disappears and the whole primary current magnetises the core. The core saturates and a very high voltage (several kV) appears across the open secondary. It can kill the person working there, break down the insulation and overheat the core. So before removing a meter or relay, short the CT secondary first.
Why a PT secondary must never be shorted
A PT behaves like an ordinary voltage transformer. A short on the secondary draws a very large current and burns the winding, which is why PT secondaries are protected by fuses.
Keep in mind
CT: series, short it. PT: parallel, never short it. One point of each secondary is earthed for safety.
Q13. Draw and label the voltage waveforms across each half of the secondary winding and across RL for the full-wave centre-tap rectifier (input ±100 V peak, 2:1 transformer, RL = 10 kΩ). What PIV must the diodes have? APSCL
Show full answer
How to think about it
Work from the input toward the load, one stage at a time: (1) what does the transformer do to the peak voltage, (2) what does the centre tap do, (3) which diode conducts in each half-cycle, (4) what does the diode that is off have across it.
How to draw the waveforms (three steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. In the positive half-cycle vs1 is positive, so D1 conducts and the load gets vs1. In the negative half-cycle vs2 is positive, so D2 conducts and the load gets vs2. Either way the load current is in the same direction, so vL is a row of positive humps of 25 V peak, two per input cycle.Numbers to write beside the waveforms
- Peak of full secondary = 100/2 = 50 V; peak of each half Vm = 25 V.
- Peak load voltage = 25 V (24.3 V if the 0.7 V diode drop is counted).
- Average (DC) load voltage = 2Vm/π = 2 × 25/π = 15.9 V; DC load current = 15.9 V / 10 kΩ = 1.59 mA.
- Ripple frequency = 2 × supply frequency.
Why the PIV is 50 V
Look at the instant when D1 is conducting at the peak. Its cathode (the load) is at +25 V. The anode of D2 is connected to the other half-winding, which is at −25 V. So the non-conducting diode has 25 − (−25) = 50 V across it in reverse. PIV = 2Vm = 50 V (2Vm − 0.7 = 49.3 V with the diode drop). Choose diodes rated comfortably above this.
Keep in mind
Centre-tap full-wave: each diode sees PIV = 2Vm, where Vm is the peak of half the secondary. A bridge rectifier using the whole secondary has PIV = Vm only. For both, Vdc = 2Vm/π and the ripple frequency is 2f.
Part B: Solved Problems on Transformer
Problem 1. Currents and flux of a 25 kVA transformer BUET M.Sc.
A 25 kVA single-phase transformer has 250 primary turns and 40 secondary turns. The primary is connected to 1500 V, 50 Hz mains. Calculate (i) the primary and secondary full-load currents and (ii) the secondary e.m.f.
Show step-by-step solution
- I = VA / V on each side.
- V1/V2 = N1/N2 and I1/I2 = N2/N1.
- E = 4.44 f N Φm; volts per turn is equal for both windings.
Problem 2. Load reflected to the primary of a transformer PGCB
A 200 Ω load resistor is connected across the secondary of a transformer with a turns ratio of 4 (primary : secondary). What load does the source see?
Show step-by-step solution
- Referred to primary: Z′ = a²Z (a = N1/N2). Referred to secondary: divide by a².
- Seen from the high-voltage side an impedance always looks larger.
Problem 3. Secondary winding impedance of a transformer NWPGCL
A 400 V/100 V, 500 VA single-phase transformer has an equivalent impedance of 0.5 p.u. If the primary winding impedance is 0.1 Ω, find the secondary winding impedance in ohms, both referred to the secondary.
Show step-by-step solution
- Zbase = V²/S (single phase).
- Total referred impedance Zeq2 = Z2 + Z1(V2/V1)².
- Read carefully whether a given value is in ohms or per unit: the answer changes from 10 Ω to 8 Ω here.
Problem 4. Voltage ratios at each tap of a distribution transformer DWASA
A 500 kVA, 13 200/480 V distribution transformer has four taps of 2.5 % each on its primary winding. What are the voltage ratios at each tapping?
Show step-by-step solution
- Taps are put on the HV winding because its current is small and fine steps are possible.
- Fewer primary turns in use gives a higher secondary voltage.
Problem 5. Turns ratio, source voltage and pf of a loaded transformer circuit DWASA
In the ideal-transformer circuit RP = 18 Ω (shunt across the primary), RL = 6 Ω, XL = 0.5 Ω in series with the source. V₂ = 120∠0° V across RL and the source power Ps = 5600 W. Find (a) the turns ratio a, (b) the source voltage Vs and (c) the input power factor.
Show step-by-step solution
- An inductor or capacitor takes no real power: use power balance over the resistors only.
- Refer a current to the primary by dividing by a; refer an impedance by multiplying by a².
Problem 6. Power shared by a shunt resistor and a transformer load DESCO
Find the percentage of the source power Ps that is dissipated in the 18 Ω resistor. The source feeds j0.5 Ω in series; the 18 Ω is across the primary of an ideal transformer with a = NP/NS = 2, and a 6 Ω load is on the secondary.
Show step-by-step solution
- Parallel resistors share power inversely as their resistances.
- When a question asks for a percentage, look for a ratio before reaching for numbers.
Problem 7. No-load current components of a transformer BPDB
A 30 kVA, 2400/240 V, 50 Hz transformer draws 138 W at pf 0.21 lagging on no load. Find I₀, Ic and Im.
Show step-by-step solution
- I0 = P0/(V cos φ0); Ic = I0 cos φ0; Im = I0 sin φ0; I0² = Ic² + Im².
- No-load pf is typically 0.1 to 0.3 lagging.
Problem 8. Exciting current of a step-up transformer on no load JOCL
A 30 kVA, 250/2500 V transformer on no load (step-up) draws 150 W at 0.25 pf lagging. Find the exciting current, core-loss and magnetising components.
Show step-by-step solution
- Always use the voltage of the winding that is actually energised.
- The kVA rating is not needed for a no-load problem; it is extra data.
Problem 9. Magnetising and iron-loss currents SGFL; BCPCL
A 2200/200 V transformer draws a no-load primary current of 0.6 A and absorbs 400 W. Find the magnetising and iron-loss currents.
Show step-by-step solution
- Different books use different symbols: Iw = Ic (working, core-loss component); Iμ = Im (magnetising component).
- Iμ = √(I0² − Iw²).
Problem 10. Transformer on load EGCB; BPDB
A single-phase 1000/200 V transformer takes 3 A at 0.2 pf lagging on no load. Find the primary current and power factor when the secondary supplies 280 A at 0.8 pf lagging.
Figure: load phasors of the transformerShow step-by-step solution
- I1 = I0 + I′2 as phasors, with I′2 = K I2.
- Lagging current: x − jy. Add components, never magnitudes: here 56 + 3 = 59 A would be wrong; the true value is 58.3 A.
Problem 11. Primary current and pf of a loaded transformer RPGCL
A 440/110 V single-phase transformer takes a no-load current of 5 A at 0.2 pf lagging. The secondary supplies 120 A at 0.8 pf lagging. Find the primary current.
Show step-by-step solution
- For pf 0.8, sin φ = 0.6. For pf 0.2, sin φ = 0.98. These pairs appear again and again.
Problem 12. Primary current and pf of a loaded transformer DPDC
A single-phase transformer has 1000 turns on the primary and 200 turns on the secondary. The no-load current is 3 A at 0.2 p.f. lagging. Calculate the primary current and power factor when the secondary current is 280 A at 0.8 p.f. lagging.
Show step-by-step solution
- "Active and reactive components" and "rectangular form" are the same method. Use whichever you write faster.
Problem 13. Transformer equivalent circuit from OC and SC tests BPDB
A 20 kVA, 8000/240 V, 60 Hz transformer gave: OC (primary) 8000 V, 0.214 A, 400 W; SC (primary) 489 V, 2.5 A, 240 W. Find the approximate equivalent circuit referred to the primary.
Figure: approximate equivalent circuit referred to primaryShow step-by-step solution
- OC test → shunt branch: Rc = V²/Poc is a quick alternative (8000²/400 = 160 kΩ).
- SC test → series branch: Req = Psc/Isc², Xeq = √(Z² − R²).
- Both tests here were on the primary, so the results are already referred to the primary.
Problem 14. Equivalent circuit parameters from O.C. and S.C. tests NWPGCL
A 75 kVA, 4600/230 V, 50 Hz transformer gave these test results. O.C. test: V = 289 V, I = 10.3 A, P = 521 W. S.C. test: V = 160 V, I = 16.3 A, P = 1200 W. Determine the core resistance Rc, the excitation reactance Xm and the voltage regulation at 0.75 lagging p.f.
Show step-by-step solution
- Compare the test current with rated current to find the test side.
- Regulation ≈ I(R cos φ + X sin φ)/V for lagging; use minus for leading.
Problem 15. Equivalent-circuit impedances of a 20 kVA transformer BPDB
The equivalent circuit impedances of a 20 kVA, 8000/240 V, 60 Hz transformer are to be determined. The open-circuit test and the short-circuit test were performed on the primary side: VOC = 8000 V, IOC = 0.214 A, POC = 400 W; VSC = 489 V, ISC = 2.5 A, PSC = 240 W. Find the impedances of the approximate equivalent circuit referred to the primary side.
Show step-by-step solution
- Parallel branch: think admittance. Series branch: think impedance.
Problem 16. Voltage regulation of a 10 kVA transformer at 95 % load EGCB; BUET M.Sc.
A 10 kVA, 11/0.4 kV single-phase transformer has R = 114 Ω and X = 800 Ω referred to the HT side. Find the voltage regulation at 95 % load, 0.85 pf lagging.
Show step-by-step solution
- Keep V, I, R and X all on the same side.
- Regulation ≈ I(R cos φ ± X sin φ)/V: plus for lagging, minus for leading.
Problem 17. Efficiency of a single-phase transformer at 75 % load BIFPCL
A single-phase, 5 kVA, 200/400 V, 50 Hz transformer has 150 W core loss and 175 W full-load copper loss. Find the efficiency at 75 % load and 0.7 pf lagging.
Show step-by-step solution
- η = x S cos φ / (x S cos φ + Pi + x²Pcu).
- Core loss never changes with load or power factor.
Problem 18. Transformer efficiency at unity power factor BGFCL; BCIC
In a single-phase 25 kVA, 2000/200 V transformer the iron and full-load copper losses are 350 W and 400 W. Find the efficiency at unity power factor and full load.
Show step-by-step solution
- Efficiency is highest at unity power factor because output is largest for the same losses.
Problem 19. Efficiency of a transformer at double load BWDB; BPDB
The core loss and copper loss of a 6.35/0.23 kV single-phase transformer are 50 W and 125 W at a 6.5 kW load. If the load is doubled, find the efficiency.
Show step-by-step solution
- Load × n → copper loss × n².
Problem 20. Full-load efficiency of a 1000 kVA transformer DPDC
Calculate the full-load efficiency at 0.8 power factor lagging for a 1000 kVA, 11 000/400 V, 50 Hz single-phase transformer. S.C. test: 2000 W, 120 V with full-load current; O.C. test: 1500 W at normal voltage.
Show step-by-step solution
- SC test power = Pcu (full load). OC test power = Pi.
- Exam questions often include data you do not need. Decide what the formula needs before you start.
Problem 21. Loss ratio for maximum efficiency at 75 % load BCS
If P₁ and P₂ are the iron and copper losses at full load and maximum efficiency occurs at 75 % of full load, find P₁ : P₂.
Show step-by-step solution
- Load fraction at maximum efficiency: x = √(Pi/Pcu), so Pi/Pcu = x².
Problem 22. All-day efficiency of a distribution transformer PGCB
A 100 kVA distribution transformer has a maximum efficiency of 98 % at 50 % of full load and unity power factor. The transformer undergoes a daily cycle: 100 kVA at p.f. 1 for 8 h; 30 kVA at p.f. 0.6 for 6 h; no load for 10 h. Find the all-day efficiency.
Show step-by-step solution
- All-day efficiency uses kWh, not kW.
- Use kVA for the copper-loss fraction and kW for the output.
- Iron loss × 24 h always.
Problem 23. Load sharing of two unequal transformers BCS
Two 2200/110 V transformers share 125 kVA at 0.8 pf lagging: A is 100 kVA, 0.9 % R, 10 % X; B is 50 kVA, 1 % R, 5 % X. Find the load shared.
Show step-by-step solution
- SA = S · ZB/(ZA + ZB). Put all per-unit impedances on a common base first.
- For sharing in proportion to rating, the per-unit impedances on their own bases must be equal.
Problem 24. Currents of a Δ–Y three-phase transformer NWPGCL
A 3-phase, 50 Hz transformer has a delta primary and star secondary; line voltages 22 000 V and 400 V. The primary line current is 5 A and the secondary load is balanced at 0.8 pf lagging. Find the currents and the output.
Show step-by-step solution
- Star: Iph = IL, Vph = VL/√3. Delta: Vph = VL, Iph = IL/√3.
- Do not use the turns ratio directly with line voltages in a Δ-Y transformer.
Problem 25. Auto-transformer rating and transferred powers NWPGCL
A two-winding transformer rated 2400/240 V, 50 kVA is reconnected as a step-up auto-transformer with 2400 V input. Find the auto-transformer rating and the inductively and conductively transferred powers at rated output and unity power factor.
Show step-by-step solution
- Auto-transformer rating = two-winding rating × (VH/(VH − VL)) = 50 × 2640/240 = 550 kVA.
- The closer the two voltages, the bigger the gain. The price is no isolation between the two sides.
Problem 26. Transformer rating at a lower frequency DPDC
A 120 kVA, 10/0.415 kV, Δ–Y transformer is designed for 60 Hz. What is the maximum allowable kVA at 50 Hz?
Show step-by-step solution
- Constant V/f keeps the flux constant. The same rule governs variable-frequency drives for induction motors.
- Running a 60 Hz transformer on 50 Hz at full voltage raises the flux by 20 % and saturates the core.
Problem 27. Referred impedance and regulation of a distribution transformer DPDC
A 50 kVA, 11/0.4 kV, Δ–Y distribution transformer has R = 1 % and X = 7 %. Find the phase impedance referred to the HV side and the regulation at 95 % load, 0.85 lagging.
Show step-by-step solution
- Zbase per phase: star VL²/S, delta 3VL²/S.
- Regulation (pu) ≈ x(Rpu cos φ + Xpu sin φ).
Found a mistake or have a better method? Leave a comment below. More topics from the question bank are in the other posts of this series.