Three-Phase Circuits question solutions for EEE job exams. 2 written questions and 34 math problems on Three-Phase Circuits, the kind asked in Bangladesh EEE recruitment exams (BPDB, PGCB, DPDC, DESCO, NWPGCL, EGCB, BCS and others), each solved in exam style: the given data, what is required, the formula used at every step, the substitution and the final answer.
This post is part 7 of the EEE Job Preparation Question Bank series. It covers three-phase circuits with 36 solved questions: 2 written (theory) questions and 16 math problems on phase sequence, star and delta loads, combined loads, unbalanced systems and wattmeter methods from recruitment exams (DPDC, PGCB, DWASA, BPDB, NWPGCL) and BUET admission tests, plus 18 practice problems on the same topics.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution is laid out the way an examiner wants to see it: the given data with symbols and values, the quantity required, and then each step as formula → substitution → result, with the reason for that step written beside it. It also shows how to think about that type of problem, a diagram, and what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
Formulas to Memorize First
- Phase sequence abc: Van = V∠0°, Vbn = V∠−120°, Vcn = V∠+120° (b lags a, c lags b).
- Star (Y): VL = √3 Vph, IL = Iph. Line voltage leads the phase voltage by 30°: Vab = √3 Van∠+30°.
- Delta (Δ): VL = Vph, IL = √3 Iph. Line current lags the phase current by 30°: Ia = √3 Iab∠−30°.
- Power (balanced, any connection): P = √3 VL IL cos φ = 3 Vph Iph cos φ = 3 Iph² R. Q = √3 VL IL sin φ. φ is the angle of the load impedance.
- Delta to star: ZY = ZΔ/3. Then solve one phase with Vph = VL/√3.
- Three-wire system: Ia + Ib + Ic = 0. Four-wire: IN = −(Ia + Ib + Ic).
- Two-wattmeter method: P = W1 + W2. For a balanced load W1 = VL IL cos(30° − φ), W2 = VL IL cos(30° + φ).
- Power factor from two wattmeters: tan φ = √3 (W1 − W2)/(W1 + W2).
- Special cases: pf = 1 → equal readings; pf = 0.5 → one reads zero; pf below 0.5 → one reads negative.
Part A: Written Questions on Three-Phase Circuits
Q1. Draw the connection diagram for the two-wattmeter method of measuring three-phase power of an unbalanced system. DESCO
Show full answer
How to draw it (three steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 1 of 3. Draw the three lines A, B and C from the supply to the three-phase load. No neutral is used.
Drawing step 2 of 3. Put wattmeter W1 with its current coil in series with line A. Connect its potential (pressure) coil from line A to line C.
Drawing step 3 of 3. Put wattmeter W2 with its current coil in series with line B and its potential coil from line B to line C. Line C, which has no current coil, is the common line for both potential coils.What it measures
The total three-phase power is the algebraic sum of the two readings: P = W1 + W2. This is true whether the load is balanced or unbalanced, and whether it is star or delta connected, as long as there are only three wires.
Why two wattmeters are enough
Instantaneous power is p = va ia + vb ib + vc ic. With three wires there is no neutral, so ia + ib + ic = 0, which gives ic = −(ia + ib). Substituting:
p = (va − vc) ia + (vb − vc) ib = vac ia + vbc ib
The first term is exactly what W1 measures (voltage A to C, current in A) and the second is what W2 measures. No assumption about balance was made. This is Blondel’s theorem: n wires need n − 1 wattmeters.
When it does not work
In a 4-wire system with an unbalanced load the neutral carries current, so ia + ib + ic is not zero. Then three wattmeters are needed, one per phase.
Extra information for a balanced load
W1 = VL IL cos(30° − φ) and W2 = VL IL cos(30° + φ), so the two readings also give the power factor: tan φ = √3 (W1 − W2)/(W1 + W2). If the pf is below 0.5 one meter reads backwards; its connections are reversed and its reading is taken as negative.
Keep in mind
Current coils in two lines, both potential coils returned to the third line. Total power = algebraic sum. Valid for any 3-wire load.
Q2. In a balanced 3-wire Y-connected system a 3-phase load has a phase voltage of 240 V and a line current of 5 A at a lagging power factor of 0.966. Draw the phasor diagram. PGCB
Show full answer
How to think about it
A balanced three-phase phasor diagram is one phasor copied three times at 120°. So work out everything for phase a, then rotate. Decide three things first: the reference, the phase sequence, and the power-factor angle.
- Reference: Van at 0°. Sequence: abc (assumed, as it is not stated).
- Power-factor angle: φ = cos⁻¹ 0.966 = 15°, lagging, so each current is 15° behind its own phase voltage.
- Line voltage: √3 × 240 = 415.7 V, and in a star each line voltage is 30° ahead of the corresponding phase voltage.
How to draw it (three steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 1 of 3. Draw the three phase voltages, each 240 V: Van along the reference axis, Vbn 120° behind it (clockwise), Vcn 120° ahead.
Drawing step 2 of 3. Draw the three line currents, each 5 A, each lagging its own phase voltage by 15°: Ia at −15°, Ib at −135°, Ic at +105°.
Drawing step 3 of 3. Draw the line voltages. Vab = Van − Vbn comes out √3 times as long and 30° ahead of Van. The other two follow at 120° intervals.What the diagram shows
- Each set of three phasors is balanced: equal lengths, 120° apart, sum zero. Because the currents add to zero, no neutral is needed (3-wire).
- The angle between a phase voltage and its current is the load angle, 15°. The angle between Vab and Ia is 30° + 15° = 45°; do not mistake that for the power-factor angle.
- Total power = 3 × 240 × 5 × 0.966 = 3477 W.
Keep in mind
Order of drawing: phase voltages, then currents (shifted by φ from their own phase voltage), then line voltages (√3 larger, 30° ahead in a star).
Part B: Solved Problems on Three-Phase Circuits
Problem 1. Phase voltage of the third phase in an abc sequence DWASA
In a balanced abc system Van = 220∠−20°. Find Vcn.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Van | 220∠−20° V | phase a |
| sequence | abc | positive |
Required (to find)
How to think about it. In a balanced set the three voltages have the same size and are 120° apart. The sequence abc tells the order in which they reach their peak: a, then b (120° later), then c (240° later). "Later" means a more negative angle.
The three phase voltages; each is 120° behind the one before it in the order a, b, c.
Solution (write it like this)
Explanation
Step 1. abc ruleVcn = Van∠−240°
c is two steps after a, so it lags by 240°.
Step 2. Angle−20° − 240°
= −260°
Subtract 240° from the angle of Van.
Step 3. Usual range−260° + 360°
= +100° → Vcn = 220∠100° V
Angles are normally quoted between −180° and +180°; lagging 240° is the same as leading 120°.
Answer: Vcn = 220∠100° V
Keep in mind- abc: Vbn = Van∠−120°, Vcn = Van∠+120°.
- acb (negative) sequence: the signs are swapped.
Problem 2. Other two phase voltages from one line-to-neutral voltage Practice problem
In a balanced positive (abc) sequence system Vbn = 110∠30° V. Find Van and Vcn.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vbn | 110∠30° V | phase b |
| sequence | abc | |
Required (to find)
How to think about it. Check: the three angles 150°, 30°, −90° are 120° apart and decrease in the order a, b, c.
Three phasors 120° apart.
Solution (write it like this)
Explanation
Step 1. Phase a (leads b)Van = Vbn∠+120°
= 110∠150° V
a leads b by 120°.
Step 2. Phase c (lags b)Vcn = Vbn∠−120°
= 110∠−90° V
c lags b by 120°.
Answer: Van = 110∠150° V, Vcn = 110∠−90° V.
Keep in mind- abc: Vbn = Van∠−120°, Vcn = Van∠+120°.
Problem 3. Finding the phase sequence from three voltages Practice problem
Find the phase sequence of van = 200 cos(ωt + 10°), vbn = 200 cos(ωt − 230°) and vcn = 200 cos(ωt − 110°).
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| van | 200 cos(ωt + 10°) | |
| vbn | 200 cos(ωt − 230°) | |
| vcn | 200 cos(ωt − 110°) | |
Required (to find)
How to think about it. Check the lag of each phase relative to a: the one lagging by 120° comes second. Mixing up "lag" and "lead" is the usual slip.
Counter-clockwise rotation: a, then c, then b.
Solution (write it like this)
Explanation
Step 1. PhasorsVan = 200∠10°
Vbn = 200∠−230° = 200∠130°
Vcn = 200∠−110°
Add 360° to −230° to bring it into the usual range.
Step 2. c after a10° − (−110°)
= 120° → Vcn lags Van
So c comes 120° after a.
Step 3. b after c−110° − (−230°)
= 120° → Vbn lags Vcn
And b comes 120° after c.
Step 4. Ordera → c → b
= acb (negative) sequence
The phasors pass a fixed axis in the order a, c, b.
Answer: acb (negative) sequence.
Keep in mind- abc: Vb = Va∠−120°, Vc = Va∠+120°.
- acb: Vc = Va∠−120°, Vb = Va∠+120°.
Problem 4. Impedance per phase of a Y load NWPGCL
For Y-connected loads on a 203 V line, the total power is 1200 W at 0.75 p.f. lagging. Calculate the impedance per phase.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 203 V | line voltage |
| P | 1200 W | total power |
| pf | 0.75 lagging | |
Required (to find)
How to think about it. Work on one phase. The total power and pf give the line current. In a star, the phase voltage is VL/√3 and the phase current equals the line current. Impedance is phase voltage over phase current, at the power-factor angle.
One impedance is between each line and the star point.
Solution (write it like this)
Explanation
Step 1. Phase voltageVph = VL/√3
= 203/√3
= 117.2 V
Star: each impedance is between a line and the neutral.
Step 2. Line currentIL = P/(√3 VL cos φ)
= 1200/(√3 × 203 × 0.75)
= 4.55 A
Total three-phase power formula, solved for current.
Step 3. Impedance magnitude|Z| = Vph/I
= 117.2/4.55
= 25.75 Ω
Ohm’s law for one phase.
Step 4. Angleφ = cos⁻¹ 0.75
= 41.4° (inductive)
The angle of the impedance is the power-factor angle; positive for lagging.
Step 5. RectangularZ = 25.75∠41.4°
= 19.3 + j17.0 Ω
Polar to rectangular: R = Z cos φ, X = Z sin φ.
Answer: Z = 25.75∠41.4° = 19.3 + j17.0 Ω per phase
Keep in mind- Zph = Vph/Iph ∠φ.
- P = √3 VL IL cos φ always uses line values.
Problem 5. Line current and power of a Y load on 2300 V DPDC
3-phase line voltages of 2300 V are impressed on a balanced wye-connected load consisting of a 100 Ω resistance per phase in series with 173.2 Ω inductive reactance per phase. Find the line current and the total power taken by the 3-phase load.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 2300 V | line voltage |
| R | 100 Ω | per phase |
| XL | 173.2 Ω | per phase |
Required (to find)
How to think about it. A balanced star load: solve one phase. The voltage across one impedance is the phase voltage; the current through it is the line current. Power is three times the power of one phase.
Each phase has 1328 V across 200 Ω.
Solution (write it like this)
Explanation
Step 1. Phase voltageVph = VL/√3
= 2300/√3
= 1328 V
Star: Vph = VL/√3.
Step 2. Phase impedance|Z| = √(R² + X²)
= √(100² + 173.2²)
= 200 Ω
Magnitude of R + jX. (100 and 173.2 = 100√3 make a 60° angle.)
Step 3. Line currentIL = Vph/|Z|
= 1328/200
= 6.64 A
Ohm’s law per phase; in a star the line current is the same current.
Step 4. Power factorpf = R/|Z|
= 100/200
= 0.5 lagging
pf = R/Z = cos 60°.
Step 5. Total powerP = 3I²R
= 3 × 6.64² × 100
= 13.2 kW
Only the resistance takes power: 3I²R. The check uses √3 VL IL cos φ.
Answer: Iline = 6.64 A; P = 13.2 kW
Keep in mind- Star: Vph = VL/√3, IL = Iph.
- Two ways to get power: 3I²R or √3 VL IL cos φ. Use one to check the other.
Problem 6. Impedance per phase from power data BUET Admission
In a Y-connected balanced three-phase circuit Vph = 208 V, p.f. = 0.6 and P = 300 W. Find Zph.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vph | 208 V | phase voltage |
| pf | 0.6 | power factor |
| P | 300 W | total power |
Required (to find)
How to think about it. Here the phase voltage is given directly, so use the per-phase form of the power equation: P = 3 Vph Iph cos φ. Then impedance = phase voltage ÷ phase current.
Per-phase circuit of the balanced load.
Solution (write it like this)
Explanation
Step 1. Power formulaP = 3VphIph cos φ
A power given without comment in a three-phase problem is the total.
Step 2. Phase currentIph = P/(3Vph cos φ)
= 300/(3 × 208 × 0.6)
= 0.80 A
Solve for the phase current.
Step 3. Impedance magnitude|Z| = Vph/Iph
= 208/0.80
= 259.6 Ω
Ohm’s law per phase.
Step 4. Polar to rectangularφ = cos⁻¹ 0.6
= 53.13°
Z = 259.6∠53.1°
= 155.8 + j207.7 Ω
pf 0.6 lagging: R = Z × 0.6 and X = Z × 0.8.
Step 5. If 300 W per phaseI = 300/(208 × 0.6)
= 2.40 A
|Z| = 208/2.40
= 86.5 Ω
State the assumption; the other reading of the question changes the answer by a factor of 3.
Answer: Zph = 259.6∠53.1° = 155.8 + j207.7 Ω (If 300 W were per phase, I = 2.40 A and |Z| = 86.5 Ω.)
Keep in mind- Ptotal = 3 × (power per phase).
- When a question is ambiguous, state your assumption and, if time allows, give both results.
Problem 7. Power factor and line current of a three-phase motor Practice problem
(a) A three-phase motor (a balanced Y load) draws 5.6 kW when the line voltage is 220 V and the line current is 18.2 A. Find its power factor. (b) Find the line current of a 30 kW three-phase motor at 0.85 pf lagging on a 440 V line.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| (a) P | 5.6 kW; VL = 220 V; IL = 18.2 A | |
| (b) P | 30 kW; pf = 0.85; VL = 440 V | |
Required (to find)
How to think about it. The formula holds for both Y and Δ connections because it uses line quantities.
The two cases.
Solution (write it like this)
Explanation
Step 1. (a) Power factorpf = P/(√3 VL IL)
= 5600/(√3 × 220 × 18.2)
= 0.807
Solve for cos θ.
Step 2. (b) Line currentIL = P/(√3 VL pf)
= 30 000/(√3 × 440 × 0.85)
= 46.31 A
Solve for IL.
Answer: (a) pf ≈ 0.807 (lagging, being a motor) (b) IL ≈ 46.3 A.
Problem 8. Total power of a balanced delta load MIST
A 3-phase delta load has Z = 20∠60° Ω and line voltage 400 V. Find total power and power per phase.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Z | 20∠60° Ω | per phase (delta) |
| VL | 400 V | line voltage |
Required (to find)
How to think about it. In a delta each impedance is connected directly between two lines, so it has the full line voltage across it. Find the current in one impedance, the power in one impedance, and multiply by three.
Each impedance has the full 400 V line voltage across it.
Solution (write it like this)
Explanation
Step 1. Delta voltageVph = VL
= 400 V
Delta: no √3 on the voltage.
Step 2. Phase currentIph = Vph/|Z|
= 400/20
= 20 A
Ohm’s law for one phase.
Step 3. Power per phasePph = VphIph cos θ
= 400 × 20 × 0.5
= 4 kW
Power in one phase = V I cos φ, where φ is the impedance angle.
Step 4. Total powerP = 3Pph
= 3 × 4
= 12 kW
Balanced load: three equal phases.
Answer: Ptotal = 12 kW; per phase = 4 kW
Keep in mind- Delta: Vph = VL, IL = √3 Iph (here 34.6 A).
- The power-factor angle is the angle of Z, not of anything else.
Problem 9. Line current and power of a Δ load PGCB
Three-phase line voltage of 400 V is impressed on a balanced Δ-connected load having a 10 Ω resistance and a 10 Ω inductive reactance in series in each phase. Find the line current and the total power.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 400 V | line voltage |
| R | 10 Ω, XL=10 Ω | per phase (delta) |
Required (to find)
How to think about it. Delta load again: phase voltage = line voltage. Get the phase current, then remember that the line current of a delta is √3 times the phase current.
The line current is √3 times the branch current.
Solution (write it like this)
Explanation
Step 1. Phase impedance|Z| = √(10² + 10²)
= 14.14 Ω
Magnitude of 10 + j10 is 10√2.
Step 2. Phase currentIph = VL/|Z|
= 400/14.14
= 28.3 A
Each branch is across a pair of lines.
Step 3. Line currentIline = √3 Iph
= 1.732 × 28.3
= 49.0 A
Each line feeds two branches whose currents are 120° apart; their difference is √3 times one of them.
Step 4. Total powerP = 3Iph²R
= 3 × 28.3² × 10
= 24 kW
Use 3Iph²R with the phase current, not the line current.
Answer: Iline = 49.0 A; P = 24 kW
Keep in mind- Delta: IL = √3 Iph.
- Power from 3Iph²R needs the current that actually flows in R.
Problem 10. Δ–Δ system: phase and line currents Practice problem
A balanced Δ load of 20 − j15 Ω per phase is connected to a Δ-connected positive-sequence source with Vab = 330∠0° V. Find the phase currents of the load and the line currents.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Z | 20 − j15 Ω | per phase (delta) |
| Vab | 330∠0° V | source line voltage |
Required (to find)
How to think about it. A capacitive load (−j15) makes the currents lead the voltages.
Δ source, Δ load.
Solution (write it like this)
Explanation
Step 1. Phase current ABZ = 25∠−36.87° Ω
IAB = Vab/Z
= 330/25∠−36.87°
= 13.2∠36.87° A
Ohm’s law per branch.
Step 2. Other phasesIBC = 13.2∠−83.13° A
ICA = 13.2∠156.87° A
Shift by ∓120°.
Step 3. Line current aIa = √3 IAB∠−30°
= √3 × 13.2∠6.87°
= 22.86∠6.87° A
Line current.
Step 4. Other linesIb = 22.86∠−113.13° A
Ic = 22.86∠126.87° A
Shift by ∓120°.
Answer: IAB = 13.2∠36.87° A (others ∓120°); Ia = 22.86∠6.87° A (others ∓120°).
Keep in mind- Δ–Δ: Vp = VL; IL = √3 Ip.
Problem 11. Phase current and line voltage of a Δ–Δ system from a line current Practice problem
A positive-sequence balanced Δ-connected source supplies a balanced Δ load of 18 + j12 Ω per phase. If Ia = 19.202∠35° A, find IAB and VAB.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Z | 18 + j12 Ω | per phase (delta) |
| Ia | 19.202∠35° A | line current |
| sequence | abc | |
Required (to find)
How to think about it. Δ load (abc): Ia = √3 IAB∠−30°. Remember the direction of the 30° shift by sketching the three phase currents.
Balanced delta load.
Solution (write it like this)
Explanation
Step 1. Phase currentIAB = (Ia/√3)∠(35° + 30°)
= (19.202/√3)∠65°
= 11.09∠65° A
The phase current leads the line current by 30°.
Step 2. ImpedanceZ = 18 + j12
= 21.63∠33.69° Ω
Per-phase load impedance.
Step 3. Line voltageVAB = IABZ
= 11.09 × 21.63∠(65° + 33.69°)
= 239.8∠98.69° V
Ohm’s law for one delta phase.
Answer: IAB ≈ 11.09∠65° A; VAB ≈ 240∠98.69° V.
Keep in mind- Δ: IL = √3 Ip, lagging by 30° (abc).
- VAB = IAB ZΔ.
Problem 12. Line currents of a Y source feeding a Δ load MPL
A balanced abc-sequence Y-connected source with Van = 220∠0° V feeds a balanced Δ load Z = 20 − j40 Ω per phase. Calculate the line currents.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Van | 220∠0° V | Y source |
| ZΔ | 20 − j40 Ω | per phase |
| sequence | abc | |
Required (to find)
How to think about it. Two 30° shifts, in opposite senses. Going from a star phase voltage to a line voltage: × √3 and +30°. Going from a delta phase current to a line current: × √3 and −30°. Do them one at a time.
The 30° shifts: Vab is 30° ahead of Van, and Ia is 30° behind Iab.
Solution (write it like this)
Explanation
Step 1. Line voltageVab = √3 Van∠+30°
= √3 × 220∠30°
= 381∠30° V
A delta load needs line-to-line voltages. Vab leads Van by 30°.
Step 2. Load impedanceZ = 20 − j40
= 44.72∠−63.43° Ω
Polar form makes the division easy. The negative angle means a capacitive load.
Step 3. Phase currentIab = Vab/Z
= 381∠30°/44.72∠−63.43°
= 8.52∠93.43° A
Divide magnitudes, subtract angles.
Step 4. Line currentIa = √3 Iab∠−30°
= √3 × 8.52∠63.43°
= 14.76∠63.43° A
Line current of a delta: √3 times and 30° behind the phase current.
Step 5. Other linesIb = 14.76∠−56.57° A
Ic = 14.76∠−176.57° A
Balanced: rotate by −120° each time.
Answer: Ia = 14.76∠63.43° A; Ib = 14.76∠−56.57° A; Ic = 14.76∠−176.57° A
Keep in mind- Y: Vab = √3 Van∠+30°. Δ: Ia = √3 Iab∠−30°.
- Shortcut: convert Δ to Y (Z/3 = 14.9∠−63.43°) and Ia = Van/(Z/3) = 14.76∠63.43° directly.
Problem 13. Phase and line currents of a Y source feeding a Δ load Practice problem
A balanced abc-sequence Y-connected source with Van = 100∠10° V supplies a balanced Δ load of 8 + j4 Ω per phase. Find the phase and line currents.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Van | 100∠10° V | Y source |
| ZΔ | 8 + j4 Ω | per phase |
| sequence | abc | |
Required (to find)
- phase currents
- line currents
How to think about it. Check: Ia = Van/(ZΔ/3) = 100∠10°/(2.667 + j1.333) = 33.54∠−16.57° A ✓.
Balanced Δ load.
Solution (write it like this)
Explanation
Step 1. Line voltageVab = √3 Van∠+30°
= 173.2∠40° V
Line voltage leads phase voltage by 30°.
Step 2. Phase currentsIAB = Vab/Z
= 173.2∠40°/8.944∠26.57°
= 19.36∠13.43° A
IBC = 19.36∠−106.57° A, ICA = 19.36∠133.43° A
Phase currents 120° apart.
Step 3. Line current aIa = √3 IAB∠−30°
= 33.54∠−16.57° A
Line current.
Step 4. Other linesIb = 33.54∠−136.57° A
Ic = 33.54∠103.43° A
Shift by ∓120°.
Answer: Phase currents 19.36 A (IAB at 13.43°); line currents 33.54 A (Ia at −16.57°).
Problem 14. Delta source feeding a balanced star load Practice problem
A balanced positive-sequence Δ-connected source with a line voltage of 210 V supplies a balanced Y load of 40 + j25 Ω per phase. Taking Vab as the reference, find the line (= phase) currents of the load.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 210 V | Δ source line voltage (Vab reference) |
| ZY | 40 + j25 Ω | per phase |
Required (to find)
How to think about it. Any balanced source can be replaced by its Y equivalent; then a single-phase calculation gives everything.
Line voltage, phase voltage and the three load currents (not to the same scale).
Solution (write it like this)
Explanation
Step 1. Equivalent Y sourceVan = (VL/√3)∠−30°
= (210/√3)∠−30°
= 121.2∠−30° V
In the abc sequence the phase voltage lags the line voltage by 30°.
Step 2. ImpedanceZY = 40 + j25
= 47.17∠32° Ω
Per-phase impedance.
Step 3. Line current aIa = Van/ZY
= 121.2∠−30°/47.17∠32°
= 2.57∠−62° A
One-phase calculation.
Step 4. Other linesIb = 2.57∠−182° A
Ic = 2.57∠58° A
Shift by −120° and +120°.
Answer: Ia = 2.57∠−62° A, Ib = 2.57∠−182° A, Ic = 2.57∠58° A.
Keep in mind- Δ → Y source: Vp = VL/√3∠−30° (abc).
- Balanced: other phases are ±120° shifts.
Problem 15. Line currents of a Δ source feeding a Y load Practice problem
In a balanced Δ–Y circuit, Vab = 240∠15° V and ZY = 12 + j15 Ω. Find the line currents.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vab | 240∠15° V | line voltage |
| ZY | 12 + j15 Ω | per phase |
Required (to find)
How to think about it. Be careful when subtracting 120° from −66.34°: −186.34° is the same as +173.66°.
Balanced Y load on a Δ source.
Solution (write it like this)
Explanation
Step 1. Equivalent phase voltageVan = (Vab/√3)∠−30°
= 138.6∠−15° V
Divide by √3 and shift by −30°.
Step 2. ImpedanceZY = 12 + j15
= 19.21∠51.34° Ω
Polar form.
Step 3. Line current aIa = Van/ZY
= 138.6∠−15°/19.21∠51.34°
= 7.21∠−66.34° A
Ohm’s law per phase.
Step 4. Other linesIb = 7.21∠173.66° A
Ic = 7.21∠53.66° A
Shift by ∓120°.
Answer: Ia = 7.21∠−66.34° A, Ib = 7.21∠173.66° A, Ic = 7.21∠53.66° A.
Keep in mind- Δ source → equivalent Y: Van = Vab/√3∠−30°.
Problem 16. Y and Δ loads on one line APSCL
A balanced three-phase source of 210 V line voltage feeds, through lines of Zl = 1 + j1 Ω, a Y load ZY = 12 + j5 Ω in parallel with a Δ load ZΔ = 24 − j30 Ω per phase. Find the magnitude of the line current of the combined loads.
Figure: per-phase equivalent of the Y and Δ loads
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 210 V | source line voltage |
| Zl | 1 + j1 Ω | line |
| ZY | 12 + j5 Ω | Y load |
| ZΔ | 24 − j30 Ω | Δ load |
Required (to find)
How to think about it. When a star load and a delta load are on the same lines, make them the same kind: convert the delta to its equivalent star (divide by 3). Then all three phases are identical and one phase can be solved as a simple series-parallel circuit.
Key formula
Solution (write it like this)
Explanation
Step 1. Δ → YZΔ/3 = (24 − j30)/3
= 8 − j10 Ω
ZY = ZΔ/3 for a balanced delta.
Step 2. Phase voltageVph = 210/√3
= 121.24 V
Per-phase circuits use the line-to-neutral voltage.
Step 3. Parallel loads(12 + j5)(8 − j10)/(20 − j5)
= (146 − j80)/(20 − j5)
= 7.81 − j2.05 Ω
The two star loads are in parallel in the per-phase circuit: product over sum, with complex numbers.
Step 4. Per-phase totalZ = 1 + j1 + 7.81 − j2.05
= 8.81 − j1.05 Ω (8.87 Ω)
The line impedance is in series with the combined load.
Step 5. Line currentIL = Vph/|Z|
= 121.24/8.87
= 13.66 A
Only the magnitude is asked, so divide magnitudes.
Answer: |IL| ≈ 13.7 A.
Keep in mind- Balanced Δ → Y: divide the impedance by 3.
- Per-phase method: Vph = VL/√3, then ordinary circuit analysis.
Problem 17. Supply current of Y and Δ loads on one line DPDC
A balanced Δ load of pure resistances of 15 Ω per phase is in parallel with a balanced-Y load with phase impedances 8 + j6 Ω. Identical impedances of 2 + j5 Ω are in each of the three lines connecting the combined loads to a 110 V three-phase supply. Find the current drawn from the supply and the line voltage at the combined loads.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| RΔ | 15 Ω | Δ load per phase |
| ZY | 8 + j6 Ω | Y load |
| Zline | 2 + j5 Ω | line |
| VL | 110 V | supply |
Required (to find)
How to think about it. The same per-phase method. Convert the delta to a star, put it in parallel with the star load, add the line impedance in series. The load voltage is found from the current and the combined load impedance, then converted back to a line value.
Per-phase equivalent: the line in series with the two loads in parallel.
Solution (write it like this)
Explanation
15 Ω in delta is the same as 5 Ω in star.
Step 2. Parallel loadsZ = 5(8 + j6)/(13 + j6)
= 3.41 + j0.73 Ω (3.49 Ω)
Product over sum: 5(8 + j6)/(5 + 8 + j6).
Step 3. Add the lineZT = 5.41 + j5.73 Ω (7.88 Ω)
Series line impedance per phase.
Step 4. Current and load voltageVph = 110/√3
= 63.5 V
I = 63.5/7.88
= 8.05 A
Vload = 8.05 × 3.49
= 28.1 V
VL = √3 × 28.1
= 48.7 V
Per-phase supply voltage, then Ohm’s law. Load phase voltage = I × Zload; multiply by √3 for the line value.
Answer: Iline = 8.05 A; line voltage at the loads = 48.7 V
Keep in mind- The voltage at the load is much lower than at the supply here (48.7 V of 110 V) because the line impedance is large.
Problem 18. Two balanced loads and the capacitors for unity power factor Practice problem
An 840 V (line, rms), 60 Hz, abc supply feeds two balanced loads: load 1 is Y-connected with 30 + j40 Ω per phase; load 2 is a three-phase motor taking 48 kW at 0.8 power factor lagging. Find (a) the complex power of the combined load, (b) the kVAR rating and capacitance of each of three Δ-connected capacitors that raise the power factor to unity, and (c) the supply current at unity power factor.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 840 V | line voltage |
| f | 60 Hz | |
| ZY | 30 + j40 Ω | load 1 per phase |
| P₂ | 48 kW at 0.8 lag | motor |
Required (to find)
- S
- QC, C (per Δ capacitor)
- I (at unity pf)
How to think about it. Δ-connected capacitors need one-third of the capacitance of Y-connected ones for the same kVAR, because each sees √3 times more voltage.
Real and reactive powers of each load.
Solution (write it like this)
Explanation
Step 1. Load 1Vp = 840/√3
= 485 V
I = 485/50
= 9.70 A
S1 = 3I²Z
= 8.47 + j11.29 kVA
Three phases, each with |Z| = 50 Ω.
Step 2. Load 2S2 = 48 + j48 × 0.75
= 48 + j36 kVA
Q = P tan φ.
Step 3. TotalS = S1 + S2
= 56.47 + j47.29 kVA
Complex powers add.
Step 4. Each Δ capacitorQ = 47.29/3
= 15.76 kvar
C = Q/(ωVL²)
= 15 763/(377 × 840²)
= 59.3 μF
In Δ each capacitor sees the full line voltage.
Step 5. Current at unity pfI = P/(√3 VL)
= 56 470/(√3 × 840)
= 38.8 A
Only real power remains.
Answer: (a) 56.47 + j47.29 kVA (b) 15.76 kVAR, about 59.3 μF each (c) ≈ 38.8 A.
Keep in mind- Stotal = ΣSk.
- Δ capacitor: C = Qphase/(ωVL²).
Problem 19. Two balanced loads on a 240 kV line: powers, line current and correction Practice problem
Two balanced loads are connected to a 240 kV rms, 60 Hz line. Load 1 draws 30 kW at 0.6 pf lagging; load 2 draws 45 kvar at 0.8 pf lagging. Find (a) the total complex, real and reactive power, (b) the line current, (c) the kvar rating and capacitance of each of three Δ-connected capacitors that raise the pf to 0.9 lagging.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 240 kV | line voltage |
| f | 60 Hz | |
| load 1 | 30 kW at 0.6 lag | |
| load 2 | 45 kvar at 0.8 lag | |
| pf₂ | 0.9 lagging | target |
Required (to find)
- S, P, Q
- IL
- QC, C (per capacitor)
How to think about it. At 240 kV a tiny capacitance gives a large kvar rating because QC = ωCV² grows with V².
Real and reactive powers before and after correction.
Solution (write it like this)
Explanation
Step 1. LoadsS1 = 30/0.6
= 50 kVA → 30 + j40 kVA
S2 = 45/0.6
= 75 kVA → 60 + j45 kVA
sin θ = 0.8 for 0.6 pf; sin θ = 0.6 for 0.8 pf.
Step 2. TotalS = 90 + j85 kVA
= 123.8∠43.36° kVA
Add.
Step 3. Line currentIL = |S|/(√3 VL)
= 123 800/(√3 × 240 000)
= 0.298 A
Line current at a very high voltage is small.
Step 4. Capacitor kvarQ₂ = 90 tan 25.84°
= 43.59 kvar
QC = 85 − 43.59
= 41.41 kvar
per capacitor
= 13.80 kvar
Three capacitors share it.
Step 5. CapacitanceC = Q/(ωVL²)
= 13 800/(2π × 60 × 240 000²)
= 635.7 pF
Δ capacitors see the line voltage.
Answer: S = 90 + j85 kVA (123.8 kVA); IL ≈ 0.298 A; capacitors 13.8 kvar each, C ≈ 636 pF.
Keep in mind- QC = P(tan θ1 − tan θ2); C = QC/(ωVL²) per Δ capacitor.
Problem 20. Line current of a store with three balanced loads Practice problem
A store has three balanced three-phase loads: 16 kVA at 0.85 pf lagging, 12 kVA at 0.6 pf lagging and 8 kW at unity pf. The line voltage at the loads is 208 V rms, 60 Hz, and the line impedance is 0.4 + j0.8 Ω per phase. Find the line current, the complex power delivered to the loads and the power lost in the lines.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| load 1 | 16 kVA at 0.85 lag | |
| load 2 | 12 kVA at 0.6 lag | |
| load 3 | 8 kW at unity pf | |
| VL | 208 V | at the loads |
| Zline | 0.4 + j0.8 Ω | per phase |
Required (to find)
How to think about it. The line loss here is more than a third of the load power — a sign that 208 V is a low voltage for 34 kVA over this line. Raising the voltage or improving the power factor would cut it sharply (loss ∝ I²).
Real power of each load and of the line.
Solution (write it like this)
Explanation
Step 1. Load 1P₁ = 16 × 0.85
= 13.6 kW
Q₁ = 16 × 0.527
= 8.43 kvar
sin φ = √(1 − 0.85²) = 0.527.
Step 2. Loads 2 and 3P₂ = 12 × 0.6
= 7.2 kW
Q₂ = 12 × 0.8
= 9.6 kvar
P₃ = 8 kW
P = S cos φ, Q = S sin φ.
Step 3. TotalS = 28.8 + j18.03 kVA
|S|
= 33.98 kVA
Add the real and reactive parts.
Step 4. Line currentIL = |S|/(√3 VL)
= 33 980/(√3 × 208)
= 94.3 A
Line current of a balanced load.
Step 5. Line lossPloss = 3IL²R
= 3 × 94.3² × 0.4
= 10.7 kW
Per-phase line impedance carries the line current.
Answer: IL ≈ 94.3 A; Sloads = 28.8 + j18.03 kVA; line loss ≈ 10.7 kW.
Keep in mind- P = S cos φ, Q = S sin φ.
- IL = |S|/(√3 VL).
- Line loss = 3IL²Rline.
Problem 21. Power in the line and load of a Y–Y system DNCC
A load of 12.8∠38.66° Ω per phase is connected to a balanced three-phase source (110 V per phase) through a line of 5 Ω resistance and −j2 Ω reactance. How much power is dissipated in the line and in the load? (Y–Y connection assumed.)
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vph | 110 V | source per phase |
| Zload | 12.8∠38.66° Ω | per phase |
| Zline | 5 − j2 Ω | per phase |
Required (to find)
How to think about it. One phase of a Y-Y system is a simple series circuit: source, line, load. Convert the load to rectangular form to see its resistance, find the current, then use I²R for each resistance and multiply by 3.
One phase of the system: line and load in series.
Solution (write it like this)
Explanation
Step 1. Per-phase impedanceZ = (5 − j2) + (10 + j8)
= 15 + j6 = 16.16∠21.8° Ω
12.8 cos 38.66° = 10 and 12.8 sin 38.66° = 8. Add to the line impedance.
Step 2. Current and line lossI = 110/16.16
= 6.81 A
Pline = 3I²Rline
= 3 × 46.3 × 5
= 695 W
Current per phase. Three lines each lose I²R.
Step 3. Load powerPload = 3I²Rload
= 3 × 46.3 × 10
= 1390 W
The load resistance is 10 Ω per phase. The reactances take no real power.
Answer: Line loss = 695 W; Load power = 1390 W
Keep in mind- Line loss = 3I²Rline; load power = 3I²Rload.
- Efficiency of transmission here = 1390/2085 = 66.7 %.
Problem 22. Third line current of a 3-wire system BUET Admission
Two line currents of an unbalanced 3-phase, 3-wire system are 100∠90° A and 110∠−10° A. Find the third line current.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| I₁ | 100∠90° A | line 1 |
| I₂ | 110∠−10° A | line 2 |
Required (to find)
How to think about it. A three-wire system has no neutral, so the three line currents have nowhere else to go: by KCL they must add to zero. The third current is minus the sum of the other two.
The three line currents. The third is equal and opposite to the sum of the other two.
Solution (write it like this)
Explanation
Step 1. KCL (3-wire)I₁ + I₂ + I₃ = 0
KCL for the whole load treated as one node.
Step 2. Rectangular sumI₁ + I₂ = j100 + (108.3 − j19.1)
= 108.3 + j80.9
Add in rectangular form: 100∠90° is purely imaginary.
Step 3. Third currentI₃ = −(I₁ + I₂)
= −108.3 − j80.9
= 135.2∠−143.2° A
With no neutral wire, KCL at the load star point forces the three line currents to add to zero, so the third is minus the sum of the other two. Convert back to polar form for the answer.
Answer: I₃ = −(I₁ + I₂) = −108.3 − j80.9 = 135.2∠−143.2° A
Keep in mind- 3-wire: Ia + Ib + Ic = 0, balanced or not.
- For the angle in the third quadrant: tan⁻¹(80.9/108.3) = 36.8°, then −180° + 36.8° = −143.2°.
Problem 23. Neutral current of an unbalanced Y load CPGCBL
The unbalanced Y load has balanced phase voltages of 100 V in the acb sequence. Calculate the neutral current. ZA = 15 Ω, ZB = 10 + j5 Ω, ZC = 6 − j8 Ω.
Figure: unbalanced Y load with neutral N
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vph | 100 V | balanced, acb |
| ZA | 15 Ω | |
| ZB | 10 + j5 Ω | |
| ZC | 6 − j8 Ω | |
Required (to find)
How to think about it. With a neutral wire each phase works independently: each impedance has its own phase voltage across it. Find the three currents separately, add them, and the neutral carries the return of that sum. Watch the sequence: acb, not abc.
Key formula
Solution (write it like this)
Explanation
Step 1. Phase voltages (acb)VAN = 100∠0°, VBN = 100∠120°, VCN = 100∠−120° V
In the acb (negative) sequence b leads a by 120° and c lags.
Step 2. Phase currentsIA = 100/15
= 6.667∠0° A
IB = 100∠120°/(10 + j5)
= 8.944∠93.43° A
IC = 100∠−120°/(6 − j8)
= 10∠−66.87° A
One division per phase, in polar form.
Step 3. SumIA + IB + IC
= 10.06∠−1.5° A
Add in rectangular form. In a balanced load this would be zero.
Step 4. Neutral currentIN = −(IA + IB + IC)
= 10.06∠178.5° A
The neutral current flows the opposite way to the sum of the line currents.
Answer: |IN| ≈ 10.06 A.
Keep in mind- 4-wire star: IN = −(IA + IB + IC).
- Always check the phase sequence before writing the angles.
Problem 24. Three-wattmeter readings on an unbalanced star load Practice problem
An unbalanced four-wire Y load (ZA = 15 Ω, ZB = 10 + j5 Ω, ZC = 6 − j8 Ω) has balanced phase voltages of 100 V rms. Three wattmeters are connected with their current coils in lines a, b, c and their voltage coils from each line to the neutral. Find each reading and the total power.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vph | 100 V rms | balanced |
| ZA | 15 Ω | |
| ZB | 10 + j5 Ω | |
| ZC | 6 − j8 Ω | |
Required (to find)
How to think about it. The phase sequence does not affect the readings here because each wattmeter sees only its own phase voltage and current. (It does affect the neutral current.)
Each wattmeter reads one phase.
Solution (write it like this)
Explanation
Step 1. W1IA = 100/15
= 6.67 A
P = I²R
= 6.67² × 15
= 666.7 W
Pure resistance.
Step 2. W2IB = 100/11.18
= 8.944 A
P = 8.944² × 10
= 800 W
Only the resistive part absorbs power.
Step 3. W3IC = 100/10
= 10 A
P = 10² × 6
= 600 W
The capacitive part absorbs none.
Step 4. TotalPT = 666.7 + 800 + 600
= 2066.7 W
Sum of the three readings.
Answer: W1 ≈ 666.7 W, W2 = 800 W, W3 = 600 W; total ≈ 2066.7 W.
Keep in mind- Three-wattmeter method: Wk = Vk Ik cos θk; total = ΣWk.
- Works for any (unbalanced) 4-wire load.
Problem 25. Unbalanced Δ load: phase currents and total power BPDB
The unbalanced Δ load is supplied by balanced line-to-line voltages of 240 V in the abc sequence. Branch AB is 10 Ω in series with −j5 Ω, branch BC is 16 Ω, branch CA is 8 Ω in series with j6 Ω. Find the phase currents and the total power. (Branch values read from the figure.)
Figure: unbalanced delta load
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 240 V | balanced, abc |
| ZAB | 10 − j5 Ω | |
| ZBC | 16 Ω | |
| ZCA | 8 + j6 Ω | |
Required (to find)
How to think about it. An unbalanced delta is easy because each branch is directly across a known line voltage. Treat the three branches as three separate single-phase circuits, then add the powers.
Key formula
Solution (write it like this)
Explanation
Step 1. Line voltagesVAB = 240∠0°, VBC = 240∠−120°, VCA = 240∠120° V
Line voltages of an abc sequence, 120° apart.
Step 2. Branch ABIAB = VAB/ZAB
= 240/11.18∠−26.57°
= 21.47∠26.57° A
Branch AB is capacitive, so its current leads its voltage.
Step 3. Branch BCIBC = 240∠−120°/16
= 15∠−120° A
A pure resistance: current in phase with VBC.
Step 4. Branch CAICA = 240∠120°/10∠36.87°
= 24∠83.13° A
Branch CA is inductive.
Step 5. Real powerP = ΣI²R
= 21.47² × 10 + 15² × 16 + 24² × 8
= 12 816 W
Only resistances take real power: I²R in each branch.
Step 6. Reactive powerQ = ΣI²X
= −21.47² × 5 + 24² × 6
= 1152 var
Capacitive VAR is negative, inductive positive; the resistor branch has none.
Answer: IAB = 21.47∠26.57°, IBC = 15∠−120°, ICA = 24∠83.13° A; P = 12.82 kW, Q = 1.15 kvar.
Keep in mind- Unbalanced Δ: solve each branch on its own line voltage.
- Total P and Q are sums over the branches.
Problem 26. Unbalanced Δ load with a j25 Ω, a 30∠30° Ω and a 40 Ω branch Practice problem
A 240 V rms positive-sequence supply feeds an unbalanced Δ load: ZAB = j25 Ω, ZBC = 30∠30° Ω, ZCA = 40 Ω. Find the phase currents and the total complex power (take VAB = 240∠0°).
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VAB | 240∠0° V rms | abc |
| ZAB | j25 Ω | |
| ZBC | 30∠30° Ω | |
| ZCA | 40 Ω | |
Required (to find)
How to think about it. Only the resistive parts absorb real power: 30 cos 30° Ω and 40 Ω.
Three different branches.
Solution (write it like this)
Explanation
Step 1. Branch ABIAB = 240/j25
= 9.6∠−90° A
Inductive branch.
Step 2. Branch BCIBC = 240∠−120°/30∠30°
= 8∠−150° A
VBC lags VAB by 120°.
Step 3. Branch CAICA = 240∠120°/40
= 6∠120° A
Resistive branch.
Step 4. Complex powerS = V²Σ(1/Z*)
= j2304 + (1662.8 + j960) + 1440
= 3103 + j3264 VA
S = V²/Z* per branch.
Answer: IAB = 9.6∠−90° A, IBC = 8∠−150° A, ICA = 6∠120° A; S ≈ 3103 + j3264 VA (4503∠46.45° VA).
Keep in mind- Unbalanced Δ: solve each branch separately.
Problem 27. Three wattmeters on an unbalanced Δ load, one of them reading zero Practice problem
The unbalanced Δ load with ZAB = 10 − j5 Ω, ZBC = 16 Ω and ZCA = 8 + j6 Ω is supplied by balanced 240 V abc line voltages (Vab = 240∠0°). Three wattmeters are connected in lines a, b and c with their common voltage-coil point joined to line B. Find the readings and the total power.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vab | 240∠0° V | abc |
| ZAB | 10 − j5 Ω | |
| ZBC | 16 Ω | |
| ZCA | 8 + j6 Ω | |
| common point | | line B |
Required (to find)
How to think about it. This is the two-wattmeter method in disguise: with the common point on one line, that line’s meter reads zero and the other two give the total.
Common voltage point on line B.
Solution (write it like this)
Explanation
Step 1. Phase currentsIAB = 240/(10 − j5)
= 19.2 + j9.6 A
IBC = 15∠−120° A
ICA = 24∠83.13° A
Branch currents.
Step 2. Line currentsIa = IAB − ICA
= 16.33 − j14.23 A
Ic = ICA − IBC
= 10.37 + j36.82 A
KCL at A and C.
Step 3. W1 and W2W1 = Re(VabIa*)
= 240 × 16.33
= 3.92 kW
W2 = 0 (no voltage on its coil)
Voltage on W2 is zero.
Step 4. W3W3 = Re(VcbIc*), Vcb = 240∠60°
= 120 × 10.37 + 207.8 × 36.82
= 8.90 kW
Vcb = −Vbc = 240∠60°.
Step 5. TotalPT = 3.92 + 0 + 8.90
= 12.82 kW
Check with I²R of the branches.
Answer: W1 ≈ 3.92 kW, W2 = 0, W3 ≈ 8.90 kW; total ≈ 12.82 kW.
Keep in mind- Blondel: n − 1 wattmeters suffice for n wires.
Problem 28. Balanced delta load with two wattmeters
A 3-phase, 3-wire, 100 V, ABC-sequence system feeds a balanced delta load of 20∠45° Ω per phase. Find the phase and line currents and the two wattmeter readings.
Figure: two-wattmeter connection and phasor diagram
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| VL | 100 V | abc, 3-wire |
| Z | 20∠45° Ω | per phase (delta) |
Required (to find)
How to think about it. Three stages: phase currents of the delta (line voltage ÷ impedance), line currents (√3 times, 30° behind), then the wattmeter formulas for a balanced load.
Key formula
Solution (write it like this)
Explanation
Step 1. Line voltagesVAB = 100∠0°, VBC = 100∠−120°, VCA = 100∠120° V
The three line voltages in the ABC sequence.
Step 2. Phase currentsIAB = VAB/Z
= 100∠0°/20∠45°
= 5∠−45° A
IBC = 5∠−165° A, ICA = 5∠75° A
Each phase current lags its own voltage by the load angle, 45°.
Step 3. Line currentsIA = IAB − ICA
= 8.66∠−75° A
IB = 8.66∠165° A, IC = 8.66∠45° A
Line current = difference of two phase currents: √3 times as large and 30° behind.
Step 4. W₁W₁ = VLIL cos(30° − φ)
= 866 × cos(−15°)
= 836.5 W
W1 = VL IL cos(30° − φ).
Step 5. W₂W₂ = VLIL cos(30° + φ)
= 866 × cos 75°
= 224.1 W
W2 = VL IL cos(30° + φ).
Step 6. CheckW₁ + W₂ = 1060.6 W
3Iph²R = 3 × 25 × 14.14
= 1060.7 W ✓
The sum must equal the power found from 3I²R.
Answer: Iph = 5 A, IL = 8.66 A, W₁ = 836.5 W, W₂ = 224.1 W, total = 1060.6 W, pf = 0.707 lagging.
Keep in mind- Balanced load: W1 = VLIL cos(30° − φ), W2 = VLIL cos(30° + φ).
- The larger reading belongs to the cos(30° − φ) meter for a lagging load.
Problem 29. Predicting two-wattmeter readings for balanced Y and Δ loads Practice problem
(a) A balanced Y load of 8 + j6 Ω per phase is on 208 V lines. Predict the two wattmeter readings and find PT and QT. (b) Repeat for a balanced Δ load of 30 − j40 Ω per phase on 440 V lines.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| (a) ZY | 8 + j6 Ω | per phase; VL = 208 V |
| (b) ZΔ | 30 − j40 Ω | per phase; VL = 440 V |
Required (to find)
How to think about it. Check: PT = 3Ip²R in each case (3 × 12.01² × 8 and 3 × 8.8² × 30).
Readings for both loads.
Solution (write it like this)
Explanation
Step 1. (a) Line currentIL = (208/√3)/10
= 12.01 A
θ = 36.87°
VLIL
= 2498 VA
Y load: IL = Ip.
Step 2. (a) ReadingsW1 = 2498 cos 66.87°
= 981 W
W2 = 2498 cos 6.87°
= 2480 W
PT
= 3461 W
QT = √3(2480 − 981)
= 2596 var
Readings and totals.
Step 3. (b) Line currentIp = 440/50
= 8.8 A
IL = √3 × 8.8
= 15.24 A
θ = −53.13°
VLIL
= 6707 VA
Δ load: IL = √3 Ip.
Step 4. (b) ReadingsW1 = 6707 cos(−23.13°)
= 6167 W
W2 = 6707 cos(−83.13°)
= 802 W
PT
= 6970 W
QT = √3(802 − 6167)
= −9293 var
Capacitive load: Q negative.
Answer: (a) W1 ≈ 981 W, W2 ≈ 2480 W, PT ≈ 3461 W, QT ≈ 2596 var (b) W1 ≈ 6.17 kW, W2 ≈ 0.80 kW, PT ≈ 6.97 kW, QT ≈ −9.29 kvar.
Keep in mind- W1,₂ = VLIL cos(θ ± 30°).
Problem 30. Y–Δ system: two-wattmeter readings BCMCL
A balanced Y-connected source (EAB = 208∠0° V, abc sequence) feeds the Δ load shown through wattmeters W₁ and W₂, whose voltage coils are joined to line C. Zab = 10 Ω, Zbc = 10 + j10 Ω, Zca = 10 − j10 Ω. Find the reading of W₁ and W₂ and the total power.
Figure: Y–Δ load with two wattmeters
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| EAB | 208∠0° V | abc |
| Zab | 10 Ω | |
| Zbc | 10 + j10 Ω | |
| Zca | 10 − j10 Ω | |
| W₁, W₂ | | voltage coils to line C |
Required (to find)
How to think about it. The load is unbalanced, so the cos(30° ± φ) formulas do not apply. Go back to what a wattmeter does: it reads V × I × cos(angle between the voltage across its potential coil and the current through its current coil). Find those two phasors for each meter.
Key formula
Solution (write it like this)
Explanation
Step 1. Line voltagesVab = 208∠0°, Vbc = 208∠−120°, Vca = 208∠120° V
The delta branches see the line voltages directly.
Step 2. Phase currentsIab = 208/10
= 20.8∠0° A
Ibc = 208∠−120°/14.14∠45°
= 14.71∠−165° A
Ica = 208∠120°/14.14∠−45°
= 14.71∠165° A
One division for each branch.
Step 3. Line currentsIA = Iab − Ica
= 35.21∠−6.2° A
IB = Ibc − Iab
= 35.21∠−173.8° A
IC = Ica − Ibc
= 7.61∠90° A
KCL at each corner of the delta.
Step 4. W₁ (VAC = 208∠−60°)W₁ = VAC IA cos(−53.8°)
= 208 × 35.21 × cos 53.8°
= 4326 W
Identify the voltage across the potential coil: from A to C, which is the negative of Vca.
Step 5. W₂ (VBC = 208∠−120°)W₂ = VBC IB cos 53.8°
= 208 × 35.21 × cos 53.8°
= 4326 W
Same for the second meter with B and C.
Step 6. CheckP = ΣI²R
= 4326.4 + 2163.2 + 2163.2
= 8652.8 W = W₁ + W₂ ✓
The branch powers add up to the same total, which confirms the readings.
Answer: W₁ = W₂ ≈ 4.33 kW, total power ≈ 8.65 kW.
Keep in mind- Wattmeter reading = Vcoil × Icoil × cos(angle between them).
- For an unbalanced load find each line current by KCL.
Problem 31. Two-wattmeter readings on an unbalanced delta load Practice problem
A balanced abc source with Vab = 208∠0° V supplies an unbalanced Δ load: ZAB = 20 Ω, ZBC = 10 − j10 Ω, ZCA = 12 + j5 Ω. Two wattmeters have their current coils in lines a and c and their voltage coils connected to line b. Find each reading and the total power.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| Vab | 208∠0° V | abc |
| ZAB | 20 Ω | |
| ZBC | 10 − j10 Ω | |
| ZCA | 12 + j5 Ω | |
| W1, W2 | | in lines a, c; coils to b |
Required (to find)
How to think about it. For an unbalanced load the two readings no longer give the power factor; only their sum is meaningful. The check with ΣI²R is quick and catches sign errors.
Current coils in lines a and c, voltage coils to b.
Solution (write it like this)
Explanation
Step 1. Phase currentsIAB = 208/20
= 10.4∠0° A
IBC = 208∠−120°/14.14∠−45°
= 14.71∠−75° A
ICA = 208∠120°/13∠22.6°
= 16∠97.4° A
Phase currents of the Δ.
Step 2. Line currentsIa = IAB − ICA
= 20.17∠−51.9° A
Ic = ICA − IBC
= 30.64∠101.0° A
KCL at the line terminals.
Step 3. W1W1 = Re(VabIa*)
= 208 × 20.17 × cos 51.9°
= 2591 W
Vab is 208∠0°.
Step 4. W2 (Vcb = 208∠60°)W2 = Re(VcbIc*)
= 208 × 30.64 × cos(−41.0°)
= 4808 W
Vcb = −Vbc.
Step 5. TotalPT = 2591 + 4808
= 7398 W
The two-wattmeter method holds for any 3-wire load.
Answer: W1 ≈ 2591 W, W2 ≈ 4808 W; total ≈ 7.40 kW.
Keep in mind- W1 + W2 = total power for any 3-wire system.
- Use the line voltage seen by each voltage coil.
Problem 32. Power factor from the two-wattmeter ratio DWASA
The two wattmeter readings are in the ratio 5 : 3. Find the power factor.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| W₁ : W₂ | 5 : 3 | wattmeter ratio |
Required (to find)
How to think about it. For a balanced load the two readings carry the power factor: their sum is the power and their difference is proportional to the reactive power. Only the ratio matters, so the unknown scale cancels.
The sum of the readings is the real power; √3 times the difference is the reactive power.
Solution (write it like this)
Explanation
Step 1. ReadingsW₁ = 5k, W₂ = 3k
Let the readings be 5k and 3k.
Step 2. Sum and differenceW₁ + W₂ = 8k
W₁ − W₂ = 2k
Sum and difference.
Step 3. Formulatan φ = √3(W₁ − W₂)/(W₁ + W₂)
= √3 × 2/8
= 0.433
W1 − W2 = VLIL sin φ and W1 + W2 = √3 VLIL cos φ; dividing gives this formula.
Step 4. Angleφ = tan⁻¹ 0.433
= 23.41°
Inverse tangent.
Step 5. Power factorpf = cos 23.41°
= 0.918 lagging
Cosine of the angle. Lagging is assumed, as for a normal load.
Answer: pf = 0.918 lagging
Keep in mind- tan φ = √3 (W1 − W2)/(W1 + W2).
- Reactive power = √3 (W1 − W2).
Problem 33. Per-phase quantities from two wattmeter readings Practice problem
Two wattmeters on a balanced Δ load read P1 = 1560 W and P2 = 2100 W. The line voltage is 220 V. Find (a) the average power per phase, (b) the reactive power per phase, (c) the power factor and (d) the phase impedance.
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| P1 | 1560 W | wattmeter 1 |
| P2 | 2100 W | wattmeter 2 |
| VL | 220 V | line voltage (Δ load) |
Required (to find)
How to think about it. Equal readings mean unity power factor; one reading zero means pf = 0.5; a negative reading means pf < 0.5.
Totals and per-phase values.
Solution (write it like this)
Explanation
Step 1. Total powerPT = P1 + P2
= 3660 W
Pp = 3660/3
= 1220 W
Sum of readings.
Step 2. Reactive powerQT = √3(P2 − P1)
= √3 × 540
= 935.3 var
Qp
= 311.8 var
Two-wattmeter reactive power.
Step 3. Power factorφ = tan⁻¹(935.3/3660)
= 14.33°
pf = cos 14.33°
= 0.969
Power factor angle.
Step 4. Phase impedanceSp = √(1220² + 311.8²)
= 1259 VA
Ip = Sp/Vp
= 1259/220
= 5.72 A
|Zp| = 220/5.72
= 38.4 Ω
In Δ the phase voltage is the line voltage.
Answer: (a) 1220 W (b) 311.8 VAR (c) 0.969 (d) Zp ≈ 38.4∠14.33° Ω.
Keep in mind- P = P1 + P2; Q = √3(P2 − P1).
- tan φ = √3(P2 − P1)/(P1 + P2).
Problem 34. Load data from two wattmeter readings with one negative Practice problem
For a balanced Y load on a 208 V line, the two wattmeters read P1 = −560 W and P2 = 800 W. Find (a) the total average power, (b) the total reactive power, (c) the power factor, (d) the phase impedance. Is the load inductive or capacitive?
Show step-by-step solution
Given
| Symbol | Value | Meaning |
|---|
| P1 | −560 W | wattmeter 1 |
| P2 | 800 W | wattmeter 2 |
| VL | 208 V | line voltage (Y load) |
Required (to find)
How to think about it. One wattmeter reads negative whenever the pf is below 0.5.
Everything follows from P1 and P2.
Solution (write it like this)
Explanation
Step 1. Total powerPT = P1 + P2
= −560 + 800
= 240 W
Sum of readings.
Step 2. Reactive powerQT = √3(P2 − P1)
= √3 × 1360
= 2356 var
Difference of readings.
Step 3. Power factorθ = tan⁻¹(2356/240)
= 84.18°
pf = cos θ
= 0.101
Very low pf.
Step 4. Phase impedance|S|
= 2368 VA
IL = 2368/(√3 × 208)
= 6.57 A
Zp = (208/√3)/6.57
= 18.27∠84.18° Ω
Y load: Vp = VL/√3.
Answer: PT = 240 W, QT ≈ 2356 var, pf ≈ 0.101, Zp ≈ 18.3∠84.2° Ω — inductive (positive Q).
Keep in mind- P = P1 + P2, Q = √3(P2 − P1).
Found a mistake or have a better method? Leave a comment below. More topics from the question bank are in the other posts of this series.