Per-Unit & Transmission Lines question solutions for EEE job exams. 15 written questions and 44 math problems on Per-Unit & Transmission Lines, the kind asked in Bangladesh EEE recruitment exams (BPDB, PGCB, DPDC, DESCO, NWPGCL, EGCB, BCS and others), each solved in exam style: the given data, what is required, the formula used at every step, the substitution and the final answer.
This post is part 21 of the EEE Job Preparation Question Bank series. It covers the per-unit system, load flow and transmission lines with 59 solved questions: 15 written (theory) questions on per-unit quantities, bus types and the fast decoupled method, power-flow results and transposition, the power-angle equation and stability, high-voltage transmission, the Bangladesh T&D system, skin and Ferranti effects and corona, ABCD constants, voltage regulation and sag and 22 math problems on base changes, per-unit impedance diagrams, Y-bus, generator load sharing, series compensation, regulation, copper saving and sag from recruitment exams (PGCB, BPDB, DPDC, NWPGCL, CPGCBL, APSCL, BGFCL) and BUET M.Sc. admission tests, plus 22 practice problems on the same topics.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution is laid out the way an examiner wants to see it: the given data with symbols and values, the quantity required, and then each step as formula → substitution → result, with the reason for that step written beside it. It also shows how to think about that type of problem, a diagram, and what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
- Formulas to memorize first
- Part A: Written questions (15)
Show the list
- Show that changing susceptance in per unit is equal to the 3-phase MVAR…
- Write down the known and unknown quantities of the different bus types…
- What are the conditions (assumptions) for the Jacobian in the fast…
- What information is obtained from power-flow analysis of a system? What…
- Write down the power-angle equation for a pure reactance network. Point…
- Write down the factors that affect power system stability.
- Why is high-voltage transmission used?
- Give three points for selecting a transmission voltage and the voltage…
- Write down the advantages and disadvantages of a.c. transmission.
- Draw a single line diagram of the transmission and distribution system…
- Write short notes on skin effect, Ferranti effect and corona.
- Show that the generalised circuit constants of a short transmission…
- The sending-end voltage of a transmission line is Vs = AVr + BIr, with…
- Draw the phasor diagram of voltage regulation of a transmission line…
- What is the shape of the conductor in the case of sag between two…
- Part B: Solved problems (44)
Show the list
- Per-unit impedance of a transformer
- Per-unit impedance of a load on a new base
- Changing the per-unit base of a generator reactance
- Changing the base of a machine reactance
- Changing the per-unit base when only the MVA changes
- Changing the MVA base of a transformer reactance
- Changing the per-unit base when both kV and MVA change
- Per-unit impedance across two transformers
- Per-unit impedance of a transformer and line on a common base
- Per-unit motor current
- Single-line diagram and per-unit reactance diagram
- Per-unit impedance diagram of a generator–line–motor system
- Bus admittance matrix of a 3-bus system
- Y-bus of two buses joined by parallel lines
- Load sharing of two generators with droop
- Frequency of two generators sharing load
- Loop inductance of a single-phase line (2 m spacing)
- Loop inductance with copper and with steel conductors
- Inductance per phase of an equilateral three-phase line
- Capacitance of a single-phase line
- Capacitance to neutral of an equilateral three-phase line
- Capacitance per phase of a 100 km three-phase line
- Series capacitor to raise power transfer
- Receiving-end voltage, current and efficiency when the sending-end…
- Power output and sending-end power factor of a short line
- Regulation and efficiency of an 11 kV line
- Voltage regulation of a transmission line with ABCD constants
- Voltage regulation from no-load and full-load readings
- Copper saving when the voltage is raised
- Extra load when a 2-wire d.c. line becomes a 3-phase, 3-wire a.c. line
- Extra load when a 3-wire d.c. line becomes a 3-phase, 4-wire a.c. line
- Voltage at two tram cars on a d.c. feeder
- Voltage distribution and string efficiency of a 3-disc string (33 kV)
- Maximum safe voltage of a 3-disc string
- Voltage across each disc of a 5-disc string on a 100 kV line
- Disruptive critical voltage of a three-phase line
- Conductor spacing for a given corona onset voltage
- Disruptive critical voltage from two corona-loss measurements
- Sag and height of a transmission line support
- Slant and vertical sag with wind loading (span 150 m)
- Sag with wind pressure on the projected area (span 200 m)
- Factor of safety from a measured vertical sag
- Sag and lowest point of a conductor on supports of different heights
- Mid-span clearance at a river crossing when the lowest point lies…
- Other parts of this series
Formulas to Memorize First
- Per-unit value = actual value/base value. Choose Sbase (MVA) once for the whole system and Vbase (kV) in one zone; other zones get Vbase through the transformer ratios.
- Base impedance: Zbase = (kVbase)²/MVAbase (single-phase: V²/VA).
- Base change: Znew = Zold × (MVAnew/MVAold) × (kVold/kVnew)².
- A per-unit impedance is the same on both sides of a transformer (when the bases follow the turns ratio).
- Y-bus: Yii = sum of admittances at bus i; Yij = −(admittance between i and j).
- Bus types: slack (|V|, δ known), PV (P, |V| known), PQ (P, Q known).
- Power transfer: P = (VsVr/X) sin δ; Pmax = VsVr/X at δ = 90°.
- Droop: f = fnl − P/sP; parallel machines run at one frequency.
- Short line: A = D = 1, B = Z, C = 0. Always AD − BC = 1.
- Regulation = (Vr,no-load − Vr,full-load)/Vr,full-load; Vr,no-load = Vs/|A|.
- Copper volume ∝ 1/V² (same power, distance and loss).
- Sag (level supports): S = wl²/(8T); unequal supports: lowest point at x₁ = l/2 − Th/(wl) from the lower support.
Part A: Written Questions on Per-Unit System, Load Flow & Transmission Lines
Q1. Show that changing susceptance in per unit is equal to the 3-phase MVAR in per unit. BUET Admission
Show full answer
Set-up
Choose the base MVA Sbase and base voltage Vbase. Then the base admittance is Ybase = 1/Zbase = Sbase/Vbase².
Proof
- A shunt susceptance B connected at line voltage VL draws a 3-phase reactive power Q = VL²B.
- Divide by Sbase = Vbase²Ybase: Qpu = VL²B/(Vbase²Ybase).
- Group the terms: Qpu = (VL/Vbase)² × (B/Ybase) = Vpu² × Bpu.
- At rated voltage Vpu = 1, so Qpu = Bpu.
Why it is useful
A shunt reactor or capacitor bank is often specified in MVAR. In per unit its MVAR rating (on the system MVA base) directly gives its susceptance, and vice versa, without converting through ohms.
Keep in mind
Q = V²B; Qpu = Vpu²Bpu; at 1 pu voltage, MVAR in pu = susceptance in pu.
Q2. Write down the known and unknown quantities of the different bus types in a load-flow study. DWASA
Show full answer
Why bus types are needed
Each bus has four quantities: P, Q, |V| and δ. The load-flow equations can fix only two of them per bus, so two must be specified and two found. Which two are specified depends on what is physically controlled at that bus.
The three types
| Bus type | Known (specified) | Unknown (calculated) | Remarks |
|---|---|---|---|
| Slack (swing, reference) | |V|, δ (usually 1∠0°) | P, Q | Supplies the losses, which are unknown until the solution is found. Only one per system. |
| Generator (PV, voltage-controlled) | P, |V| | Q, δ | Governor fixes P, AVR fixes |V|. Becomes PQ if Q hits its limit. |
| Load (PQ) | P, Q | |V|, δ | Most buses are of this type. |
Keep in mind
Slack: |V|, δ known. PV: P, |V| known. PQ: P, Q known. The two unknowns are always the other two.
Q3. What are the conditions (assumptions) for the Jacobian in the fast decoupled load-flow method? BUET M.Sc.
Show full answer
Idea
In the Newton–Raphson load flow the Jacobian has four blocks. In a transmission system real power depends mainly on the angles, and reactive power mainly on the voltage magnitudes. The fast decoupled method uses this to drop two blocks and make the other two constant.
The decoupled Jacobian
Assumptions
- Weak P–|V| and Q–δ coupling: J₂ = ∂P/∂|V| ≈ 0 and J₃ = ∂Q/∂δ ≈ 0.
- Line R/X ratio is small, so Gij sin(δi − δj) ≪ Bij.
- Angle differences are small: cos(δi − δj) ≈ 1.
- Qi ≪ Bii|Vi|².
- All voltages are close to 1 pu.
Result
ΔP/|V| = [B′]Δδ and ΔQ/|V| = [B″]Δ|V|. B′ and B″ are built from the bus susceptance matrix and factorised only once, so each iteration is very fast, though more iterations are needed than in full Newton–Raphson.
Keep in mind
FDLF: drop ∂P/∂|V| and ∂Q/∂δ; assume small R/X, small angle differences and |V| ≈ 1; constant B′ and B″.
Q4. What information is obtained from power-flow analysis of a system? What is transposition of conductors and why is it used? BPDB
Show full answer
Information from a power-flow study
- Voltage magnitude and angle at every bus.
- Real and reactive power flow in every line and transformer.
- Line losses and total system loss.
- The P and Q the generators and slack bus must supply; reactive power from compensators.
- Overloaded lines and buses outside voltage limits.
- It is the starting point for planning, contingency studies, economic dispatch and stability studies.
Transposition of conductors
Why it is used
- In an unsymmetrical (for example flat) arrangement each phase has a different inductance and capacitance, so the phase voltage drops are unequal even with balanced current.
- Transposition gives every phase the same average inductance and capacitance, so the line is balanced.
- It also reduces induced interference in nearby telephone lines.
Keep in mind
Load flow gives |V|, δ, P/Q flows and losses. Transposition = rotating phase positions in three sections to equalise L and C.
Q5. Write down the power-angle equation for a pure reactance network. Point out a change in which network element would affect system stability. DPDC
Show full answer
The power-angle equation
For a lossless link of reactance X between sending voltage |Vs|∠δ and receiving voltage |Vr|∠0:
P = (|Vs||Vr|/X) sin δ
The maximum Pmax = |Vs||Vr|/X occurs at δ = 90°; this is the steady-state stability limit.
The curve
Which element affects stability
The series (transfer) reactance X of the network. Ways to reduce X and raise Pmax:
- Adding parallel lines or circuits.
- Bundled conductors.
- Series capacitors.
- Transformers with lower reactance.
Raising the voltages (strong excitation, voltage control) also raises Pmax.
Keep in mind
P = (VsVr/X) sin δ; Pmax at 90°. Lower X or higher V → more stable.
Q6. Write down the factors that affect power system stability. BUET Admission
Show full answer
The factors
- Transfer reactance of the network: larger X lowers Pmax.
- Excitation and voltage: higher internal e.m.f. raises Pmax; fast AVRs help.
- Inertia H of the machines: larger inertia slows the swing.
- Fault clearing time: faster relays and breakers keep the rotor angle swing smaller.
- Pre-fault loading: a heavily loaded machine starts closer to the limit.
- Type and location of the fault, and reclosing: three-phase faults near the generator are the worst; auto-reclosing helps.
- Governor action, damping and power-system stabilisers.
Keep in mind
X, excitation, inertia, clearing time, loading, fault type/reclosing, damping.
Q7. Why is high-voltage transmission used? PGCB
Show full answer
Short answer
For a given power P = √3VIcos φ, raising the voltage reduces the current in the same proportion. The I²R loss falls with the square of the voltage, so long lines become efficient and economical.
How loss depends on voltage
Advantages
- Lower current → lower I²R loss → higher efficiency.
- Smaller conductor cross-section → less copper/aluminium.
- Smaller voltage drop → better regulation.
- More power can be sent over the same right of way.
Limits
Higher voltage needs more insulation, taller towers, larger clearances and costlier transformers and switchgear, and corona loss rises. So the economic voltage depends on the power and distance.
Keep in mind
I ∝ 1/V; loss ∝ 1/V²; copper volume ∝ 1/V².
Q8. Give three points for selecting a transmission voltage and the voltage levels in Bangladesh. PGCB
Show full answer
Points for selecting a transmission voltage
- Amount of power and distance: more power over a longer distance needs a higher voltage. A rule of thumb: V (kV) ≈ 5.5√(L/1.6 + P/100), L in km and P in kW.
- Allowable losses and voltage regulation.
- Cost: insulation, towers, transformers and switchgear rise with voltage, while conductor cost falls; the economic voltage balances them.
- Standard voltages already used in the grid (for interconnection).
Voltage levels in Bangladesh
Keep in mind
Transmission 400, 230, 132 kV; distribution 33, 11 kV; consumers 400/230 V, 50 Hz.
Q9. Write down the advantages and disadvantages of a.c. transmission. PGCL
Show full answer
Advantages of a.c. transmission
- Voltage can be stepped up and down easily and efficiently with transformers.
- A.c. generators are simpler and cheaper, and can be built in larger ratings.
- Circuit breaking is easier because the current passes through zero every half cycle.
- A.c. substations and motors are cheap and simple.
- The system is easy to extend and interconnect.
Disadvantages
- Skin effect raises the effective resistance; corona loss.
- Line inductance and capacitance cause voltage drop, charging current and the Ferranti effect.
- Reactive power flow and power-factor problems.
- Stability limits the power over long lines; generators must stay in synchronism.
- Needs three conductors (HVDC needs two or one) and more insulation for the same r.m.s. voltage (peak = √2 × r.m.s.).
Keep in mind
a.c. wins on transformation, generation and switching; d.c. (HVDC) wins on very long distance, cables and asynchronous links.
Q10. Draw a single line diagram of the transmission and distribution system in Bangladesh. PGCL
Show full answer
How to draw it
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. Distribution: 33/11 kV substations → 11 kV feeders → 11/0.4 kV distribution transformers → 400/230 V consumers.The stages
- Generation at 11–15.75 kV (larger units up to about 22 kV).
- Step-up to 132, 230 or 400 kV.
- Transmission by PGCB on 400/230 kV lines and the 132 kV network.
- Grid substations: 400/230, 230/132 and 132/33 kV.
- Sub-transmission at 33 kV.
- Distribution substations 33/11 kV (BPDB, DPDC, DESCO, NESCO, WZPDCL, REB/PBS).
- Primary distribution at 11 kV; distribution transformers 11/0.4 kV.
- Secondary distribution at 400 V three-phase, 230 V single-phase to consumers. Large industries take 33 or 11 kV directly.
Keep in mind
G → step-up → 400/230/132 kV → grid SS → 33 kV → 33/11 kV → 11 kV → 11/0.4 kV → consumers.
Q11. Write short notes on skin effect, Ferranti effect and corona.
Show full answer
Skin effect
With d.c. the current spreads evenly over the cross-section; with a.c. it crowds towards the surface.The alternating flux inside the conductor induces a back e.m.f. that is largest at the centre, so a.c. current concentrates near the surface. The effective area falls and Rac > Rdc. The effect grows with frequency, conductor diameter and permeability. It is reduced by stranded, ACSR or hollow conductors.
Ferranti effect
It matters on long (over about 200 km) EHV lines and underground cables at light load. It is controlled with shunt reactors at the receiving end.
Corona
When the electric field at the conductor surface exceeds the breakdown strength of air (about 30 kV/cm peak, 21.1 kV/cm r.m.s.), the air around the conductor ionises. A faint violet glow, a hissing sound, ozone and power loss result, with radio interference. Corona increases with voltage, small conductor diameter, rough surfaces and wet weather. It is reduced with larger-diameter or bundled conductors and greater spacing.
Keep in mind
Skin: Rac > Rdc. Ferranti: Vr > Vs at light load (use shunt reactors). Corona: air ionises above ~30 kV/cm (use bundled conductors).
Q12. Show that the generalised circuit constants of a short transmission line satisfy the condition AD − BC = 1. NWPGCL
Show full answer
Short-line model
Derivation
- The same current flows at both ends: Is = Ir.
- The sending voltage is the receiving voltage plus the drop: Vs = Vr + ZIr.
- Compare with Vs = AVr + BIr and Is = CVr + DIr: A = 1, B = Z, C = 0, D = 1.
- AD − BC = (1)(1) − (Z)(0) = 1.
Why AD − BC = 1 in general
Any linear, passive, bilateral (reciprocal) two-port satisfies AD − BC = 1. For example, a nominal-π line has A = D = 1 + YZ/2, B = Z, C = Y(1 + YZ/4); then AD − BC = (1 + YZ/2)² − ZY(1 + YZ/4) = 1.
Keep in mind
Short line: A = D = 1, B = Z, C = 0. AD − BC = 1 for any passive reciprocal network; A = D if it is symmetrical.
Q13. The sending-end voltage of a transmission line is Vs = AVr + BIr, with A = |A|∠α, B = |B|∠β, Vr = |Vr|∠δ and Vs = |Vs|∠0. Obtain expressions for the real and reactive power in terms of these quantities. PGCB
Show full answer
Set-up
A = |A|∠α, B = |B|∠β, Vs = |Vs|∠0, Vr = |Vr|∠δ (as stated in the question).
Derivation
- From Vs = AVr + BIr: Ir = (Vs − AVr)/B.
- Receiving-end complex power: Sr = VrIr* = Vr(Vs* − A*Vr*)/B*.
- Substitute the angles: VrVs*/B* = (|Vr||Vs|/|B|)∠(δ + β) and A*Vr Vr*/B* = (|A||Vr|²/|B|)∠(β − α).
- So Sr = (|Vs||Vr|/|B|)∠(β + δ) − (|A||Vr|²/|B|)∠(β − α).
Result
Pr = (|Vs||Vr|/|B|) cos(β + δ) − (|A||Vr|²/|B|) cos(β − α)
Qr = (|Vs||Vr|/|B|) sin(β + δ) − (|A||Vr|²/|B|) sin(β − α)
With the usual convention (Vr reference, Vs leading by δ) replace β + δ by β − δ. The sending-end powers follow the same way from Is = (DVs − Vr)/B.
Keep in mind
Pr is maximum when β − δ = 0 (δ = β): Pr,max = |Vs||Vr|/|B| − (|A||Vr|²/|B|) cos(β − α).
Q14. Draw the phasor diagram of voltage regulation of a transmission line using different loads. Which load shows the minimum variation? BUET Admission
Show full answer
Drawing the phasor diagrams
Each picture adds one step to the one before it. Draw it on paper in the same order.
Regulation
Regulation = (Vs − Vr)/Vr (short line). It is large and positive for lagging loads, small for unity p.f., and zero or negative for leading loads.
Which load shows the minimum variation
The leading power-factor load. At a particular leading p.f., cos(φ + θ) = 0 where θ is the line impedance angle, so Vs = Vr and the regulation is zero.
Keep in mind
Approx. regulation ≈ (IR cos φ ± IX sin φ)/Vr: + for lagging, − for leading.
Q15. What is the shape of the conductor in the case of sag between two towers? BPDB
Show full answer
Short answer
A freely hanging uniform conductor takes the shape of a catenary: y = c cosh(x/c), where c = T/w. For transmission lines the sag is small compared with the span (below about 6 to 10 %), so the catenary is very closely approximated by a parabola.
Picture
Formulas
- Parabola measured from the lowest point: y = wx²/(2T).
- Sag for level supports, span l: S = wl²/(8T).
- Unequal supports (difference h): the lowest point is x₁ = l/2 − Th/(wl) from the lower support.
- Wind and ice: use the resultant weight w = √((wc + wi)² + ww²).
Keep in mind
Exact: catenary. Practical: parabola, S = wl²/8T.
Part B: Solved Problems on Per-Unit System, Load Flow & Transmission Lines
Problem 1. Per-unit impedance of a transformer EGCB
A single-phase 100 kVA, 1000/100 V transformer has an equivalent impedance of (1 + j2) Ω referred to the high-voltage side. Find the per-unit impedance.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 100 kVA | |
| V | 1000/100 V | |
| Z | 1 + j2 Ω | referred to HV |
- Zpu
- Zbase = Vbase²/Sbase.
- Use the base of the side where Z is referred.
- The per-unit value is the same from either side.
Problem 2. Per-unit impedance of a load on a new base CPGCBL
A 200 MVA, 345/20.5 kV transformer feeds a 180 MVA, 22.5 kV, 0.8 pf lagging motor. The system base is 100 MVA, 345 kV. Find the per-unit load impedance.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 200 MVA, 345/20.5 kV | transformer |
| M | 180 MVA, 22.5 kV, 0.8 pf lag | motor |
| base | 100 MVA, 345 kV | system |
- Zload (pu)
- Bases follow transformer ratios.
- Znew = Zold × (Snew/Sold)(Vold/Vnew)².
- Load at rated voltage and MVA = 1 pu on its own base.
Problem 3. Changing the per-unit base of a generator reactance BGFCL, BCIC
A generator reactance is 0.25 pu on its nameplate base of 18 kV, 500 MVA. Find the per-unit value on a base of 18 kV, 100 MVA.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Xold | 0.25 pu | on 18 kV, 500 MVA |
| new base | 18 kV, 100 MVA |
- Xnew
- Smaller MVA base → smaller pu value.
- Xohm stays the same; only the base changes.
- Xnew = Xold × Snew/Sold.
Problem 4. Changing the base of a machine reactance BCIC
The reactance X″ of an induction/synchronous machine is 0.25 pu at 18 kV, 100 MVA. What will it be if the new base is 18 kV, 500 MVA?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Xold | 0.25 pu | on 18 kV, 100 MVA |
| new base | 18 kV, 500 MVA |
- Xnew
- pu ∝ MVA base (same kV).
- Check: back-conversion gives 0.25 pu.
- A value above 1 pu is possible on a large base.
Problem 5. Changing the per-unit base when only the MVA changes PGCB
The reactance of a generator designated X″ is given as 0.25 p.u. on the generator's nameplate rating of 18 kV and 500 MVA. The new base for calculation is 18 MVA. Find X″ on the new base.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Xold | 0.25 pu | on 18 kV, 500 MVA |
| new base | 18 MVA | same kV |
- Xnew
- pu ∝ MVA base.
- Read the units: "18 MVA" here, not 18 kV.
- Xnew = Xold × Snew/Sold.
Problem 6. Changing the MVA base of a transformer reactance PGCB
A transformer reactance is 15 % on a 200 MVA base. What is it on a 100 MVA base (same voltage base)?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Xold | 15 % | on 200 MVA |
| Snew | 100 MVA | same kV |
- Xnew
- % = pu × 100.
- Xnew = Xold × Snew/Sold.
- Transformer % reactance is usually on its own rating.
Problem 7. Changing the per-unit base when both kV and MVA change NWPGCL
The reactance of a generator, designated X, is 0.3 per unit based on the generator rating of 10 kV and 500 MVA. If the base is changed to 20 kV and 100 MVA, what is the new per-unit value of X?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Xold | 0.3 pu | on 10 kV, 500 MVA |
| new base | 20 kV, 100 MVA |
- Xnew
- kV enters squared.
- A higher kV base → smaller pu impedance.
- Order: new/old for MVA, old/new for kV.
Problem 8. Per-unit impedance across two transformers MPL
Three parts A, B and C of a single-phase system are joined by transformers A–B (10 000 kVA, 13.8/138 kV, X = 10 %) and B–C (10 000 kVA, 138/69 kV, X = 8 %). The base in circuit B is 10 000 kVA, 138 kV. Find the per-unit impedance of a 300 Ω resistive load in circuit C referred to circuit A.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| TAB | 10 MVA, 13.8/138 kV, 10 % | |
| TBC | 10 MVA, 138/69 kV, 8 % | |
| base in B | 10 MVA, 138 kV | |
| R | 300 Ω | load in C |
- Zpu
- Vbase(other side) = Vbase × turns ratio.
- Zpu = Zohm/Zbase (same zone).
- Per unit is the same in all zones.
Problem 9. Per-unit impedance of a transformer and line on a common base DPDC
A three-phase 5 MVA, 115/13.2 kV transformer has a per-phase series impedance of 0.007 + j0.075 per unit. It is connected to a short line of series impedance 0.02 + j0.10 per unit on a base of 10 MVA, 13.2 kV, supplying a balanced 4 MVA, 13.2 kV load at 0.85 lagging. Draw the per-unit equivalent circuit on a base of 10 MVA, 13.2 kV at the load.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 5 MVA, 0.007 + j0.075 pu | |
| line | 0.02 + j0.10 pu | on 10 MVA |
| load | 4 MVA at 0.85 lag | |
| base | 10 MVA, 13.2 kV |
- per-unit circuit
- Znew = Zold × Snew/Sold.
- Load impedance (pu) = Vpu²/Spu at the p.f. angle.
- Draw the impedance diagram as series boxes.
Problem 10. Per-unit motor current BUET Admission
In a 3-phase motor P = 0.6 p.u. and V = 0.95 p.u. What is the value of I in p.u.?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 0.6 pu | power |
| V | 0.95 pu | voltage |
- I (pu)
- Ppu = Vpu Ipu cos φ.
- No √3 in per unit.
- State any assumption (p.f.).
Problem 11. Single-line diagram and per-unit reactance diagram PGCB, BUET
A 100 MVA, 11 kV generator (X″ = 8 %) feeds a 20 MW, 0.85 pf lagging load at 11 kV through a unit transformer (11/132 kV, 200 MVA, 15 %), a 132 kV double-circuit line (100 km, 80 Ω per circuit) and a grid transformer (132/11 kV, 200 MVA, 15 %). Draw the single-line and reactance diagrams on a 100 MVA base. Neglect resistance and shunt admittance except for the load.
Figure: single-line diagram and per-unit reactance diagramShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 100 MVA, 11 kV, 8 % | |
| T | 200 MVA, 11/132 kV, 15 % | each |
| line | 2 × 80 Ω | double circuit |
| load | 20 MW at 0.85 lag | |
| base | 100 MVA |
- reactance diagram
- Parallel circuits halve the line reactance.
- Zbase(132 kV, 100 MVA) = 174.24 Ω.
- Load impedance = 1/S* in pu at 1 pu voltage.
Problem 12. Per-unit impedance diagram of a generator–line–motor system BPDB
The ratings of the system are: G 60 MVA, 20 kV, X = 9 %; T1 50 MVA, 20/200 kV, X = 10 %; T2 50 MVA, 200/20 kV, X = 10 %; M 43.2 MVA, 18 kV, X = 8 %; line 200 kV, Z = 120 + j200 Ω. Draw the impedance diagram in per unit on a 100 MVA base, taking 20 kV as the voltage base in the generator circuit.
Figure: per-unit impedance diagram on 100 MVAShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| G | 60 MVA, 20 kV, 9 % | |
| T1, T2 | 50 MVA, 20/200 kV, 10 % | |
| M | 43.2 MVA, 18 kV, 8 % | |
| line | 120 + j200 Ω | |
| base | 100 MVA, 20 kV |
- impedance diagram
- Use (kVrated/kVbase)² when ratings differ from the base.
- Zbase at 200 kV, 100 MVA = 400 Ω.
- The resistance of the line stays in the diagram.
Problem 13. Bus admittance matrix of a 3-bus system BCIC
The line series impedances (pu) are 1–2: 0.06 + j0.18; 1–3: 0.03 + j0.09; 2–3: 0.08 + j0.24. Neglect shunt capacitance. Determine Ybus.
Figure: 3-bus network with line impedances and admittancesShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| z₁₂ | 0.06 + j0.18 pu | |
| z₁₃ | 0.03 + j0.09 pu | |
| z₂₃ | 0.08 + j0.24 pu |
- Ybus

- Yii = Σ y at bus i; Yij = −yij.
- Y-bus is symmetric.
- No shunt elements → each row sums to zero.
Problem 14. Y-bus of two buses joined by parallel lines NWPGCL
Two buses are joined by two parallel lines, each j0.2 pu. Find Ybus.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| z | j0.2 pu | each of two parallel lines |
- Ybus
- Parallel: y adds; series: z adds.
- Y₁₂ = −ytotal.
- The matrix rows sum to zero (no shunt).
Problem 15. Load sharing of two generators with droop GTCL
Two generators (no-load frequencies 51.5 Hz and 51 Hz, droop 1 MW/Hz each) supply 3.5 MW. Find the frequency and each share.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| fnl1 | 51.5 Hz | |
| fnl2 | 51 Hz | |
| droop | 1 MW/Hz | each |
| PL | 3.5 MW | load |
- f
- P₁
- P₂
- f = fnl − P/sP.
- Same frequency for all parallel machines.
- Higher no-load setting → larger share.
Problem 16. Frequency of two generators sharing load APSCL
A generator with a no-load frequency of 61.0 Hz and a slope of 1 MW/Hz supplies load 1 of 1000 kW at 0.8 pf lagging. Load 2 of 800 kW at 0.707 pf lagging is to be connected in parallel. Find (a) the frequency before the switch is closed, (b) the frequency after load 2 is connected, and (c) the action to restore 60 Hz.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| fnl | 61.0 Hz | |
| sP | 1 MW/Hz | |
| P₁ | 1000 kW at 0.8 lag | load 1 |
| P₂ | 800 kW at 0.707 lag | load 2 |
- f (before and after)
- correction
- Frequency depends on P only (not Q).
- Restore frequency by raising the governor set-point.
- Slope sP in MW/Hz.
Problem 17. Loop inductance of a single-phase line (2 m spacing) Practice problem
A single-phase line has two parallel conductors 2 m apart. Each conductor is 1.2 cm in diameter. Find the loop inductance per km of the line.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d | 2 m | spacing |
| D | 1.2 cm | conductor diameter |
- L (loop inductance per km)
- Single-phase loop: L = 10⁻⁷(μᵣ + 4 ln d/r) H/m.
- Larger spacing or thinner wire → more inductance (logarithmically).
Problem 18. Loop inductance with copper and with steel conductors Practice problem
A single-phase transmission line has two parallel conductors 3 m apart, each of radius 1 cm. Find the loop inductance per km if the conductors are (i) copper and (ii) steel with a relative permeability of 100.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d | 3 m | |
| r | 1 cm | |
| μᵣ | 1 (copper), 100 (steel) |
- L per km
- Internal inductance ∝ μᵣ.
- Steel conductors → much higher inductance.
Problem 19. Inductance per phase of an equilateral three-phase line Practice problem
A three-phase transmission line uses conductors 1.24 cm in diameter placed at the corners of an equilateral triangle of side 2 m. Find the inductance per phase per km.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| D | 1.24 cm | conductor diameter |
| d | 2 m | equilateral side |
- L per phase per km
- 3-phase, equilateral: L = 10⁻⁷(0.5 + 2 ln d/r) H/m per phase.
- Unsymmetrical spacing: use d = ∛(d₁₂d₂₃d₃₁) with transposition.
Problem 20. Capacitance of a single-phase line Practice problem
A single-phase line has two parallel conductors 3 m apart, each of radius 1 cm. Find the capacitance of the line per km (ε₀ = 8.854 × 10⁻¹² F/m).
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d | 3 m | |
| r | 1 cm | |
| ε₀ | 8.854 × 10⁻¹² F/m |
- C per km
- 1-phase: C = πε₀/ln(d/r) (line to line).
- 3-phase: C = 2πε₀/ln(d/r) per phase to neutral.
Problem 21. Capacitance to neutral of an equilateral three-phase line Practice problem
A three-phase overhead line has its conductors at the corners of an equilateral triangle of 2 m side. Each conductor is 1.25 cm in diameter. Find the capacitance of each conductor to neutral per km.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d | 2 m | equilateral |
| D | 1.25 cm | diameter |
- C to neutral per km
- Cn = 2πε₀/ln(d/r) F/m.
- Typical overhead lines: about 0.01 μF/km per phase.
Problem 22. Capacitance per phase of a 100 km three-phase line Practice problem
Find the capacitance per phase of a 100 km long, 50 Hz, three-phase overhead line with conductors of 2 cm diameter at the corners of an equilateral triangle of 2.5 m side.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| l | 100 km | |
| D | 2 cm | diameter |
| d | 2.5 m | equilateral |
- C per phase
- Line capacitance ∝ length.
- Ic = 2πf C Vph.
Problem 23. Series capacitor to raise power transfer PGCB, BUET
A transmission line has 4 Ω inductive reactance. How much series capacitive reactance raises the real power flow by 10 %?
Figure: series compensation and P–δ curvesShow step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| X₁ | 4 Ω | line reactance |
| ΔP | +10 % | required |
- XC (series capacitor)
- Series capacitor: Xnet = XL − XC.
- P ∝ 1/Xnet.
- Typical compensation 30–70 %.
Problem 24. Receiving-end voltage, current and efficiency when the sending-end voltage is given Practice problem
A three-phase line delivers 3600 kW at 0.8 pf lagging to a load. The sending-end voltage is 33 kV. Each conductor has a resistance of 5.31 Ω and a reactance of 5.54 Ω. Find (i) the receiving-end voltage, (ii) the line current and (iii) the transmission efficiency.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| P | 3600 kW at 0.8 lag | load |
| VS | 33 kV | sending end |
| R | 5.31 Ω | |
| X | 5.54 Ω | per conductor |
- VR
- I
- η
- VS ≈ VR + IR cos φR + IX sin φR (lagging).
- I = Pphase/(VR cos φ).
Problem 25. Power output and sending-end power factor of a short line Practice problem
A short three-phase line with an impedance of (6 + j8) Ω per phase has sending-end and receiving-end voltages of 120 kV and 110 kV respectively for a receiving-end load at 0.9 pf lagging. Find (i) the power output and (ii) the sending-end power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| Z | 6 + j8 Ω | per phase |
| VS | 120 kV | |
| VR | 110 kV | |
| pfR | 0.9 lagging |
- P
- pfS
- cos φS = (VR cos φR + IR)/VS.
- A 10 kV difference across 10 Ω of impedance lets about 650 A flow.
Problem 26. Regulation and efficiency of an 11 kV line Practice problem
An 11 kV, three-phase line has a resistance of 1.5 Ω and a reactance of 4 Ω per phase. Find the percentage regulation and the efficiency when it supplies a total load of 5000 kVA at 0.8 pf lagging at 11 kV at the far end.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VR | 11 kV | receiving end |
| R | 1.5 Ω | |
| X | 4 Ω | per phase |
| S | 5000 kVA at 0.8 lag |
- regulation
- η
- Short line: regulation = (VS − VR)/VR.
- Drop ≈ I(R cos φ + X sin φ).
Problem 27. Voltage regulation of a transmission line with ABCD constants SGFL
A 132 kV, 50 Hz, 3-phase line delivers 50 MW at 0.8 pf lagging. Its constants are A = D = 0.95∠1.4°, B = 96∠78° Ω and C = 0.0015∠90° S. Find the voltage regulation and the charging current.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 132 kV | |
| P | 50 MW at 0.8 lag | |
| A | D=0.95∠1.4° | |
| B | 96∠7.8° Ω | |
| C | 0.0015∠90° S |
- regulation
- VR(no-load) = VS/|A| (not VS).
- Work per phase in kV and A.
- Medium/long lines need A, B, C, D.
Problem 28. Voltage regulation from no-load and full-load readings NWPGCL
Find the voltage regulation at the receiving end of a 50 km long transmission line from the data: load current 0 A: sending-end and receiving-end line-to-neutral voltages 230 V and 230 V; 200 A: 230 V sending and 215 V receiving; 200 A: 240 V sending and 225 V receiving.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| I | 0 A | 230 V / 230 V |
| I | 200 A | 230 V / 215 V or 240 V / 225 V |
- regulation
- Regulation = (VNL − VFL)/VFL.
- VNL = Vs for a short line.
- Use line-to-neutral or line values consistently.
Problem 29. Copper saving when the voltage is raised BUET M.Sc.
What percentage of feeder copper is saved if a 2-wire DC system is raised from 200 V to 400 V for the same power, distance and loss?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V₁ | 200 V | |
| V₂ | 400 V | same P, distance, loss |
- copper saving
- Copper volume ∝ 1/V².
- Doubling V saves 75 % copper.
- Same power and same loss assumed.
Problem 30. Extra load when a 2-wire d.c. line becomes a 3-phase, 3-wire a.c. line Practice problem
A 2-wire d.c. system is converted into a 3-phase, 3-wire a.c. system by adding a third conductor of the same cross-section as the existing two. If the voltage between wires and the percentage line loss stay the same, what percentage of additional load can now be supplied? Assume a balanced load at unity power factor.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d.c. | 2 wires, voltage V | |
| a.c. | 3 wires, line voltage V, unity pf | |
| loss | same percentage |
- extra load
- Compare systems by equal voltage between conductors and equal percentage loss.
- 3-phase 3-wire: P = √3VI cos φ.
Problem 31. Extra load when a 3-wire d.c. line becomes a 3-phase, 4-wire a.c. line Practice problem
A 3-wire d.c. system is converted into a 3-phase, 4-wire system by adding a fourth wire equal in cross-section to each outer of the d.c. system. If the percentage power loss and the voltage at the consumer’s terminals (conductor to neutral) are the same in both cases, find the extra power at unity pf that the a.c. system can supply. Assume balanced loads.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| d.c. | 3-wire, V outer to neutral | |
| a.c. | 3-phase 4-wire, V phase to neutral, unity pf | |
| loss | same percentage |
- extra power
- Balanced load → no neutral current, no neutral loss.
- 3-phase 4-wire: P = 3Vph I at upf.
Problem 32. Voltage at two tram cars on a d.c. feeder Practice problem
Two tram cars A and B, 2 km and 6 km from a sub-station, take 40 A and 20 A respectively. The sub-station voltage is 600 V d.c. The trolley wire has a resistance of 0.25 Ω/km and the track (return) 0.03 Ω/km. Find the voltage across each tram car.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 600 V | sub-station |
| IA | 40 A at 2 km | |
| IB | 20 A at 6 km | |
| rw | 0.25 Ω/km | trolley |
| rt | 0.03 Ω/km | track |
- VA
- VB
- Section current = sum of all loads beyond it.
- Use loop (go + return) resistance.
Problem 33. Voltage distribution and string efficiency of a 3-disc string (33 kV) Practice problem
In a 33 kV overhead line there are three discs in each string of insulators. The capacitance between each insulator pin and earth is 11 % of the self-capacitance of each insulator. Find (i) the voltage across each of the 3 discs and (ii) the string efficiency.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VL | 33 kV | |
| n | 3 | discs |
| K | 0.11 | shunt/self capacitance |
- V₁, V₂, V₃
- string efficiency
- V₂ = V₁(1 + K); V₃ = V₂ + (V₁ + V₂)K.
- String efficiency = V/(n × Vn).
Problem 34. Maximum safe voltage of a 3-disc string Practice problem
An insulator string consists of three units, each with a safe working voltage of 15 kV. The ratio of self-capacitance to shunt capacitance of each unit is 8 : 1. Find the maximum safe working voltage of the string and the string efficiency.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| n | 3 | units |
| Vsafe | 15 kV | each |
| C/Csh | 8 : 1 |
- Vstring
- efficiency
- Max string voltage is set by the disc nearest the conductor.
- Guard rings or grading reduce the unequal sharing.
Problem 35. Voltage across each disc of a 5-disc string on a 100 kV line Practice problem
A string of 5 insulators is connected across a 100 kV line. If the capacitance of each disc to earth is 0.1 of the capacitance of the insulator, find (i) the voltage across each disc and (ii) the string efficiency.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| n | 5 | discs |
| VL | 100 kV | |
| K | 0.1 | shunt/self capacitance |
- V across each disc
- efficiency
- More discs → lower string efficiency.
- The bottom disc takes almost a third of the voltage here.
Problem 36. Disruptive critical voltage of a three-phase line Practice problem
A three-phase line has conductors 2 cm in diameter spaced equilaterally 1 m apart. The dielectric strength of air is 30 kV (peak) per cm. Find the disruptive critical voltage of the line. Take the air density factor δ = 0.952 and the irregularity factor m₀ = 0.9.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| D | 2 cm | diameter |
| d | 1 m | spacing |
| g₀ | 30 kV/cm peak | |
| δ | 0.952 | |
| m₀ | 0.9 |
- Vc
- Vc = m₀g₀δr ln(d/r) (phase, r.m.s.).
- g₀ = 30 kV/cm peak = 21.2 kV/cm r.m.s.
Problem 37. Conductor spacing for a given corona onset voltage Practice problem
A 132 kV line with 1.956 cm diameter conductors is built so that corona takes place only if the line voltage exceeds 210 kV (r.m.s.). If the potential gradient at which ionisation occurs is 30 kV per cm (peak), find the spacing between the conductors. Assume smooth conductors and standard air (m₀ = δ = 1).
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| VL | 210 kV | corona onset |
| D | 1.956 cm | diameter |
| g₀ | 30 kV/cm peak | |
| m₀ | δ=1 |
- d
- ln(d/r) = Vc/(m₀g₀δr).
- The answer is very sensitive to rounding.
Problem 38. Disruptive critical voltage from two corona-loss measurements Practice problem
A three-phase equilateral line has a total corona loss of 53 kW at 106 kV and 98 kW at 110.9 kV. Find the disruptive critical voltage and the corona loss at 113 kV.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| W₁ | 53 kW at 106 kV | |
| W₂ | 98 kW at 110.9 kV | |
| V₃ | 113 kV | new voltage |
- Vc
- W (at 113 kV)
- Corona loss ∝ (Vph − Vc)².
- Use phase voltages in Peek’s formula.
Problem 39. Sag and height of a transmission line support DPDC
A 132 kV transmission line has a conductor weight of 680 kg/km, a span of 260 m, an ultimate strength of 3100 kg and a safety factor of 2. The required ground clearance is 10 m. Find the height above ground at which the conductor should be supported.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| w | 680 kg/km | 0.68 kg/m |
| l | 260 m | span |
| Tu | 3100 kg | ultimate |
| SF | 2 | |
| clearance | 10 m |
- height of support
- S = wl²/(8T) (level supports).
- Use w in kg/m with T in kg.
- Height = clearance + sag.
Problem 40. Slant and vertical sag with wind loading (span 150 m) Practice problem
A transmission line has a span of 150 m between level supports. The conductor has a cross-section of 2 cm², the tension in it is 2000 kg, the specific gravity of the conductor material is 9.9 g/cm³ and the wind pressure is 1.5 kg per metre length. Find the sag and the vertical sag.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| l | 150 m | |
| A | 2 cm² | |
| T | 2000 kg | |
| ρ | 9.9 g/cm³ | |
| ww | 1.5 kg/m | wind |
- slant sag
- vertical sag
- S = wt l²/(8T); vertical sag = S cos θ.
- wt = √(w² + ww²) (add ice weight to w if given).
Problem 41. Sag with wind pressure on the projected area (span 200 m) Practice problem
A transmission line has a span of 200 m between level supports. The conductor has a cross-section of 1.29 cm², weighs 1170 kg/km and has a breaking stress of 4218 kg/cm². Calculate the sag for a safety factor of 5, allowing a wind pressure of 122 kg per square metre of projected area. What is the vertical sag?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| l | 200 m | |
| A | 1.29 cm² | |
| w | 1170 kg/km | |
| σ (breaking) | 4218 kg/cm² | |
| SF | 5 | |
| p | 122 kg/m² | wind |
- slant sag
- vertical sag
- ww = pressure × diameter.
- T = breaking stress × area/factor of safety.
Problem 42. Factor of safety from a measured vertical sag Practice problem
A transmission line has a span of 214 m between level supports. The conductors have a cross-section of 3.225 cm². Find the factor of safety given: vertical sag = 2.35 m, wind pressure = 1.5 kg per metre run, breaking stress = 2540 kg/cm², weight of conductor = 1.125 kg per metre run.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| l | 214 m | |
| A | 3.225 cm² | |
| Sv | 2.35 m | vertical sag |
| ww | 1.5 kg/m | |
| σ (breaking) | 2540 kg/cm² | |
| w | 1.125 kg/m |
- safety factor
- cos θ = w/wt.
- Factor of safety = breaking load/working tension.
Problem 43. Sag and lowest point of a conductor on supports of different heights PGCB
The towers of height 30 m and 90 m respectively support a transmission line conductor at a water crossing. The horizontal distance between the towers is 500 m. If the tension in the conductor is 1600 kg, find the minimum clearance of the conductor and water, and the clearance midway between the supports. The weight of the conductor is 1.5 kg/m. The bases of the towers can be considered to be at water level.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| h₁, h₂ | 30 m, 90 m | tower heights |
| l | 500 m | |
| T | 1600 kg | |
| w | 1.5 kg/m |
- minimum clearance
- mid-span clearance
- x₁ = l/2 − Th/(wl) from the lower support.
- Clearance = lower support height − S₁.
- Height at x = lowest + w(x − x₁)²/(2T).
Problem 44. Mid-span clearance at a river crossing when the lowest point lies outside the span Practice problem
An overhead line at a river crossing is supported from two towers 40 m and 90 m above water level, 400 m apart horizontally. The maximum allowable tension is 2000 kg and the conductor weighs 1 kg/m. Find the clearance between the conductor and the water at a point mid-way between the towers.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| hA, hB | 40 m, 90 m | tower heights |
| l | 400 m | |
| T | 2000 kg | |
| w | 1 kg/m |
- mid-span clearance
- Sag from lowest point: y = wx²/(2T).
- h = (w/2T)(x₂² − x₁²).
- DC Circuit Analysis
- Network Theorems
- RL, RC & RLC Transients
- Single-Phase AC Circuits
- Series & Parallel Resonance
- Power Factor Correction
- Three-Phase Circuits
- Transformer
- DC Generator & DC Motor
- Three-Phase Induction Motor
- Synchronous Machines
- Diode Circuits
- BJT Biasing & Amplifiers
- MOSFET & Power Electronics
- Op-Amp Circuits
- AM, FM & Analog Modulation
- Signals and Sampling
- PCM, Delta Modulation & TDM
- Digital Communication & Telecom
- Load Curves & Power Generation
- Per-Unit & Transmission Lines (this post)
- Faults & Symmetrical Components
- Protection & Switchgear
- Control Systems
- Digital Logic & Microprocessors
- Measurement, Mechanics & Aptitude
Topics shown in grey are coming soon. See every post in this series.
Found a mistake or have a better method? Leave a comment below. More topics from the question bank are in the other posts of this series.
Thank you for visiting my blog.