Protection & Switchgear question solutions for EEE job exams. 18 written questions and 17 math problems on Protection & Switchgear, the kind asked in Bangladesh EEE recruitment exams (BPDB, PGCB, DPDC, DESCO, NWPGCL, EGCB, BCS and others), each solved in exam style: the given data, what is required, the formula used at every step, the substitution and the final answer.
This post is part 23 of the EEE Job Preparation Question Bank series. It covers protection, switchgear and substations with 35 solved questions: 12 written (theory) questions on relays, fuses and circuit breakers, the relay–breaker trip circuit, ACB and OCB, CTs and PTs, biased differential and loss-of-excitation protection, neutral earthing, lightning arresters and substation layouts and 6 math problems on relay pick-up, IDMT operating time, CT ratios for transformer differential protection and circuit-breaker ratings from recruitment exams (PGCB, BPDB, DPDC, PGCL, BREB, EGCB, BIFPCL, NPCBL), plus 11 practice problems and 6 practice written questions on the same topics.
The answers are written for learning, not only for checking. A written answer explains what the thing is, why it is so, how it works and where it is used; where a question says "draw", the diagram is built up one step at a time. A math solution is laid out the way an examiner wants to see it: the given data with symbols and values, the quantity required, and then each step as formula → substitution → result, with the reason for that step written beside it. It also shows how to think about that type of problem, a diagram, and what to keep in mind.
How to use this post: every answer is hidden. Try the question on paper first, then click Show full answer or Show step-by-step solution. The grey tag beside a question shows the exam it came from.
- Formulas to memorize first
- Part A: Written questions (18)
Show the list
- Write down the function of a relay, a fuse and a circuit breaker.
- Draw a basic diagram showing how a relay is interfaced with a circuit…
- Differentiate ACB and oil circuit breaker.
- What are instrument transformers?
- Why is a CT short-circuited before the relay coil is removed during…
- Draw a diagram for a biased differential protection scheme for a unit…
- How is loss-of-excitation protection of a synchronous motor provided?
- Why do we ground the Y-neutral in a D-Y transformer?
- Why do we use a lightning arrester with a transformer?
- What is a substation and what are its main components?
- Draw and describe the single-line diagram of a typical 33/11 kV…
- Draw the layout diagram of a substation having a double bus-bar with a…
- Explain the Merz-Price circulating-current protection of an alternator.…
- What is time-graded over-current protection? Explain it for a radial…
- How is an alternator protected against inter-turn (turn-to-turn) faults…
- In the differential protection of a star–delta power transformer, why…
- Explain the differential protection of a bus-bar with a diagram.
- Draw the single-line diagram of an 11 kV/400 V distribution sub-station…
- Part B: Solved problems (17)
Show the list
- Relay pick-up current through a CT
- Pick-up current of an over-current relay
- Operating time of an over-current relay
- CT ratio for a differential relay across a Δ–Y transformer
- CT ratio for a Y–Δ transformer differential relay
- CT ratio on the 11 kV side of a 0.4/11 kV star–delta transformer
- CT ratio on the 33 kV side when the given CTs are on the delta side
- Unprotected part of a stator winding (earthing resistance 7.5 Ω)
- Unprotected winding and the resistance needed for 90 % protection
- Earthing resistance for 85 % protection with a 20 % earth-fault setting
- Unprotected winding when the alternator reactance is included
- Protected percentage and the resistance for 95 % protection (25 MVA, 11…
- Ratings of a circuit breaker
- Peak restriking voltage, frequency and RRRV of an 11 kV breaker
- Average RRRV and natural frequency from a short-circuit test
- Voltage across the contacts when a magnetising current is chopped
- Radius of a fuse wire for a lower fusing current
- Other parts of this series
Formulas to Memorize First
- Relay senses and decides; circuit breaker interrupts (and can reclose); fuse senses and interrupts once, then must be replaced.
- CT: in series, steps current down (e.g. 400/5 A); never open its secondary on load. PT: in parallel, steps voltage down (e.g. 11 kV/110 V); never short its secondary.
- Relay secondary current = primary current × (CT secondary/CT primary).
- Pick-up current = relay rating × current (plug) setting; PSM = secondary fault current/pick-up current.
- IDMT time = time at TMS 1 (from the curve) × TMS. Standard (normal inverse) curve: t = 0.14 × TMS/(PSM0.02 − 1); 3 s at PSM 10.
- Transformer differential: CTs on the star side in delta, on the delta side in star; delta CTs multiply the relay current by √3.
- Biased differential: trip when |I₁ − I₂| > K(I₁ + I₂)/2.
- Breaker ratings: symmetrical breaking current = MVA/(√3 kV); making current = 2.55 × breaking current (peak); short-time current for 1 or 3 s.
- Arc quenching media: air (ACB, LV), oil (OCB), SF₆, vacuum (VCB, 11–33 kV).
Part A: Written Questions on Protection, Switchgear & Substations
Q1. Write down the function of a relay, a fuse and a circuit breaker. PGCL
Show full answer
The idea
Protection has two jobs: detect the fault and interrupt the current. A relay and a circuit breaker share these jobs; a fuse does both in one cheap device.
The chain
Each picture adds one step to the one before it. Draw it on paper in the same order.
Functions
| Device | Function | Notes |
|---|---|---|
| Relay | Senses an abnormal condition (over-current, under-voltage, differential current, impedance) through CTs/PTs and closes its contacts to send a trip signal to the breaker. | Cannot interrupt the current itself. |
| Fuse | A thin series element that melts when the current exceeds its rating for long enough, opening the circuit. | Cheap and fast; works once and must be replaced; used mainly at LV and for small equipment. |
| Circuit breaker | A mechanical switch that can make, carry and break normal and fault currents, quenching the arc. Operated by hand, by a relay or remotely. | Can be reclosed after the fault is cleared. |
Keep in mind
Relay = detect; CB = interrupt (reusable); fuse = detect + interrupt (one-time).
Q2. Draw a basic diagram showing how a relay is interfaced with a circuit breaker. NPCBL
Show full answer
How to draw it
Each picture adds one step to the one before it. Draw it on paper in the same order.
How it works
- The CT gives the relay a current proportional to the line current.
- On a fault the relay current exceeds its setting, and the relay contact closes.
- The DC battery drives current through the trip coil, which releases the breaker mechanism; the main contacts open and the arc is quenched.
- The 52a auxiliary contact (closed when the breaker is closed) opens with the breaker, cutting off the trip-coil current so the coil does not burn.
Why a DC battery
During a fault the a.c. voltage may collapse; a station battery keeps the trip circuit working.
Keep in mind
CT → relay coil; relay contact + trip coil + 52a in series with the DC battery.
Q3. Differentiate ACB and oil circuit breaker. BEPZA
Show full answer
Short answer
Both are circuit breakers; they differ in the medium used to extinguish the arc.
| Point | Air circuit breaker (ACB) | Oil circuit breaker (OCB) |
|---|---|---|
| Arc medium | Air at atmospheric pressure (air-blast types use compressed air) | Insulating (transformer) oil |
| How the arc is quenched | The arc is lengthened by arc runners, split by the plates of an arc chute and cooled until it cannot restrike | The arc decomposes the oil into gas (mainly hydrogen); the gas bubble cools the arc and the oil also insulates the gap |
| Voltage range | Mainly LV (up to about 1 kV); air-blast up to EHV | Medium and high voltage (11–220 kV in older stations) |
| Fire risk | None | Oil is flammable; risk of fire or explosion |
| Maintenance | Less; contacts and chutes checked | More; oil becomes carbonised and must be filtered or replaced |
| Size | Compact at LV | Large tank and heavy |
Today
SF₆ breakers (high voltage) and vacuum breakers (11–33 kV) have largely replaced OCBs because they need little maintenance and have no fire risk.
Keep in mind
ACB: air, LV, no fire. OCB: oil → hydrogen, HV, fire risk, more maintenance.
Q4. What are instrument transformers? PGCL
Show full answer
Definition
Instrument transformers are accurate, low-power transformers used to extend the range of a.c. meters and relays and to isolate them from the high-voltage line.
How they are connected
The two types
- Current transformer (CT): primary in series with the line (often one turn, the line itself). It steps the current down to 5 A or 1 A for ammeters, wattmeter current coils, energy meters and relays. Its secondary must never be open-circuited on load.
- Potential (voltage) transformer (PT/VT): primary connected across the line. It steps the voltage down to 110 V for voltmeters, wattmeter pressure coils and relays. Its secondary must never be short-circuited.
Advantages
- Standard low-range instruments (5 A, 110 V) can measure any current or voltage.
- Meters and personnel are isolated from high voltage; the secondary is earthed.
- Meters can be placed in a control room away from the line.
Keep in mind
CT: series, 5 A/1 A, never open. PT: parallel, 110 V, never short.
Q5. Why is a CT short-circuited before the relay coil is removed during inspection? What is the observation? DWASA
Show full answer
Short answer
Because an open-circuited CT secondary develops a dangerously high voltage. The secondary is short-circuited first so the current always has a closed path.
Why it happens
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. With the secondary open nothing opposes the primary ampere-turns: the whole primary current magnetises the core, which saturates. The flux becomes flat-topped and changes very fast near each current zero, so es = N dΦ/dt has very high peaks.What is observed
- Very high voltage peaks (several kV) across the open secondary terminals: a shock hazard and a risk of insulation breakdown.
- Heavy core loss: the CT overheats.
- The core may be left with residual magnetism, which spoils its accuracy afterwards.
Correct practice
Close the CT shorting link (or test-block short) before removing a relay or meter, and remove the short only after the instrument is reconnected.
Keep in mind
CT secondary open = all primary current magnetises the core → saturation → kV peaks. Always short it first.
Q6. Draw a diagram for a biased differential protection scheme for a unit connection (generator–transformer unit). PGCB
Show full answer
How to draw it
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. Connect the operating coil from the mid-point of the restraining coil to the return pilot wire. Mark I₁, I₂ and I₁ − I₂.Principle
- For load current or an external (through) fault, the same current enters and leaves the zone, so I₁ = I₂ and nothing flows in the operating coil.
- For an internal fault I₁ ≠ I₂, and the difference flows in the operating coil.
Why the bias
CT mismatch, tap changing and magnetising inrush make I₁ and I₂ slightly different even for a through fault, and the error grows with the current. The restraining coils carry (I₁ + I₂)/2, so the operating current needed to trip rises with the through current: trip when |I₁ − I₂| > K(I₁ + I₂)/2, with K about 10–40 %.
CT connections for a unit transformer
CTs on the star side of the transformer are connected in delta and those on the delta side in star. This corrects the 30° phase shift and removes zero-sequence current, and the CT ratios are chosen so the relay currents balance.
Keep in mind
Differential = compare currents in and out. Bias = restraint ∝ through current; operate ∝ difference.
Q7. How is loss-of-excitation protection of a synchronous motor provided? BIFPCL
Show full answer
What happens on loss of excitation
When the field fails, the machine can no longer produce its own magnetising (reactive) power. It draws large reactive power from the system, the stator current rises, the rotor slips out of synchronism (a motor stalls or pulls out of step) and the rotor surface overheats from induced currents.
Methods of protection
- Field-failure (d.c. under-current) relay connected in the field circuit: it drops out and trips the breaker when the field current falls below a set value.
- Offset mho (impedance) relay at the stator terminals, fed from CTs and PTs, which watches the impedance seen from the machine terminals.
- A reactive-power (var) relay that operates when the machine absorbs more than a set amount of reactive power.
The offset mho relay
The circle is offset by Xd′/2 below the origin and has a diameter of about Xd, so stable power swings do not enter it. After a short time delay the relay trips the breaker and may transfer the field to a standby exciter or start an alarm.
Keep in mind
Loss of field: field under-current relay, or offset mho relay (offset Xd′/2, diameter Xd) at the stator.
Q8. Why do we ground the Y-neutral in a D-Y transformer? BPDB
Show full answer
The reasons
- Earth-fault protection: a single line-to-ground fault produces a large enough current (through the neutral) to operate the earth-fault relays and clear the fault quickly.
- Stable phase voltages: the neutral is fixed at earth potential, so unbalanced single-phase loads (very common on 400/230 V and 11 kV systems) do not shift the phase voltages.
- Limits over-voltages: it prevents arcing-ground and transient over-voltages on the healthy phases during an earth fault; the insulation can be designed for phase voltage.
- Single-phase supply: the earthed neutral gives the 230 V phase-to-neutral supply for consumers.
- The Δ winding provides a closed path for third-harmonic and zero-sequence currents, so the phase voltages stay sinusoidal.
Keep in mind
Earthed Y neutral → path for I₀ (relays operate), fixed neutral, no arcing-ground over-voltage, single-phase supply.
Q9. Why do we use a lightning arrester with a transformer? BPDB
Show full answer
The problem
Lightning strokes and switching operations send travelling voltage surges along the line. Their peak can be several times the transformer's insulation level, and the winding insulation (which is costly and slow to repair) would puncture.
How the arrester protects
- At normal voltage the arrester (non-linear metal-oxide or SiC blocks) has a very high resistance and draws almost no current.
- When the surge voltage exceeds its sparkover/clamping level its resistance falls sharply, and it diverts the surge current to earth.
- The voltage across the transformer is held at the arrester's residual voltage, below the transformer BIL.
- After the surge passes, the arrester returns to the high-resistance state, so the power-frequency follow current is cut off and the supply is not interrupted.
Keep in mind
Arrester: open at normal voltage, short to earth during a surge, self-restoring; mount close to the transformer.
Q10. What is a substation and what are its main components? BREB
Show full answer
Definition
A substation is a node of the power system where the voltage is transformed (stepped up or down) and/or circuits are switched, protected and controlled. Types: step-up (at power stations), grid/transmission, distribution, switching and converter substations.
Picture
A typical 33/11 kV distribution substation showing the main components.Main components
- Power transformers: change the voltage.
- Circuit breakers: switch and interrupt fault current.
- Isolators: off-load disconnection for maintenance.
- Bus bars: common connection points.
- CTs and PTs: feed meters and relays.
- Protective relays and the control panel.
- Lightning arresters: surge protection.
- Capacitor banks: power-factor and voltage support.
- Station auxiliary transformer, battery and charger, earthing grid, and the control room.
Keep in mind
Transformer, CB, isolator, bus bar, CT/PT, relay, LA, capacitor bank, battery, earthing.
Q11. Draw and describe the single-line diagram of a typical 33/11 kV substation. DPDC
Show full answer
How to draw it
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. From the 11 kV bus: outgoing 11 kV feeders, each with a breaker, CT and relay; the station auxiliary transformer and a capacitor bank.Description
- Power arrives on two 33 kV lines (for reliability). The lightning arresters at the entry protect the station from surges.
- Isolators allow each breaker to be isolated for maintenance; breakers are operated by relays fed from CTs.
- The 33 kV bus collects the incoming supply; a PT on it feeds voltmeters and relays.
- Two (or more) 33/11 kV transformers, typically 10/13.33 or 20/26.66 MVA, step down the voltage. Their Y-side neutral is earthed.
- The 11 kV bus distributes the power to outgoing feeders; each feeder breaker has over-current and earth-fault relays.
- The station auxiliary transformer (11/0.4 kV) supplies lighting, battery chargers and cooling; capacitor banks improve the power factor.
Keep in mind
LA → isolator → CB (CT) → 33 kV bus → transformer → CB → 11 kV bus → feeder CBs.
Q12. Draw the layout diagram of a substation having a double bus-bar with a single circuit breaker for each circuit. DPDC
Show full answer
Layout
How it is arranged
- Two parallel bus-bars run the length of the substation: the main bus and the reserve bus.
- Each incoming or outgoing circuit has one circuit breaker, with an isolator on each side of it.
- Above the breaker, two bus-selector isolators connect the circuit to either the main or the reserve bus.
- A bus coupler (a breaker with isolators) joins the two buses, so circuits can be transferred between buses on load.
Advantages and disadvantages
- Any circuit can be moved to the other bus without an outage; either bus can be taken out for maintenance.
- Loads can be split between the buses, and a bus fault affects only the circuits on that bus.
- But maintenance of a circuit breaker still disconnects its own circuit (unless a transfer bus is added), and the isolator switching is more complex.
Keep in mind
Double bus, single breaker: 2 buses, 1 CB per circuit, 2 bus-selector isolators, 1 bus coupler.
Q13. Explain the Merz-Price circulating-current protection of an alternator. Why is a part of the stator winding next to the star point left unprotected against earth faults? Practice question
Show full answer
Principle
Each picture adds one step to the one before it. Draw it on paper in the same order.
Main points
- The protected zone is the part of the circuit between the two sets of CTs.
- It is very fast and does not need time grading, because external faults give no relay current.
- The CTs must be matched; otherwise saturation during external faults produces a false difference current (biased relays cure this).
Why part of the winding is unprotected
When the neutral is earthed through a resistance R, an earth fault at a fraction x of the winding (measured from the star point) is driven only by x × Vph. The fault current x Vph/R is below the relay setting when x is small, so faults close to the star point are not detected. The unprotected fraction is x = Isetting × R/Vph; reducing R increases the protected part but raises the earth-fault current.
Keep in mind
Equal currents at both ends → circulate, relay current 0. Internal fault → difference → trip. Unprotected fraction x = Iset R/Vph.
Q14. What is time-graded over-current protection? Explain it for a radial system fed from a main bus. Practice question
Show full answer
Idea
In a radial system the same fault current flows through every breaker between the source and the fault. To make only the breaker nearest the fault open, the relays are given operating times that increase towards the source. This is time grading (discrimination by time).
Picture
Points to mention
- The grading margin (here 0.4 s) must cover breaker opening time, relay overshoot and errors — typically 0.3–0.5 s.
- Disadvantage: the relay nearest the source, where the fault current is largest, has the longest time. IDMT relays reduce this because they operate faster on heavier currents.
- Time grading is simple and cheap and is used on distribution feeders; unit (differential) protection is used where fast clearance is essential.
Keep in mind
Farther from the source → shorter time. Grading margin ≈ 0.4 s. Backup is automatic.
Q15. How is an alternator protected against inter-turn (turn-to-turn) faults in its stator winding? Practice question
Show full answer
The problem
A short circuit between turns of the same phase does not change the current entering and leaving that phase, so the ordinary Merz-Price (circulating-current) scheme cannot detect it. Inter-turn faults are serious in multi-turn coils, because the large circulating current in the shorted turns burns the insulation.
Split-winding (transverse differential) protection
- When the winding is healthy, the two paths carry equal currents and the relay current is zero.
- A short between turns of one path changes its e.m.f. and impedance, so a circulating current flows between the paths; the CT currents become unequal and the relay trips.
- Where the winding cannot be split, a voltage-based method is used: an inter-turn fault produces a neutral (zero-sequence) voltage, measured across a voltage transformer connected between the star point and the line terminals.
Keep in mind
Inter-turn faults are invisible to Merz-Price. Use split-phase (compare the parallel paths) or zero-sequence voltage protection.
Q16. In the differential protection of a star–delta power transformer, why are the CTs connected in delta on the star side and in star on the delta side? Practice question
Show full answer
Two problems to solve
- Phase shift: a star–delta transformer shifts the line currents by 30° between its two sides. If the CTs were connected the same way on both sides, the two secondary currents would never be equal in phase, and the relay would see a difference current even at normal load.
- Zero-sequence current: for an earth fault outside the zone on the star side, zero-sequence current flows in the star-side lines but not in the delta-side lines. Star-connected CTs on the star side would send it into the relay and cause a false trip.
How the connections fix them
- The delta of CTs shifts its output by 30° in the same direction as the power transformer, so the two pilot currents are in phase.
- Zero-sequence currents circulate inside the CT delta and do not reach the pilots, so external earth faults cannot trip the relay.
- The delta multiplies the current by √3, so the CT ratios are chosen to make the pilot currents equal (see the CT-ratio problems in Part B).
Keep in mind
CT connection is always the opposite of the winding it sits on: Y winding → Δ CTs, Δ winding → Y CTs.
Q17. Explain the differential protection of a bus-bar with a diagram. Practice question
Show full answer
Principle
It is Kirchhoff’s current law applied to the bus: for a healthy bus-bar the total current flowing in equals the total current flowing out. CTs of the same ratio are placed in every circuit connected to the bus, and their secondaries are paralleled with the relay.
Picture
- Normal load or a fault on a feeder: the current entering the bus equals the current leaving it, so the CT secondary currents cancel and the relay current is zero.
- Fault on the bus: all sources feed into the bus and nothing leaves; the CT currents add up in the relay, which trips every breaker connected to the bus.
- CT saturation during heavy external faults can upset the balance; high-impedance relays or biased relays are used to keep the scheme stable.
Keep in mind
Σ Iin = Σ Iout → 0 in the relay. Bus fault → all CT currents add → trip every bus breaker.
Q18. Draw the single-line diagram of an 11 kV/400 V distribution sub-station (pole-mounted) and name its equipment. Practice question
Show full answer
How to draw it
Each picture adds one step to the one before it. Draw it on paper in the same order.
Drawing step 3 of 3. On the low-voltage side: the earthed neutral, an L.T. breaker or MCCB, the 400 V bus and the outgoing 400/230 V feeders.Equipment and purpose
- Lightning arrester: diverts surges from the 11 kV line to earth.
- Drop-out fuse: protects the transformer against faults and isolates it visibly when it blows.
- Isolating switch (A.B. switch): off-load disconnection for maintenance.
- Transformer (Δ/Y, 11 kV/400 V): the star-point is solidly earthed to give 230 V phase-to-neutral supply.
- L.T. circuit breaker or MCCB, and fuses on each feeder: protect the transformer and the low-voltage lines.
Larger indoor (or plinth) 11 kV/400 V sub-stations follow the same chain, but use an 11 kV circuit breaker with CTs and relays in place of the drop-out fuse, PTs for metering, and several transformers on a common 11 kV bus.
Keep in mind
LA → DO fuse → isolator → 11/0.4 kV transformer (Y neutral earthed) → L.T. breaker → 400 V feeders.
Part B: Solved Problems on Protection, Switchgear & Substations
Problem 1. Relay pick-up current through a CT PGCB
What does a protective relay do? A 132 kV line has rated current 700 A and a CT of 800:5. What must the relay pick-up exceed?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| V | 132 kV | line |
| Ir | 700 A | rated current |
| CT | 800 : 5 |
- pick-up current
- Is = Ip × (5/primary rating).
- Pick-up above maximum load current.
- The relay rating is 5 A (or 1 A).
Problem 2. Pick-up current of an over-current relay EGCB
An over-current relay with a current setting of 125 % is connected to a supply circuit through a 400/5 CT. Find the pick-up current.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| setting | 125 % | current setting |
| CT | 400/5 | |
| Irated | 5 A | relay |
- pick-up current
- Pick-up = rating × plug setting.
- Primary pick-up = secondary × CT ratio.
- PSM uses the secondary pick-up current.
Problem 3. Operating time of an over-current relay BIFPCL
Determine the time of operation of a 5 A, 3 s over-current relay with a current setting of 125 % and a time-setting multiplier of 0.6, connected through a 400/5 current transformer when the circuit carries a fault current of 4000 A (use the standard IDMT relay curve).
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| relay | 5 A, 3 s | |
| setting | 125 % | |
| TMS | 0.6 | |
| CT | 400/5 | |
| If | 4000 A |
- t (operating time)
- PSM = Ifault(sec)/Ipick-up.
- t = t(TMS 1) × TMS.
- The "3 s" relay gives 3 s at PSM 10, TMS 1.
Problem 4. CT ratio for a differential relay across a Δ–Y transformer PGCB
A 11/132 kV, Δ–Y transformer is protected by differential relay with 500/5 CTs on the 11 kV side. Find the ratio on the 132 kV side.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 11/132 kV, Δ–Y | |
| CT₁₁ | 500/5 | on 11 kV side |
- CT ratio (132 kV side)
- Star side of the power transformer → CTs in delta (and vice versa).
- Delta CTs give √3 × CT secondary current.
- Pick the nearest standard CT ratio.
Problem 5. CT ratio for a Y–Δ transformer differential relay BCMCL
A 3-phase transformer of 220/11 000 line volts is connected star/delta. The protective CTs on the 220 V side are 600/5. What CT ratio is needed on the 11 000 V side?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 220/11 000 V, Y–Δ | |
| CT₂₂₀ | 600/5 |
- CT ratio (11 kV side)
- IL ∝ 1/VL.
- √3 appears on the side whose CTs are in delta.
- Ratio x : 5 means x A primary per 5 A secondary.
Problem 6. CT ratio on the 11 kV side of a 0.4/11 kV star–delta transformer Practice problem
A 3-phase transformer with a line-voltage ratio of 0.4 kV/11 kV is connected star–delta. The protective CTs on the 400 V side have a ratio of 500/5. What must the ratio of the CTs on the 11 kV side be?
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 0.4/11 kV, Y–Δ | |
| CT₄₀₀ | 500/5 |
- CT ratio (11 kV side)
- Star side → CTs in delta; delta side → CTs in star.
- Equate the currents in the pilot wires.
Problem 7. CT ratio on the 33 kV side when the given CTs are on the delta side Practice problem
A 3-phase, 33/6.6 kV, star/delta transformer is protected by the Merz-Price circulating-current system. If the CTs on the low-voltage (6.6 kV, delta) side have a ratio of 300/5, find the ratio of the CTs on the high-voltage (33 kV, star) side.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| T | 33/6.6 kV, Y–Δ | |
| CT6.6 | 300/5 | on delta side |
- CT ratio (33 kV side)
- CTs in delta → their secondary = pilot current/√3.
- Compare with the earlier 11/132 kV problem, which has the same structure.
Problem 8. Unprotected part of a stator winding (earthing resistance 7.5 Ω) Practice problem
A star-connected, 3-phase, 10 MVA, 6.6 kV alternator is protected by the Merz-Price circulating-current principle using 1000/5 A current transformers. The star point is earthed through a resistance of 7.5 Ω. If the minimum operating current of the relay is 0.5 A, find the percentage of each phase of the stator winding that is unprotected against earth faults at normal voltage.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 6.6 kV | |
| CT | 1000/5 | |
| Rn | 7.5 Ω | earthing resistance |
| Irelay | 0.5 A | minimum |
- unprotected winding
- x = Ipick-up(primary) × R/Vph.
- Lower R → less unprotected winding.
Problem 9. Unprotected winding and the resistance needed for 90 % protection Practice problem
A 10 MVA, 6.6 kV, 3-phase star-connected alternator is protected by a Merz-Price circulating-current system. The CT ratio is 1000/5, the minimum operating current of the relay is 0.75 A and the neutral earthing resistance is 6 Ω. Find (i) the percentage of each stator winding that is unprotected against earth faults at normal voltage and (ii) the minimum earthing resistance that gives protection to 90 % of the winding.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 6.6 kV | |
| CT | 1000/5 | |
| Irelay | 0.75 A | |
| Rn | 6 Ω |
- unprotected %
- R (for 90 % protection)
- R = x Vph/Ipick-up.
- Coverage improves as R falls.
Problem 10. Earthing resistance for 85 % protection with a 20 % earth-fault setting Practice problem
A star-connected, 3-phase, 10 MVA, 6.6 kV alternator is protected by circulating-current protection, with the star point earthed through a resistance r. Estimate r if 85 % of the stator winding is to be protected against earth faults. Assume an earth-fault setting of 20 % and neglect the impedance of the winding.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 6.6 kV | |
| setting | 20 % | of full load |
| protection | 85 % | of winding |
- r (earthing resistance)
- Setting % × full-load current = primary pick-up.
- x Vph = Iset × R.
Problem 11. Unprotected winding when the alternator reactance is included Practice problem
A 10 MVA, 11 kV, 3-phase star-connected alternator is protected by the Merz-Price balance-current system, which operates when the out-of-balance current exceeds 20 % of full-load current. Find what portion of the winding is unprotected if the star point is earthed through a resistance of 9 Ω. The reactance of the alternator is 2 Ω.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 10 MVA | |
| V | 11 kV | |
| setting | 20 % | of full load |
| Rn | 9 Ω | |
| X | 2 Ω | alternator |
- unprotected %
- Fault-path impedance = √(R² + (xX)²).
- Usually R dominates.
Problem 12. Protected percentage and the resistance for 95 % protection (25 MVA, 11 kV) Practice problem
The neutral of a 25 MVA, 11 kV alternator is grounded through a resistance of 5 Ω. The relay is set to operate when there is an out-of-balance current of 2 A, and the CTs have a ratio of 1000/5. Neglecting the reactance of the alternator, find (i) the percentage of stator winding protected against an earth fault and (ii) the minimum value of earthing resistance to protect 95 % of the winding.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| S | 25 MVA | |
| V | 11 kV | |
| Rn | 5 Ω | |
| Irelay | 2 A | |
| CT | 1000/5 |
- protected %
- R (for 95 %)
- Protected % = 100 − x.
- High coverage ↔ low earthing resistance ↔ high fault current.
Problem 13. Ratings of a circuit breaker BCPCL
A circuit breaker is rated 1500 A, 1000 MVA, 33 kV, 3 s, 3-phase oil circuit breaker. Find (i) the rated normal current, (ii) the breaking capacity, (iii) the rated symmetrical breaking current, (iv) the rated making current, (v) the short-time rating and (vi) the rated service voltage.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| rating | 1500 A, 1000 MVA, 33 kV, 3 s | 3-phase OCB |
- ratings (i)–(vi)
Short-circuit current: making (first peak) and breaking currents.- Ibreak = MVA/(√3 kV).
- Imake = 2.55 × Ibreak (= 1.8 × √2).
- Short-time rating usually for 1 s or 3 s.
Problem 14. Peak restriking voltage, frequency and RRRV of an 11 kV breaker Practice problem
A 50 Hz, 11 kV, 3-phase alternator with an earthed neutral has a reactance of 5 Ω per phase and is connected to a bus-bar through a circuit breaker. The distributed capacitance up to the breaker between phase and neutral is 0.01 μF. Determine (i) the peak restriking voltage across the breaker contacts, (ii) the frequency of oscillations and (iii) the average rate of rise of restriking voltage up to the first peak.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| f | 50 Hz | |
| V | 11 kV | |
| X | 5 Ω | per phase |
| C | 0.01 μF | phase to neutral |
- Vpeak
- fn
- RRRV
- Peak restriking voltage ≈ 2 × peak recovery voltage.
- fn = 1/(2π√LC); tpeak = π√LC.
- RRRV = peak/tpeak.
Problem 15. Average RRRV and natural frequency from a short-circuit test Practice problem
In a short-circuit test on a circuit breaker the following readings were obtained on a single-frequency transient: time to reach the peak restriking voltage 50 μs; peak restriking voltage 100 kV. Find the average RRRV and the frequency of oscillations.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| tp | 50 μs | time to peak |
| Vp | 100 kV | peak restriking voltage |
- RRRV
- fn
- tpeak = 1/(2fn).
- RRRV = Vpeak/tpeak.
Problem 16. Voltage across the contacts when a magnetising current is chopped Practice problem
An air-blast circuit breaker interrupting a transformer magnetising current of 11 A (r.m.s.) chops the current at an instantaneous value of 7 A. If the inductance and capacitance of the circuit are 35.2 H and 0.0023 μF, find the voltage that appears across the breaker contacts. Assume that all the inductive energy is transferred to the capacitance.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| i | 7 A | chopped current |
| L | 35.2 H | |
| C | 0.0023 μF |
- e (contact voltage)
- Current chopping: e = i√(L/C).
- Air-blast breakers are prone to chopping.
Problem 17. Radius of a fuse wire for a lower fusing current Practice problem
A fuse wire of circular cross-section with a radius of 0.8 mm blows at a current of 8 A. Find the radius of a wire of the same material that will blow at 1 A.
Show step-by-step solution
| Symbol | Value | Meaning |
|---|---|---|
| r₁ | 0.8 mm | |
| I₁ | 8 A | fusing current |
| I₂ | 1 A | new fusing current |
- r₂
- I ∝ r1.5 (Preece).
- Halving the current needs the radius × 0.63.
- DC Circuit Analysis
- Network Theorems
- RL, RC & RLC Transients
- Single-Phase AC Circuits
- Series & Parallel Resonance
- Power Factor Correction
- Three-Phase Circuits
- Transformer
- DC Generator & DC Motor
- Three-Phase Induction Motor
- Synchronous Machines
- Diode Circuits
- BJT Biasing & Amplifiers
- MOSFET & Power Electronics
- Op-Amp Circuits
- AM, FM & Analog Modulation
- Signals and Sampling
- PCM, Delta Modulation & TDM
- Digital Communication & Telecom
- Load Curves & Power Generation
- Per-Unit & Transmission Lines
- Faults & Symmetrical Components
- Protection & Switchgear (this post)
- Control Systems
- Digital Logic & Microprocessors
- Measurement, Mechanics & Aptitude
Topics shown in grey are coming soon. See every post in this series.