Power Factor Correction question solutions for EEE job exams. 2 written questions and 23 math problems on Power Factor Correction, the kind asked in Bangladesh EEE recruitment exams (BPDB, PGCB, DPDC, DESCO, NWPGCL, EGCB, BCS and others), each solved in exam style: the given data, what is required, the formula used at every step, the substitution and the final answer.
This post is part 6 of the EEE Job Preparation Question Bank series. It covers power factor and its correction with 25 solved questions: 2 written (theory) questions and 16 math problems on real and reactive power, combined loads, capacitor sizing and synchronous condensers from recruitment exams (BPDB, DPDC, PGCB, BCIC, BWDB, BCS) and BUET M.Sc. admission tests, plus 7 practice problems on the same topics.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution is laid out the way an examiner wants to see it: the given data with symbols and values, the quantity required, and then each step as formula → substitution → result, with the reason for that step written beside it. It also shows how to think about that type of problem, a diagram, and what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
- Formulas to memorize first
- Part A: Written questions (2)
- Part B: Solved problems (23)
Show the list
- Real and reactive power from apparent power
- Line current and pf of three parallel loads
- Total kW, kVA and power factor of a generator feeding three different…
- Power factor of three parallel loads
- Overall power factor of three loads
- Total complex power and power factor of two parallel loads
- Total complex power of three parallel loads on 240 V
- Capacitor for unity power factor
- Capacitor bank to correct a 440 V load to 0.95 pf
- Capacitor that makes a load resonant (unity pf)
- Capacitance for power-factor correction on a 60 Hz line
- Capacitor for power-factor correction (220 V, 5 A load)
- Capacitor that raises a single-phase motor from 0.7 to 0.9 power factor…
- Effect of a capacitor bank on current and pf
- Capacitor for unity power factor of a motor
- Capacitor rating for power-factor correction
- Power factor and compensation from meter readings
- Capacitor bank rating for a motor
- kVAR per phase of a delta capacitor bank for a 5 kW motor
- Capacitance from reactive power at a given voltage
- Power-factor correction with a synchronous motor
- Extra kW from an alternator at unity power factor
- Monthly bill with a power-factor penalty or credit
- Other parts of this series
Formulas to Memorize First
- Power triangle: P = S cos φ (kW), Q = S sin φ (kVAR), S = √(P² + Q²) (kVA), tan φ = Q/P.
- Power factor: cos φ = P/S. Lagging for inductive loads (Q positive), leading for capacitive loads (Q negative).
- Useful pairs: pf 0.8 → sin 0.6, tan 0.75. pf 0.6 → sin 0.8, tan 1.333. pf 0.707 → tan 1. pf 0.95 → tan 0.329. pf 0.9 → tan 0.484.
- Several loads: add all the P, add all the Q with sign, then find S and the pf. Never add kVA values directly.
- Capacitor kVAR needed: QC = P(tan φ1 − tan φ2). The real power P does not change.
- Capacitance, single phase: C = QC/(ωV²), with ω = 2πf.
- Three phase: divide QC by 3 for each phase. Star bank: C = Qph/(ωVph²). Delta bank: C = Qph/(ωVL²), one third of the star value.
- Current: single phase I = S/V; three phase I = S/(√3 VL).
- Unity pf with a parallel capacitor: ωC = susceptance of the load, i.e. C = X/(ω(R² + X²)) for a load R + jX.
Part A: Written Questions on Power Factor Correction
Q1. Why is a low power factor undesirable and how is it improved?
Show full answer
What power factor is
Power factor is the cosine of the angle between voltage and current: cos φ = P/S = kW/kVA. It tells what fraction of the current is doing useful work. Most loads (motors, transformers, chokes, furnaces) are inductive: they need magnetising current that lags the voltage by 90° and does no work. That reactive current is what makes the power factor low.
Why a low power factor is undesirable
For a fixed power P at a fixed voltage, I = P/(V cos φ). A lower power factor means a larger current for the same useful power. Everything else follows from that:
- Larger kVA rating of equipment. Alternators, transformers and switchgear are rated in kVA, so they must be bigger for the same kW.
- Larger conductors. Cables and lines must carry more current.
- Higher copper loss. I²R loss rises as 1/cos²φ: at 0.5 pf the loss is four times that at unity.
- Poor voltage regulation. A larger, lagging current gives a larger voltage drop in lines and transformers.
- Less capacity available. A generator loaded to its kVA limit at low pf delivers fewer kW.
- Penalty in the bill. Utilities charge extra when the pf is below a set limit.
Example: 100 kW at 400 V three-phase needs 144 A at unity pf but 241 A at 0.6 pf.
How it is improved
A device that takes leading current is connected in parallel with the load, so that it supplies the reactive power locally and the supply does not have to.
- Static capacitors (capacitor banks) in parallel with the load: cheap, no moving parts, low loss. The most common method.
- Synchronous condenser: an over-excited synchronous motor running on no load. Adjustable smoothly; used at large substations.
- Phase advancer on large induction motors: supplies the rotor excitation so the stator need not.
How to see the correction on the power triangle (three steps)
Each picture adds one step to the one before it. Draw it on paper in the same order.
Keep in mind
Low pf → more current for the same kW → more loss, more drop, bigger equipment. Cure: a parallel capacitor or a synchronous condenser. The kW never changes; only the kVAR drawn from the supply does.
Q2. What is a synchronous condenser? BEPZA
Show full answer
Short answer (write this in the exam)
A synchronous condenser is a synchronous motor that runs without any mechanical load and with its field over-excited. In this condition it draws a current that leads the voltage by nearly 90°, exactly as a capacitor does, so it supplies lagging reactive power to the system. It is used to improve power factor and to control voltage.
How it works
The power factor of a synchronous motor depends on its field current. With weak excitation it takes lagging current; at normal excitation, unity pf; with strong excitation, leading current. On no load the real power is only the losses, so the current is almost purely reactive.
Why use it instead of capacitors
| Point | Synchronous condenser | Static capacitor bank |
|---|---|---|
| Control | Smooth and continuous by field current; can also absorb VAR when under-excited | In steps, by switching units |
| Voltage support | Good: output can be raised when the voltage falls | Output falls as V² when the voltage falls |
| Cost and upkeep | High cost, losses, noise, maintenance of a rotating machine | Cheap, low loss, almost no maintenance |
| Typical size | Large (above about 5 MVAR), at transmission substations | Any size, at loads and distribution substations |
Where it is used
At the receiving end of long transmission lines and at major substations to hold the voltage steady as load changes, and in large factories. A loaded synchronous motor run over-excited does both jobs at once: it drives its load and corrects the plant power factor (see Problem 15 in Part B).
Keep in mind
Synchronous condenser = synchronous motor + no load + over-excitation = adjustable capacitor.
Part B: Solved Problems on Power Factor Correction
Problem 1. Real and reactive power from apparent power BPDB
A load receives 10 000 VA at 0.707 p.f. Find (a) the average power taken by the load and (b) the total reactive power.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 000 VA | apparent power |
| pf | 0.707 | power factor |
- P
- Q
- P = S cos φ, Q = S sin φ, S² = P² + Q².
Problem 2. Line current and pf of three parallel loads DPDC
Three loads are in parallel on a 400 V, 50 Hz balanced 3-phase source: 24 kW at 0.7 lagging, 12 kW at 0.6 lagging, 12 kVA at 0.85 leading. Find the line current and resultant power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VL | 400 V | line voltage |
| load 1 | 24 kW, 0.7 lag | |
| load 2 | 12 kW, 0.6 lag | |
| load 3 | 12 kVA, 0.85 lead |
- IL
- pf
- Make a small table: P, Q for each load, then totals.
- Leading loads reduce the total Q.
Problem 3. Total kW, kVA and power factor of a generator feeding three different loads Practice problem
A single-phase a.c. generator supplies (i) a lighting load of 20 kW at unity power factor, (ii) an induction motor load of 100 kW at 0.707 pf lagging and (iii) a synchronous motor load of 50 kW at 0.9 pf leading. Find the total kW and kVA delivered by the generator and its power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P₁ | 20 kW at unity pf | lighting |
| P₂ | 100 kW at 0.707 lag | induction motor |
| P₃ | 50 kW at 0.9 lead | synchronous motor |
- total kW
- kVA
- pf
- Add kW and kVAR separately, never kVA.
- Leading kVAR has the opposite sign.
Problem 4. Power factor of three parallel loads BWDB
Three parallel loads on a 50 Hz supply: load 1 is 100 Ω in series with 25.4 mH; load 2 is 120 Ω in series with 39.75 µF; load 3 is 60 Ω in series with 80 Ω. Find the power factor of the composite load.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| f | 50 Hz | supply |
| Z₁ | 100 Ω + 25.4 mH | load 1 |
| Z₂ | 120 Ω + 39.75 μF | load 2 |
| Z₃ | 60 Ω + 80 Ω | load 3 |
- pf (of the composite load)
- Parallel branches: add admittances. Series elements: add impedances.
- Positive susceptance → capacitive → leading.
Problem 5. Overall power factor of three loads BPDB
An a.c. circuit consists of a resistive load in series with a parallel combination of an inductive load and a capacitive load. The three loads consume real power of 100 W, 200 W and 300 W respectively. The reactive power consumed at the inductive and capacitive loads are 700 VAR and 1500 VAR respectively. If the supply voltage is 100∠0° V, find the overall power factor of the circuit.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 100, 200, 300 W | resistive, inductive, capacitive loads |
| QL | 700 var | inductive load |
| QC | 1500 var | capacitive load |
| V | 100∠0° V | supply |
- overall pf
- Conservation of complex power: total P = ΣP, total Q = ΣQ, for any connection.
- Net Q negative → leading pf.
Problem 6. Total complex power and power factor of two parallel loads Practice problem
(a) A 120∠10° V rms source supplies Z1 = 60∠−30° Ω and Z2 = 40∠45° Ω in parallel. Find the total apparent, real and reactive power and the power factor seen by the source. (b) Two parallel loads take 2 kW at 0.75 pf leading and 4 kW at 0.95 pf lagging. Find the combined power factor and the complex power from the source.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| (a) V | 120∠10° V rms; Z1 = 60∠−30° Ω; Z2 = 40∠45° Ω | |
| (b) | 2 kW at 0.75 lead; 4 kW at 0.95 lag |
- S, P, Q
- pf
- Stotal = ΣSk; pf = ΣP/|S|.
Problem 7. Total complex power of three parallel loads on 240 V Practice problem
Three loads, 80 − j50 Ω, 120 + j70 Ω and 60 Ω, are connected in parallel across a 240 V rms, 50 Hz supply. Find (a) the total complex power and (b) the power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 240 V rms | supply |
| Z1 | 80 − j50 Ω | |
| Z2 | 120 + j70 Ω | |
| Z3 | 60 Ω |
- S
- pf
- S = Vrms²/Z* for a load across V.
Problem 8. Capacitor for unity power factor BWDB
A 120 V, 60 Hz source supplies a load Z = 10 + j12 Ω. Find the capacitor to be connected in parallel so that the power factor becomes unity. (The answer does not depend on the voltage.)
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 120 V | supply |
| f | 60 Hz | frequency |
| Z | 10 + j12 Ω | load |
- C (for unity pf)
- For a load R + jX: C = X/(ω(R² + X²)).
- The answer does not depend on the supply voltage.
Problem 9. Capacitor bank to correct a 440 V load to 0.95 pf BCIC
A 440 V, 51 kW, 60 kVA Y-connected inductive load at 60 Hz is to be corrected to 0.95 lagging. Find the capacitor per phase.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VL | 440 V | line voltage |
| P | 51 kW | real power |
| S | 60 kVA | apparent power |
| f | 60 Hz | |
| pf₂ | 0.95 lagging | target |
- C (per phase)
- QC = Q1 − Q2 = P(tan φ1 − tan φ2).
- Star: use Vph. Delta: use VL (and C is one third).
Problem 10. Capacitor that makes a load resonant (unity pf) BUET M.Sc.
A load absorbs 4 kW at 0.8 power factor lagging from a 215 V (rms), 50 Hz line. Find the capacitance that makes the circuit resonant (unity power factor).
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 4 kW | load power |
| pf | 0.8 lagging | |
| V | 215 V rms | line |
| f | 50 Hz |
- C (for unity pf)
- Unity pf: QC = Q of the load.
- C = Q/(ωV²).
Problem 11. Capacitance for power-factor correction on a 60 Hz line Practice problem
(a) A load on a 120 V rms, 60 Hz line absorbs 4 kW at 0.8 pf lagging. Find the parallel capacitance that raises the pf to 0.95. (b) A load of 140 kvar at 0.85 pf lagging is supplied from a 110 V rms, 60 Hz line. Find the capacitance that corrects it to unity pf.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| (a) | 4 kW, 0.8 lag → 0.95; 120 V, 60 Hz | |
| (b) | 140 kvar, 0.85 lag → unity; 110 V, 60 Hz |
- C (for (a) and (b))
- QC = P(tan θ1 − tan θ2); C = QC/ωV².
Problem 12. Capacitor for power-factor correction (220 V, 5 A load) MPL
A 220 V AC source supplies 5 A to a load at 0.8 pf lagging. What capacitance must be connected in parallel to make the power factor 0.95 lagging? (Take 50 Hz.)
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 220 V | supply |
| I | 5 A | load current |
| pf₁ | 0.8 lagging | |
| pf₂ | 0.95 lagging | target |
| f | 50 Hz |
- C
- Correcting to 0.95 needs much less capacitance than correcting to unity (660 var would need 43.4 µF).
Problem 13. Capacitor that raises a single-phase motor from 0.7 to 0.9 power factor (current method) Practice problem
A single-phase motor connected to a 400 V, 50 Hz supply takes 31.7 A at a power factor of 0.7 lagging. Find the capacitance that must be connected in parallel with the motor to raise the power factor to 0.9 lagging.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 400 V | supply |
| f | 50 Hz | |
| I₁ | 31.7 A | motor current |
| pf₁ | 0.7 lagging | |
| pf₂ | 0.9 lagging | target |
- C
- Active current is unchanged by a parallel capacitor.
- IC = I₁ sin φ₁ − I₂ sin φ₂.
- C = IC/(2πfV).
Problem 14. Effect of a capacitor bank on current and pf BUET M.Sc.
A three-phase load draws 250 kW at a power factor of 0.707 lagging from a 440 V line. A three-phase capacitor bank drawing 60 kVAR is connected in parallel. Find the total current and the resultant power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 250 kW | load |
| pf | 0.707 lagging | |
| VL | 440 V | line voltage |
| QC | 60 kvar | capacitor bank |
- I
- pf
- New Q = Qload − QC; P unchanged.
- The line current falls from 464 A to 412 A although the load is the same.
Problem 15. Capacitor for unity power factor of a motor PGCB
In the circuit the motor draws IM = 50 A at 0.6 lagging from a 120 V, 50 Hz supply. To improve the power factor from 0.6 lagging to unity, what should be the value of C?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| IM | 50 A | motor current |
| pf | 0.6 lagging | |
| V | 120 V | supply |
| f | 50 Hz |
- C (for unity pf)
- IC = I sin φ for unity pf; supply current becomes I cos φ.
- The motor itself still draws 50 A; only the supply current falls.
Problem 16. Capacitor rating for power-factor correction BCS
A 20 kW load at 0.8 lagging pf is to be raised to 0.95 lagging. Find the capacitor rating; and the rating of a device drawing leading current at pf 0.1 to do the same.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 20 kW | load |
| pf₁ | 0.8 lagging | |
| pf₂ | 0.95 lagging | target |
| device pf | 0.1 leading | alternative |
- QC
- S (of the 0.1-pf device)
- QC = P(tan φ1 − tan φ2).
- If the correcting device takes real power, include it in the total P.
Problem 17. Power factor and compensation from meter readings BIFPCL
A voltmeter reads 240 V, an ammeter 10 A and a wattmeter 1200 W. (a) Find the power factor. (b) What type of load is it? (c) What reactive power must be compensated for unity p.f.? (d) What capacitor is needed?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 240 V | voltmeter |
| I | 10 A | ammeter |
| P | 1200 W | wattmeter |
| f | 50 Hz |
- pf
- load type
- Q
- C
- pf = W/(V × A).
- Q = √(S² − P²).
Problem 18. Capacitor bank rating for a motor PGCB
A 3-phase, 50 Hz, 400 V motor develops 74.6 kW at a power factor of 0.75 lagging and an efficiency of 93 %. A bank of capacitors is connected in delta across the supply terminals and the power factor is raised to 0.95 lagging. Determine the kVAR rating of the capacitors in each phase.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Pout | 74.6 kW | motor output |
| η | 93 % | efficiency |
| pf₁ | 0.75 lagging | |
| pf₂ | 0.95 lagging | target |
| VL | 400 V |
- QC (per phase)
- Always use the electrical input power in pf correction.
- 74.6 kW is exactly 100 hp.
Problem 19. kVAR per phase of a delta capacitor bank for a 5 kW motor Practice problem
A three-phase, 5 kW induction motor has a power factor of 0.75 lagging. A bank of capacitors connected in delta across the supply terminals raises the power factor to 0.9 lagging. Find the kVAR rating of the capacitors in each phase. (Take 5 kW as the motor input.)
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 5 kW | motor input |
| pf₁ | 0.75 lagging | |
| pf₂ | 0.9 lagging | target |
- QC (per phase)
- QC = P(tan φ₁ − tan φ₂).
- Per-phase rating = total/3.
- Delta-connected capacitors need one third of the capacitance of a star bank for the same kVAR.
Problem 20. Capacitance from reactive power at a given voltage BPDB
A 50 Hz capacitor is added in parallel with an 11 kV bus. The reactive power injected by the capacitor is 50 kVAR. What is the value of the capacitor?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 11 kV | bus voltage |
| Q | 50 kvar | capacitor output |
| f | 50 Hz |
- C
- QC = ωCV². Doubling the voltage gives four times the VAR.
Problem 21. Power-factor correction with a synchronous motor EGCB
An infinite bus is operating at 480 V. One load on the bus is an induction motor consuming 200 kW at 0.8 p.f. lagging and another load is a synchronous motor consuming 150 kW at 0.85 p.f. leading. What is the line power factor?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 480 V | bus voltage |
| P₁ | 200 kW at 0.8 lag | induction motor |
| P₂ | 150 kW at 0.85 lead | synchronous motor |
- line pf
- An over-excited synchronous motor does useful mechanical work and improves the pf at the same time.
Problem 22. Extra kW from an alternator at unity power factor DPDC
An alternator supplying a load of 500 kVA at 0.6 power factor has its power factor raised to unity. How many more kW can the alternator supply at the same kVA loading?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 500 kVA | alternator loading |
| pf₁ | 0.6 | initial |
| pf₂ | 1 | after correction |
- ΔP (extra kW)
- kW = kVA × pf. Improving the pf releases capacity in generators, transformers and lines.
Problem 23. Monthly bill with a power-factor penalty or credit Practice problem
An industrial tariff charges Tk 8 per kWh. For every 0.01 that the power factor falls below 0.85 a penalty of 0.1 % of the energy charge is added; for every 0.01 above 0.85 a credit of 0.1 % is given. Find the monthly bill of (a) a 300 kW load at 0.80 power factor that runs 520 hours a month, and (b) an 800 kW induction furnace at 0.88 power factor that runs 20 hours a day for 26 days.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| rate | Tk 8/kWh | energy charge |
| base pf | 0.85 | |
| step | 0.1 % per 0.01 pf | penalty or credit |
| (a) | 300 kW, 0.80 pf, 520 h | |
| (b) | 800 kW, 0.88 pf, 20 h × 26 days |
- monthly bill (for (a) and (b))
- Bill = energy charge × (1 ± pf adjustment).
- Count steps of 0.01 from the threshold.
- DC Circuit Analysis
- Network Theorems
- RL, RC & RLC Transients
- Single-Phase AC Circuits
- Series & Parallel Resonance
- Power Factor Correction (this post)
- Three-Phase Circuits
- Transformer
- DC Generator & DC Motor
- Three-Phase Induction Motor
- Synchronous Machines
- Diode Circuits
- BJT Biasing & Amplifiers
- MOSFET & Power Electronics
- Op-Amp Circuits
- AM, FM & Analog Modulation
- Signals and Sampling
- PCM, Delta Modulation & TDM
- Digital Communication & Telecom
- Load Curves & Power Generation
- Per-Unit & Transmission Lines
- Faults & Symmetrical Components
- Protection & Switchgear
- Control Systems
- Digital Logic & Microprocessors
- Measurement, Mechanics & Aptitude